FL1B-B12RCA IDEC, FL1B-B12RCA Datasheet - Page 8

83C9515

FL1B-B12RCA

Manufacturer Part Number
FL1B-B12RCA
Description
83C9515
Manufacturer
IDEC
Datasheet

Specifications of FL1B-B12RCA

Peak Reflow Compatible (260 C)
No
Signal Input Type
AC/DC Voltage
Output Type
Relay
Supply Voltage Max
24V
No. Of Digital Inputs
8
Leaded Process Compatible
No
No. Of Digital Outputs
4
Rohs Compliant
No
H
Specifications
H-8
Input
Network
Variable
Output
Network
Variable
Configuration
Property
Operating Temperature
Operating Humidity
Storage Temperature
Storage Humidity
Rated Power Voltage
Allowable Voltage Range
Current Draw
Dielectric Strength
Insulation Resistance
EMC
Vibration Resistance
Shock Resistance
Dimensions
Mounting Style
Degree of Protection
Terminal Style
Weight
Communication System
Transceiver
Topology
Transmission Rate
Neuron Chip
CPU Clock Frequency
Transmission Distance
Electrostatic
Discharge
Burst Pulses
SNVT_obj_request: (Quantity 1)
SNVT_switch: (Quantity 14)
SNVT_occupancy: (Quantity 2)
SNVT_temp_p: (Quantity 1)
SNVT_lux: (Quantity 1)
SNVT_lev_percent: (Quantity 6)
SNVT_obj_status: (Quantity 1)
SNVT_switch: (Quantity 8)
SNVT_occupancy: (Quantity 2)
SNVT_tod_event: (Quantity 2)
SCPTmaxSendTime:
www.idec.com
0 to 55°C (no freezing)
10 to 85% RH (no condensation)
–40 to +70°C (no freezing)
10 to 85% RH (no condensation)
24V AC/DC
20.4 to 26.4V AC, 20.4 to 28.8V DC
33 mA max.
500V DC, 1 minute
(between power terminal and dead parts)
10 M minimum
(500V DC megger between power terminal and dead parts)
8 kV air discharge
6 kV contact discharge
2 kV (power terminal)
5 to 9 Hz, amplitude 3.5 mm
9 to 150 Hz, 9.8 m/s
150 m/s
35.5W 90H 58D mm
DIN rail or panel surface
IP20
Screw-cage clamp terminal
85g
LON
FTT-10A
Bus topology, free topology
78 kbps
TMPN3120FE5M (Toshiba)
20 MHz
Bus topology: 1400m
(only FTT-10A transceiver, using Level 4 AWG22 cable)
Free topology: 500m total, 400m between nodes
(when using Level 4 AWG22 cable)
®
system
2
2
Request object mode
Switch light, alarm, window
contact, free inputs/outputs
Occupancy
Room temperature (°C)
Brightness - lighting level (lux)
Position (%)
Output object status
Switch light, alarm, window
contact, free inputs/outputs
Occupancy
Scheduler program
Just current state
Send heartbeat (Q5 to Q16)
Specifications con’t
USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IDEC SmartRelay

Related parts for FL1B-B12RCA