OSP-V16-23-16-N1 Orion Fans, OSP-V16-23-16-N1 Datasheet

no-image

OSP-V16-23-16-N1

Manufacturer Part Number
OSP-V16-23-16-N1
Description
PDU 16OUT RACK 230V W/SENSORS
Manufacturer
Orion Fans
Series
-r
Datasheet

Specifications of OSP-V16-23-16-N1

Voltage - Input
230VAC
Features
Circuit Breaker
Ac Input Connector
IEC 320-C20
Connector - Ac Output
IEC 320-C13 (14), C19 (2)
Ac Outlets
16
Cord Length
9.8' (3m)
Mounting Type
Rack Mount
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
1053-1430
Orion Fans
10557 Metric Drive
Dallas, TX 75243
800.323.2439
Features
Current Meter
Power Monitor
Protocols
Outlet Control
Power Delay
Alarm Thresholds
Event Alert
Specification:
Regulatory Approvals:
UL 60950-1, UL Listed, CSA, cUL Listed, CB by UL
CE, EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3
C-Tick AS/NZS CISPR 22: 2006
FCC Part 15 Class A, ICES-003
General
Output: (14) IEC320 C13
Input: (1) IEC320 C20 Inlet;
Enclosed IEC320 C19 to C20 Power
Cord 3 Meters long
Protection (1) 16 Amp Circuit Breaker
(2) IEC320 C19
Switched PDU
Input (left)
MODEL:
Digital True RMS Current Meter
Remote Total Power Monitoring by Meter, Web, SNMP, Free Bundle Software
http, https, SNMP, DHCP, UDP
Individual Outlet Control
Power On/Off Sequence can be Defined
User-Defined Alarm Thresholds for Warning and Overload
Email, Trap, Audible Alarm
Communication
SSL Indication (1) Yellow LED
DHCP Indication (1) Green LED
Output Status (16) Red LED
Network (1) RJ45 for Ethernet
Current Meter 3 Digits Seven Segments
for True RMS Meter
Range: 0A ~ 20A
Resolution: 0.1A
Precision: +/-2%+/-0.1 Amp
OSP-V-16-23-16-N1
Operation
Nominal Voltage 230V
Voltage 200V~ 240V full range
Frequency 50/60HZ full range
Max. Output Current 16 Amp
(UL derated 12 Amp)
Temperature 0 ~ 40 Celsius degree
Humidity 0% ~ 90%
Size 56 x 1245 x 44 mm
Weight 4 kg
MODEL NUMBER:
information and data are subject to
change without prior notification.
A division of Knight Electronics,