EG1R-CVM EDWARDS SIGNALING PRODUCTS, EG1R-CVM Datasheet - Page 2

no-image

EG1R-CVM

Manufacturer Part Number
EG1R-CVM
Description
20H6023
Manufacturer
EDWARDS SIGNALING PRODUCTS
Datasheet
FIRE ALARM EQUIPMENT
TECHNICAL INFORMATION
27/32”
2 3/4”
(21mm)
(70mm)
4 1/2”
(114mm)
GENESIS CHIMES & CHIME/STROBES
Housing
Red or white textured UV stabilized, color impregnated engineered plastic. Exceeds 94V-0 UL flammability rating.
Lens
Optical grade polycarbonate
Mounting
Flush: 2 1/2" (64mm) deep one-gang box
(indoor wall mount only)
Surface: Edwards model 27193 surface mount box, wiremold box, or equivalent surface-mount box
With optional trim plate: One-gang, two-gang, four-inch square, octagonal, or European single-gang box
2
2
Wire Connections
Screw terminals: separate polarized inputs for speaker & strobe, #18 to #12 AWG (0.75 mm
to 2.5 mm
) wire size
Operating Environment
32-120° F (0-49° C) ambient temperature; 93% relative humidity.
Agency Approvals
UL1971, UL1638, UL464, CE, FCC, (MEA, FM, CSFM pending).
(All models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule).
Operating Voltage
EG1-C Series chimes: Non-coded, filtered 16-33V DC or unfiltered 16-33V DC FWR
(or coded when chime set to single-stroke operation)
EG1-CVM Series chime-strobes: Non-coded, filtered 16-33V DC or unfiltered 16-33V DC FWR
(or coded (audible NAC only) when used with optional EG1M Signal Master)
Strobe Output Rating
UL 1971, UL 1638, selectable 15 cd, 30 cd, 75 cd, or 110 cd output
Strobe Flash Rate
One flash per second (fps) with optional EG1M Signal Master indefinitely within 10 milliseconds
(or self synchronized within 200 milliseconds over 30 minutes on common circuit without EG1M).
Compatible Sync Module
EG1M-RM
Chime Pulse Rate
Non-coded operation - one stroke per second synchronized with optional EG1M Signal Master, indefinitely
within 10 milliseconds (or self-synchronized within 200 milliseconds over thirty minutes on a common circuit
without the EG1M Signal Master); coded operation - up to one stroke per second (EG1M Signal Master required)