CS405-7A-T EDWARDS SIGNALING PRODUCTS, CS405-7A-T Datasheet

no-image

CS405-7A-T

Manufacturer Part Number
CS405-7A-T
Description
20H4968
Manufacturer
EDWARDS SIGNALING PRODUCTS
Datasheet
Harsh Environment
Strobes
CS405-7A, -8A
Overview
CS405 Series strobes are specially designed for use with compat-
ible life safety communication and control equipment to alert the
hearing impaired of a life safety event. Strobes are available with
15 cd, 15/75 cd, 30 cd, 60 cd, and 110 cd effective flash intensity.
They are fully compatible with Genesis signals.
CS405 Series strobes exceed UL synchronization requirements
(within 10 milliseconds other over a two-hour period) when
used with a separately-installed EG1M Signal Master, or E-NAC
Synchronization Module, or when powered by suitably enabled
booster power supplies and control panels.
The flash from CS405 Series strobes can be noticed from almost
any position in the room, corridor, or large open space. CS405
Series strobes are UL 1971 listed with both wall and ceiling cd
intensity ratings (see Specifications). This is useful in areas where
the Authority Having Jurisdiction (AHJ) permits ceiling-mount
strobes.
CS405 Series strobes are designed for 16 to 33 Vdc operation
and must be connected to signal circuits that output a constant
(not pulsed) voltage. A diode is used to allow full signal circuit
supervision and polarized connections are made to terminals that
accept up to #12 AWG (2.5mm²) wire.
The strobe front plate is of steel construction finished with durable
baked epoxy polyester powder-coat paint.
Page 1 of 4
Standard Features
• UL 1971-listed synchronizing strobe
• Genesis-compatible
• Approved for public and private mode applications
• Rugged red or white steel front plate
• Rated for wall or ceiling installation
• Field changeable field markings
• Fits 4-inch square flush box
• UL/ULC rated outdoor option
Integrity strobes synchronize to the latest UL 1971 require-
ments when used with a synchronization source.
All Genesis and Integrity strobes on the same circuit meet UL
1971 synchronization requirements when used with an external
control module.
UL 1971-listed as signaling devices for the hearing impaired
and UL 1638-listed as protective visual signaling appliances.
Ideal for outdoor or harsh environments.
Lens language or standard “FIRE” marking is easily changed
with optional LKW and LKC series lens kits.
Ideal for retrofit and renovation projects.
Edwards Signaling Catalog u
Not to be used for installation purposes.
CS405 Series
D A T A S H E E T
Strobes, Horns, Bells, Chimes
S85001-0305
Patented
Issue 8
MEA

Related parts for CS405-7A-T

CS405-7A-T Summary of contents

Page 1

... Specifications). This is useful in areas where the Authority Having Jurisdiction (AHJ) permits ceiling-mount strobes. CS405 Series strobes are designed for Vdc operation and must be connected to signal circuits that output a constant (not pulsed) voltage. A diode is used to allow full signal circuit supervision and polarized connections are made to terminals that accept up to #12 AWG (2.5mm² ...

Page 2

... Consult with your Authority Having Jurisdiction for details. As part of the Enhanced Integrity line of products, CS405 Se- ries strobes exceed UL synchronization requirements (within 10 milliseconds other over a two-hour period) when used with a synchronization source ...

Page 3

... Horizontal UL min UL min UL min Average Average Average Average Average Vertical Vertical -90° -90° -90° CS405-8A, CS405-8A 90° Horizontal 110cd 90° 90° 110cd wall 60cd ceiling Not to be used for installation purposes. 110 cd (-8A) Horizo - - - - - -90 60 100 ...

Page 4

... UTC Fire & Security. All rights reserved. Page Ordering Information Catalog Number Description Outdoor Listed Strobes CS405-7A-T Strobe, 15/75, Outdoor, Red CS405-8A-T Strobe, 110 cd, Outdoor, Red Mounting Accessories 449 Surface Mount Box, Gray, Outdoor, (‘CS’ models only) Ship Wt. ...

Related keywords