7P.20.9.350.0020 FINDER, 7P.20.9.350.0020 Datasheet
7P.20.9.350.0020
Specifications of 7P.20.9.350.0020
Related parts for 7P.20.9.350.0020
7P.20.9.350.0020 Summary of contents
Page 1
Features SPD Type 1+2 Surge arrester range - single phase system / three phase system Surge arresters suitable in low-voltage applications • in order to protect equipment against overvoltage by direct lightning strike, induction overvoltage and switching overvoltage ...
Page 2
Features SPD Type 1+2 Surge arrester range - three phase system (230/400 V) Surge arresters suitable in low-voltage applications • in order to protect equipment against overvoltage by direct lightning strike, induction overvoltage and switching overvoltage installed at ...
Page 3
Features SPD Type 1 Surge arrester range with “Low U -System” – Single phase / three phase system p Surge arrester suitable for 230/400 V system/ • applications to prevent overvoltage effects caused by direct or indirect lightning strikes. To ...
Page 4
Features SPD Type 1 Surge arrester range with “Low U -System” – three phase system p Surge arrester suitable for 230/400 V system/ • applications to prevent overvoltage effects caused by direct or indirect lightning strikes installed at ...
Page 5
Features SPD Type 2 Surge arrester range - single phase systems Surge arrester suitable for 230V system/ • applications Protects equipment against overvoltage caused • by lightning strikes or switching transients To be installed at the boundary of LPZ 1-LPZ ...
Page 6
Features SPD Type 2 Surge arrester range - three-phase systems Surge arrester suitable for 230/400V • system/applications Protects equipment against overvoltage caused • by lightning strikes or switching transients To be installed at the boundary of LPZ 1-LPZ 2 • ...
Page 7
... A 200 V DC — 100 A 200 V DC 125 A gL/gG — 7P.20.9.350.0020 7P.20.1.000.9020 7P.20.9.350.0020 °C solid cable 2 1x1...1x50 1x 17...1x1 1 CO (SPDT) 0.5 - 0.1 250 solid cable stranded cable solid cable 2 1.5 1.5 1 7P.23.9.000.1020 SPD Type 2 (3 varistors) for • ...
Page 8
... Features SPD Type 3 Surge arrester for incorporation within socket outlets Provides easy additional surge protection for • existing 230 V sockets Protects electric and electronic equipment • against pulse overvoltage Combined varistor + spark-gap protection • (avoiding earth leakage current) Acoustical indication of varistor status • ...
Page 9
... Maximum discharge current (8/20 μs) (I Voltage protection level (U Response time ( Maximum overcurrent protection Replacement varistor and Spark-Gap modules 7P.20.8.275.0020 7P.20.9.350.0020 7P.20.9.500.0020 7P.20.1.000.0020 7P.20.1.000.9020 Maximum operating voltage (U Nominal discharge current (8/20 μs) (I Maximum discharge current (8/20 μs) (I Voltage protection level (U Response time (t ...
Page 10
Series - Surge Protection Device (SPD) - Dimensional data Type 7P.09 Screw terminal Type 7P.02 Screw terminal Type 7P.03 Screw terminal Type 7P.04 Screw terminal 10 Outline drawings Type 7P.01 Screw terminal ...
Page 11
Series - Surge Protection Device (SPD) - Dimensional data Type 7P.05 Screw terminal Type 7P.12 Screw terminal Type 7P.14 Screw terminal Type 7P.15 Screw terminal Outline drawings Type 7P.13 Screw terminal 11 ...
Page 12
Series - Surge Protection Device (SPD) - Dimensional data Type 7P.21 Screw terminal Type 7P.23.8 Screw terminal Type 7P.23.9 Screw terminal Type 7P.26 Screw terminal Type 7P.20 Replaceable module 12 Outline drawings Type 7P.22 Screw terminal Type 7P.24 Screw ...
Page 13
Installation example - SPD Type TT-SINGLE PHASE SYSTEM - SPD UP-STREAM OF RCD TT-THREE PHASE SYSTEM - SPD UP-STREAM OF RCD 7P Series - Surge Protection Device (SPD) TT-SINGLE PHASE SYSTEM - SPD UP-STREAM OF RCD TT ...
Page 14
Installation example for SPD Type 1 and Type 2 - Single phase TT-SINGLE PHASE SYSTEM - SPD UP-STREAM OF RCD Mandatory with LPS Note: suggested RCD type Series - Surge Protection Device (SPD TN-S SINGLE ...
Page 15
Installation example for SPD Type 1 and Type 2 - Three phase TT-THREE PHASE SYSTEM - SPD UP-STREAM OF RCD Mandatory with LPS TN-S THREE PHASE SYSTEM - SPD DOWN-STREAM OF OVERCURRENT PROTECTION 7P Series - Surge Protection Device (SPD) ...
Page 16
Installation examples - photovoltaic 16 7P Series - Surge Protection Device (SPD) ...
Page 17
... Figure 1: Ideal operation of an SPD SPD technologies Finder surge voltage protectors use either varistors or spark gaps. Varistor: this can be considered as a variable resistance that at nominal voltage has a very high ohmic value. But the resistance rapidly falls to near zero as the voltage surges. In this way the varistor applies a near short circuit which clamps the surge voltage ...
Page 18
... Finder SPD specified as 275 Voltage protection level: This is the highest voltage level seen across the SPD during its intervention. For example, for Finder SPD Type 2, this means that a 4kV overvoltage would be limited by the SPD to a maximum 1.2 kV. Consequently, electronic devices such as PC, TV, stereo, etc ...
Page 19
Protection against SPD’s short circuits is provided by the overcurrent protective devices (fuses type gL/gG) recomended. If the overcurrent protective devices F1 (which are part of the installation) have a rating smaller than or equal to the maximum recommended rating ...
Page 20
... LPS (with or without solar panels Series - Surge Protection Device (SPD) SPD fuse protection The Finder SPD can break a 100 A DC (@200 V DC) current. This means that for short circuit current of string (Isc) lower than 100 not necessary to install a back up fuse. = 420 V, ...