Datasheet

Specifications of DLJ615A2

Lead Free Status / Rohs Status
Supplier Unconfirmed
PRoDuCtioN tEsts
Tests are conducted in accordance
with IEEE Std 386
Tests are conducted in accordance with
Cooper Power Systems re quire ments.
TABLE 1
Voltage Ratings and Characteristics
Voltage ratings and characteristics are in accordance
with applicable IEEE Std 386 ™ -2006 standard require-
ments.
oRDERiNG iNFoRMAtioN
To order the 600 A, 15 kV Class Clēēr
Loadbreak Connector System, refer to
Table 3.
Each complete 600 A, 15 kV Class
Clēēr Loadbreak Connector
(LCND2DLJ615) Assembly Kit
contains:
Standard Voltage Class
Maximum Rating Phase-to-
Phase
Maximum Rating Phase-to-
ground
AC 60 hz 1 Minute Withstand
DC 15 Minute Withstand
BIL and Full Wave Crest
Minimum Partial Discharge
Extinction Voltage
AC 60 hz 1 Minute Withstand
– 34 kV
Minimum Partial Discharge
Extinction Voltage
– 11 kV (3pc Sensitivity)
Physical In spec tion
Periodic Dissection
Periodic Fluoroscopic Analysis
(2) 600 A, 15 kV, Loadbreak/
Deadbreak 2-Position Junctions
(1) 600 A, 15 kV, Loadbreak "C"
Connector
(1) Stainless steel mounting bracket
(1) Stainless steel hardware kit
(In-line bracket only)
(2) ground lugs (#8 sol to 2/0 str.)
Silicone Lubricant
Installation Instruction Sheet
Description
-2006 standard.
15
8.3
34
53
95
11
kV
14.4
TABLE 2
Current Ratings and Characteristics
Current ratings and characteristics are in ac cor dance with applicable IEEE Std 386 ™ -2006 standard requirements.
TABLE 3
600 A 15 kV Clēēr Loadbreak Connector System
PRotECtiVE CAP
The 600 A, 15 kV Clēēr loadbreak
protective cap is an accessory device
designed to electrically insulate and
mechanically seal the 600 A Cleer
loadbreak bushing interfaces.
It incorporates Cooper Power Systems
field proven POSI-BREAK technology,
providing a layer of insulation over the
conductive internal insert and an
insulative sleeve on the base of the
probe. This results in increased strike
distance greatly reducing the possibility
of partial vacuum flashovers and
providing superior switching
performance and reliability.
The protective cap is fully shielded and
submersible and meets the applicable
requirements of IEEE Std 386™ -2006
standard. Refer to Installation
Instruction Sheet, S600-100-2 for
details.
Description
600 A Loadbreak Interface
Continuous
Current
Loadbreak
Switching
Fault Closure
4 hour
Overload Current
Short Time
Current
IEEE Std 386™ -2006 standard 600 A, 15/25 kV Deadbreak Interface
Continuous
Current
4 hour
Overload Current
Short Time
Current
Description
600 A 15 kV Loadbreak Connector Assembly includes: two loadbreak/
deadreak junctions with loadbreak "C" connector assembled in a In-Line
SS. Bracket
600 A 15 kV Loadbreak Connector assembly includes: two loadbreak/
deadbreak junctions with loadbreak "C" connector assembled in a Square
SS. Bracket
600 A, 15 kV, Loadbreak/Deadbreak 2-position Junction (aluminum)
600 A 15 kV, Insulated Loadbreak Protective Cap
600 A, 15 kV Loadbreak "C" Connector
600 A rms
Ten make and break operations at 600 A at 14.4 kV Phase-Phase
Three make and break operations at 900 A at 14.4 kV Phase-Phase
16 kA rms symmetrical at 14.4 kV Phase-Phase after ten 600 A loadbreak
switching operations for 0.17 seconds
16 kA rms symmetrical at 14.4 kV Phase-Phase after three 900 A loadbreak
switching operations for 0.17 seconds
900 A rms
16 kA rms symmetrical for 0.17 seconds (limited by fault closure rating)
10 kA rms symmetrical for 3.0 seconds
600 A rms
900 A rms
16 kA rms symmetrical for 0.17 seconds
10 kA rms symmetrical for 3.0 seconds
Amperes
Figure 4.
600 A, 15 kV Clēēr Loadbreak Connector
Protective Cap.
Catalog Number
LCN2DLJ615A2ILB
LCN2DLJ615A2SQB
DLJ615A2
LPC615
LCN615
600-100
3

Related parts for DLJ615A2