LCN2DLJ615A2SQB Cooper/Bussmann, LCN2DLJ615A2SQB Datasheet

no-image

LCN2DLJ615A2SQB

Manufacturer Part Number
LCN2DLJ615A2SQB
Description
Manufacturer
Cooper/Bussmann
Datasheet

Specifications of LCN2DLJ615A2SQB

Lead Free Status / Rohs Status
Supplier Unconfirmed
Loadbreak Apparatus
Connectors
600 A 15 kV Class Clēēr Loadbreak Connector system
GENERAL
The Cooper Power Systems Clēēr™
Loadbreak Connector System is a 600
A loadbreak device rated for operation
on 15 kV class systems. It is used to
provide a visible break and visible
ground on 600 A network and
distribution systems without having to
remove 600 A terminations and move
heavy cable. The Clēēr Loadbreak
Connector System Is fully shielded,
submersible and meets the applicable
requirements of IEEE Std 386™ -2006
standard – “Separable Insulated
Connector Systems”.
Many configurations are possible with
this connector system. Under normal
operating conditions, the current path
is through one of the 600 A loadbreak/
deadbreak 2-position junctions
(DLJ615), through the 600 A loadbreak
“C” (LCN) connector and through the
second 600 A loadbreak/deadbreak
junction.
When isolating underground cable,
with the system energized or
de-energized, with or without rated
load current, with the use of a
clampstick, the LCN connector can be
removed. A 600 A loadbreak protective
cap (LPC615) can then be installed on
the two exposed loadbreak interfaces.
All bushings of the connector system
are then insulated and deadfront. If a
600 A termination with a 200 A
reducing tap plug is used on the IEEE
Std 386™ -2006 standard 600 A
15/25 kV deadbreak interfaces of the
junction, a grounding elbow can be
installed, providing a visible ground. It
is then safe to perform work on the
underground cable.
CoNstRuCtioN
The Clēēr 600 A Loadbreak Connector
System includes two loadbreak/
deadbreak junctions, each consisting
of one Cooper Power Systems
exclusive 600 A loadbreak interface
and one IEEE Std 386™ -2006
standard 600 A deadbreak interface.
The 600 A loadbreak “C” (LCN)
connector incorporates Cooper Power
Systems field proven POSI-BREAK™
technology, providing a layer of
insulation over the conductive internal
inserts and an insulative sleeve on the
base of the probes. This results in
0711 • New Issue
Figure 1.
600 A 15 kV Class Clēēr Loadbreak Connector System.
increased strike distance greatly
reducing the possibility of partial
vacuum flashovers and providing
superior switching performance and
reliability.
iNtERCHANGEABiLitY
The IEEE Std 386™ -2006 standard
600 A deadbreak interfaces are
interchangeable with 600 A
terminations currently available from all
other manufacturers that also comply
with IEEE Std 386™ -2006 standard.
iNstALLAtioN
No special tools are required for
installation.
The Clēēr 600 A Loadbreak Connector
System is available in both in-line and
square configurations. It is designed to
be mounted directly to a vault or
manhole walls or inside an enclosure.
The in-line junction assembly has an
adjustable stainless steel bracket for
mounting at various operating angles.
600 A, BOL-T, T-OP II or BT-TAP cable
terminations are assembled to the
source and load side 600 A deadbreak
bushings following the instructions
provided in those kits. Using a
clampstick, the loadbreak "C"
connector (LCN) is assembled to the
two center 600 A loadbreak interfaces
to complete the current path. Refer to
mounting dimensions on page 5 and
installation instructions, Service
Information, S600-100-1 for details.
600-100
Electrical Apparatus
1

Related parts for LCN2DLJ615A2SQB

LCN2DLJ615A2SQB Summary of contents

Page 1

... The IEEE Std 386™ -2006 standard 600 A deadbreak interfaces are interchangeable with 600 A terminations currently available from all other manufacturers that also comply with IEEE Std 386™ -2006 standard. iNstALLAtioN No special tools are required for installation. The Clēēr 600 A Loadbreak Connector System is available in both in-line and square configurations ...

Page 2

Class Clēēr Loadbreak Connector System 600 LOADBREAK BUShINg IEEE Std 386™ -2006 STANDARD 600 A, 15/25 kV DEADBREAK BUShINg Figure 2. 600 Clēēr Loadbreak Connector System with In-line Bracket. 600 ...

Page 3

... The protective cap is fully shielded and submersible and meets the applicable requirements of IEEE Std 386™ -2006 standard. Refer to Installation Instruction Sheet, S600-100-2 for details. 600-100 Catalog Number LCN2DLJ615A2ILB LCN2DLJ615A2SQB DLJ615A2 LPC615 LCN615 Figure 4. 600 Clēēr Loadbreak Connector Protective Cap. 3 ...

Page 4

Class Clēēr Loadbreak Connector System tYPiCAL CoNFiGuRAtioNs in-Line Bracket configurations SOURCE Figure 5. 600 Loadbreak Connector System with (2) BOL-T terminations. BOL-T TERMINATION SOURCE Figure 6. 600 Loadbreak Connector System ...

Page 5

Figure 9. Dimensional drawing shows mounting configurations for in-line bracket. Note: Dimensions given are for reference only. 13.79 (350.3 mm) 10.21 (259.3 mm) 4.00 (101.6 mm) 15.30 (388.6 mm) 7.90 ...

Page 6

Class Clēēr Loadbreak Connector System ADDitioNAL iNFoRMAtioN Refer to the following reference literature for application recommendations: S600-100-1, 600 Class Clēēr Loadbreak Connector System Installation Instructions S600-100-2, 600 Class Clēēr Loadbreak ...

Page 7

600-100 7 ...

Page 8

... Cooper Industries. All Rights Reserved. Cooper Power Systems, Clēēr, BOL-T, T-OP, POSI-BREAK, and BT-TAP are valuable trademarks of Cooper Industries in the U.S. and other countries. You are not permitted to use the Cooper Trademarks without the prior written consent of Cooper Industries. ...