WD30-ME Omron, WD30-ME Datasheet - Page 26

no-image

WD30-ME

Manufacturer Part Number
WD30-ME
Description
WIRELESS DEVICENET MASTER UNIT
Manufacturer
Omron
Datasheet

Specifications of WD30-ME

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
WD30ME
14
1-4
Application Limitations
Application Limitations
1,2,3...
The wireless unit is not designed to be compatible with every type of applica-
tion that uses DeviceNet. Do not use the unit with the following applications.
1. Applications that require real-time control
2. Applications that use FINS message communications
CS1
Wireless master
station
Wireless slave
station
Do not use the unit with applications that require real-time control. In par-
ticular, it cannot be used under conditions that require responsiveness
greater than that outlined in "Section 9 Communications Timing".
Applications that do not require real-time control, such as indicators, equip-
ment error monitors, and parts picking operation, are recommended.
Wireless units do not support FINS message communications. For exam-
ple, although CX-Programmer Ver. 2.1 and later versions support online
connection (i.e., remote programming and monitoring) to PLCs on De-
viceNet networks (e.g., PLCs with CS/CJ-series DeviceNet Units or pro-
grammable slaves), this functionality is not available via wireless units.
Lower DeviceNet network
CX-Programmer
installed on a
computer
Upper DeviceNet network
Programmable slave
Section 1-4

Related parts for WD30-ME