A16-30-10-110V-50HZ ABB, A16-30-10-110V-50HZ Datasheet - Page 31

no-image

A16-30-10-110V-50HZ

Manufacturer Part Number
A16-30-10-110V-50HZ
Description
POWER RELAY, 110VAC, 17A, 3PST, PANEL
Manufacturer
ABB
Datasheet

Specifications of A16-30-10-110V-50HZ

Operating Voltage
690VAC
Switching Power Ac1
7.5kW
Switching Power Ac3
7.5kW
Switching Current Ac1
30A
Switching Current Ac3
17A
Load Current Inductive
17A
Load Current Resistive
30A
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
15-16
15-18
TE 5S
R
U
t1
Equivalent diagram
Front face
0.8 ... 8s
Star-Delta Timer
t1
U
R
0.1
A1
16
t1+t2
TE5S-*
Chart
15
t1
18
TE5S
6 ... 60s
0.5
1.0
A2
t2 = 50ms
Accessories
for A contactors
TE5S electronic timer for wye-delta starters
Electronic timer
Application
Utilization
When used in wye-delta starters, the TE5S lags the wye connection and provides a lapse of 50 ms before the switchover to
the delta connection.
Description
According to the type of device chosen, the electronic circuit has a 24 VAC/VDC, 110 – 120 VAC or 220 – 230 VAC supply.
An output relay with reversing contact ensures high current switching. A two-position switch allows selection of one of the
two time delay ranges: 0.8 to 8 s or 6 to 60 s. The 0.1 to 1.0 adjustable knob allows an initial setting without steps within the
previously selected range which can then be adjusted using a stopwatch.
Note: We recommend that you allow for temperature drift for the fi nal adjustment of the time delay setting. Drift: – 0.2% per
°C. For example, a setting made at 20 °C will yield a time delay shorter by 7% at 55 °C in an enclosure. ( – 0.2% per °C i.e.
– 0.2 x 35 = – 7%).
The TE5S, which is not affected by these settings, establishes a fi xed “lapse” of 50 ms between the opening of contact 15 –
16 and the closing of contact 15 – 18. It is this time delay that prevents from arc short-circuit during wye to delta switching.
Operation
On energization, the green U indicator light (voltage applied) comes on. Contact 15 – 16 then immediately moves to the
closed position.
Count-down of the programmed time immediately commences.
When the time delay has elapsed, contact 15 – 16 opens and at the same time the 50 ms lapse, t2, begins after which
contact 15 – 18 moves to the closed position. The yellow R indicator light comes on.
On de-energization, the U and R indicator lights go out and, after the 250 ms resetting time, the device is ready for a new
cycle.
Mounting
Mounts on 35mm DIN rail.
A9 – AF750
contactors
For
Discount schedule ABA
110 – 120 AC
220 – 240 AC
380 – 440 AC
Rated control
24 AC/DC
voltage U
V
c
Packing
piece
1
1
1
1
weight
0.080
0.080
0.080
0.080
Unit
kg
TE5S-24
TE5S-120
TE5S-240
TE5S-440
Catalog
number
1SXU 000 023 C0201
1
$ 120
price
List
1.31
1

Related parts for A16-30-10-110V-50HZ