5-24
Troubleshooting
a.7a0
Display
Overheat
Error
Occurs when the
control circuit
power supply is
turned ON.
Overheating of
radiation shield
occurs when the
main circuit power
supply is turned
ON, or during Ser-
vomotor operation.
Status when
error occurs
• Servo Driver is defective. • Replace the Servo
• An overload alarm has
• The load exceeds the
• The Servo Driver's ambi-
• Servo Driver is defective. • Replace the Servo
• An overload alarm has
• There is a faulty connec-
• Was the load excessive,
• The Servo Driver was
• The Servo Driver's fan is
been reset several times
by turning OFF the
power.
rated load.
ent temperature exceeds
55 ° C.
been reset several times
by turning OFF the
power.
tion between the Servo
Driver board and the Ser-
vomotor switch.
or was the regeneration
processing capacity
exceeded?
mounted in an unsuit-
able way (direction, spac-
ing). (Is there heat
radiation in the panel or
is there a heating effect
from the surroundings?)
stopped.
Cause of error
• Change the alarm reset
• Recheck the load condi-
• Reduce the Servo
• Change the alarm reset
• Replace the Servo
• Recheck the load and
• Reduce the Servo
• Replace the Servo
Driver.
method.
tions, the operating con-
ditions, and the
Servomotor capacity.
Driver's ambient temper-
ature to 55 ° C or below.
Driver.
method.
Driver.
operating conditions.
Driver's ambient temper-
ature to 55 ° C or below.
Driver.
Countermeasures
Chapter 5