NT-AL001 Omron, NT-AL001 Datasheet - Page 260

no-image

NT-AL001

Manufacturer Part Number
NT-AL001
Description
ADAPTER RS232C/RS-422A
Manufacturer
Omron
Datasheet

Specifications of NT-AL001

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
NTAL001
Inspection Method
Inspection and Cleaning
Power supply
voltage
Ambient envi-
ronmental con-
ditions
Mounting condi-
tions
Components
with limited lives
Inspected
Point
Fluctuation in power supply terminal
voltage
Ambient temperature (temperature in
the operation panel)
Ambient humidity (humidity in the
operation panel)
Presence/absence of dust
Looseness of mounting brackets, etc.
Connector connections of connecting
cable
Looseness of screws in external wir-
ing
Conditions of external connecting
cables
Brightness of the backlight
(NT631C only)
Note
Inspection Details
In normal environments, inspect the NT631/NT631C at intervals of between 6
months and a year. In environments that are extremely hot and humid, or very
dusty environments, shorten the inspection interval.
Items Required for The Inspection
Prepare the following items before starting the inspection.
Points Inspected
Inspect the following points to determine if there is any divergence from the
stated criteria. If there is, either improve the surrounding environment so that
the values fall within the stated range, or adjust the NT631/NT631C, for exam-
ple by re-tightening screws.
1. Do not disassemble for repairs or modification.
• Screwdrivers (Phillips, flat head)
• Tester (or digital voltmeter)
• Industrial alcohol
• 100% cotton cloth
• Hygrometer (required in some cases)
• Thermometer (required in some cases)
• Synchroscope (required in some cases)
• Pen-writing oscilloscope (required in some cases)
Permissible voltage fluctuation range
20.4 to 26.4 VDC (24 VDC –15% to
+10%)
0 to 50°C
35% to 85% RH
Dust must not be settled
To be no looseness
To be fully inserted and locked, with no
looseness
To be no looseness
Faults such as incipient disconnection
Must be sufficiently bright.
Backlight life:
(Under the normal range of ambient tem-
perature and humidity)
NT631C-ST141@-EV2: Approx.
25,000 hours or longer
NT631C-ST151@-EV2: Approx.
30,000 hours or longer
NT631C-ST152@-EV2/ST153@-EV3:
Approx. 50,000 hours or longer
(Brightness setting is not available for
the NT631C-ST151/152@-EV2/
ST153@-EV3 and the backlight can-
not be replaced.)
Criterion
Tester
Thermometer
Hygrometer
Visual inspection
Phillips screwdriver
Phillips screwdriver
Phillips screwdriver
Visual inspection
Visual inspection
Instrument
Inspection
Section 7-4
243