G79-O50C Omron, G79-O50C Datasheet - Page 3

no-image

G79-O50C

Manufacturer Part Number
G79-O50C
Description
50CM OUTPUT CABLE
Manufacturer
Omron
Datasheet

Specifications of G79-O50C

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
G79O50C
General
CPM2C Power Consumption
Use the following power consumption tables to calculate the total power
capacity required when using a CPM2C PLC. The rated output for the
CPM2C-PA201 AC Power Supply Unit is 15 W. Any surplus power not
required for the PLC directly can be used as service power supply for
sensors and other devices.
88
Item
Supply voltage
Operating voltage range
Power consumption (Add Ex-
pansion Unit consumption from
following tables.)
Inrush current
Insulation resistance
Dielectric strength
Noise immunity
Vibration resistance
Shock resistance
Ambient temperature
Humidity
Atmosphere
I/O interface
Power interrupt time
Weight
Specifications
CPU Unit Specification
CPU Units with
10 I/O points
(relay outputs)
24 V DC
20.4 to 26.4 V DC
4 W
25 A max.
20 M min. (at 500 V DC) between isolated circuits
2,300 V AC for 1 min (between isolated circuits)
Conforms to IEC61000-4-4, 2 kV (power lines)
Conforming to IEC 60068-2-6, JIS C0040: 10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s
tions for 80 minutes each (Time coefficient; 8 minutes
Conforming to IEC 60068-2-27, JIS C0041: 147 m/s
Operating: 0 to 55 C
Storage: –20 to 75 C (except for the battery)
10% to 90% (with no condensation)
Must be free from corrosive gas
Terminal block
2 ms min.
200 g max.
Expansion I/O Unit with 10 I/O points (relay outputs)
Expansion I/O Unit with 20 I/O points (relay outputs)
Expansion I/O Units with 24 I/O points (transistor outputs)
Expansion I/O Unit with 32 I/O points (transistor outputs)
Expansion I/O Unit with 8 input points
Expansion I/O Unit with 16 input points
Expansion I/O Units with 8 output points (transistor outputs)
Expansion I/O Units with 16 output points (transistor outputs)
Expansion I/O Unit with 8 output points (relay outputs)
Simple Communications Unit
Peripheral/RS232C Adapter Unit
RS422/RS232C Adapter Unit
AC Power Supply Unit
Analog I/O Unit
Temperature Sensor Unit
CompoBus/S I/O Link Unit
CPU Units with
10 I/O points
(transistor outputs)
3 W
200 g max.
Connector
CPU Units with
20 I/O points
(relay outputs)
4 W
Terminal block
250 g max.
2
The power consumption of the CPU Unit includes power for the Pro-
gramming Consoles and Adapter Units.
Add the following consumptions when using Expansion I/O Units.
CPU Unit
CPM2C-10C(1)DR-D
CPM2C-20C(1)DR-D
CPM2C-S1@0C-DRT1
CPM2C-S1@0C
CPM2C-10C(1)DT(1)@-D
CPM2C-20C(1)DT(1)@-D
CPM2C-32C(1)DT(1)@-D
Expansion I/O Unit
CPM2C-10EDR
CPM2C-20EDR
CPM2C-24EDT(1)@
CPM2C-32EDT(1)@
CPM2C-MAD11
CPM2C-SRT21
CPM2C-TS001/002
CPM2C-8ED@/16ED@
CPM2C-8ER
CPM2C-8ET(1)@/16ET(1)@
three times each in X, Y, and Z directions
coefficient factor 10 = total time 80 minutes)
CPU Units with
20 I/O points
(transistor outputs)
3 W
Connector
200 g max.
200 g max.
200 g max.
200 g max.
200 g max.
150 g max.
150 g max.
150 g max.
150 g max.
200 g max.
150 g max.
150 g max.
150 g max.
250 g max.
200 g max.
200 g max.
150 g max.
CPU Units with
32 I/O points
(transistor outputs)
3 W
200 g max.
Power consumption (W)
4
4
3
3
3
3
3
Programmable Controllers
Power consumption (W)
1
2
1
1
3.5
1
1.5
1
2
1
2
CPM2C-S CPU Unit
with 10 I/O points
(transistor outputs)
3 W
160 g max.
in X, Y, and Z direc-