Overview
9 System Configuration
System Configuration
General Information
The System Configuration section describes the various PLC system
configurations possible and assists in selecting the necessary components to
complete a required parts list. Specific details about configuring PLC systems are
described throughout the section. System Configuration Worksheets have also
been provided to simplify the configuration and parts selection. Some basic
control system application information is required in order to select the proper
components.
There are several system configurations that are possible with the C200H
system. The following paragraphs briefly describe the types of possible C200H
system configurations.
Additional configuration and technical information can be found in the detailed
product manuals. Refer to Section 6 of this catalog for a list of publications.
Local I/O Systems
Local I/O System configurations are designed to accommodate large amounts of
I/O that are located within 12 meters (39 ft.) of the CPU Rack. The CPU rack can
be expanded with two additional racks to accommodate large amounts of I/O.
Several different configurations are possible depending on the distance and I/O
requirements of the system.
Remote I/O Systems
Remote I/O systems are used in applications requiring I/O to be located at long
distances from the CPU. In a C200H system, remote I/O are counted separately
from local I/O, allowing expansion up to 512 remote I/O points. Multiple remote
I/O systems can be added to a single PLC for additional configuration flexibility.
These systems are available in fiber-optic and wired (twisted pair) versions. This
section includes configuration information for the following:
Number of I/O
Type of I/O: discrete, analog, special I/O, interrupt and communications
Distribution of I/O: Local or remote I/O requirements, location of I/O and num-
ber of I/O required at each location
Communication system requirements
Man-machine interface requirements
CPU Rack only
CPU Rack and Local Expansion Racks
SYSMAC BUS Fiber-optic Remote I/O System
SYSMAC BUS Wired Remote I/O System