804-1210 XANTREX TECHNOLOGY, 804-1210 Datasheet - Page 33

no-image

804-1210

Manufacturer Part Number
804-1210
Description
BATTERY CHARGER, LEAD ACID, 265VAC
Manufacturer
XANTREX TECHNOLOGY
Datasheet

Specifications of 804-1210

Battery Charger Type
Switch Mode
Battery Technologies Supported
Lead Acid
Supply Voltage
265VAC
Table 2-2 DC Wiring Examples for 24 V chargers
Over-current protection disconnect
975-0402-01-01
Wire Length
(
5
7.5
20
feet
max length one way
a.Values based on American Boating and Yachting Council E-11 2008 Table VI-A and
Table IX.
1.Per American Boating and Yachting Council E-11.
This guide for use by qualified installers only
Electrical codes require the DC circuit from each battery to
the charger to be equipped with a disconnect and an over-
current protection device, usually within 7 inches (17.8 cm)
of each battery
breakers, fused disconnects, or a separate fuse and disconnect
for each circuit. These devices must be rated for DC voltage
and current and be rated to withstand the short circuit current
available from the connected battery bank. Do not substitute
devices rated only for AC voltage; they may not operate
properly.
The current rating of the DC fuses must be correctly matched
to the size of the DC wiring used, in accordance with the
applicable codes. This helps to protect the installation against
fire in case of any overcurrent or short circuit fault.
meters
1.5
2.25
6
)
TC1524
No. 14
2 mm
No. 14
2 mm
No. 10
5.3 mm
1
. The devices are usually DC-rated circuit
2
2
2
Wire Size (AWG and mm
TC2024
No. 10
5.3 mm
No. 10
5.3 mm
No. 8
8.4 mm
2
2
2
TC3024
No. 10
5.3 mm
No. 10
5.3 mm
No. 6
13.3 mm
Preparing for Installation
a
2
2
2
2
)
TC5024
No. 6
13.3 mm
No. 6
13.3 mm
No. 4
21.2 mm
2–9
2
2
2

Related parts for 804-1210