Specifications of NIC1001-A01-10VV

Lead Free Status / Rohs Status
Compliant
System Parameters
Battery Reconnect
Voltage**
Battery Reconnect
Delay Time**
Load 1 Disconnect
Voltage **
Load 1 Disconnect
Delay Time**
Load 1 Reconnect
Voltage**
Load 1 Reconnect
Delay Time**
Load 2 Disconnect
Voltage **
Load 2 Disconnect
Delay Time**
Load 2 Reconnect
Voltage**
Load 2 Reconnect
Delay Time**
Load 3 Disconnect
Voltage **
Load 3 Disconnect
Delay Time**
Load 3 Reconnect
Voltage**
The Battery Disconnect contactor in the
battery panel will reconnect if the plant
voltage exceeds this set point
The amount of time delayed after
reaching the battery reconnect voltage
set point, before closing the battery
disconnect contactor
The Load 1 Disconnect contactor in a
distribution panel will open if the plant
voltage falls below this set point
The amount of time delayed after
reaching the load 1 disconnect voltage
set point, before opening the load 1
disconnect contactor
The Load 1 Disconnect contactor in the
distribution panel will reconnect if the
plant voltage exceeds this set point
The amount of time delayed after
reaching the load 1 reconnect voltage
set point, before closing the load 1
disconnect contactor
The Load 2 Disconnect contactor in a
distribution panel will open if the plant
voltage falls below this set point
The amount of time delayed after
reaching the load 2 disconnect voltage
set point, before opening the load 2
disconnect contactor
The Load 2 Disconnect contactor in the
distribution panel will reconnect if the
plant voltage exceeds this set point
The amount of time delayed after
reaching the load 2 reconnect voltage
set point, before closing the load 2
disconnect contactor
The Load 3 Disconnect contactor in a
distribution panel will open if the plant
voltage falls below this set point
The amount of time delayed after
reaching the load 3 disconnect voltage
set point, before opening the load 3
disconnect contactor
The Load 3 Disconnect contactor in the
distribution panel will reconnect if the
plant voltage exceeds this set point
Description
Page - 11 - of 19
10.75 V
12.75 V
11.25 V
Nominal
12.5 V
12.5 V
12 Volt
20 Sec
11 V
13 V
5 Sec
5 Sec
5 sec
5 sec
5 sec
dc
dc
dc
dc
dc
dc
dc
Nominal
21.5 V
25.5 V
22.5 V
24 Volt
20 Sec
25 V
25 V
22 V
26 V
5 Sec
5 Sec
5 sec
5 sec
5 sec
dc
dc
dc
dc
dc
dc
dc
Nominal
48 Volt
20 Sec
50 V
43 V
50 V
44 V
51 V
45 V
52 V
5 Sec
5 Sec
5 sec
5 sec
5 sec
dc
dc
dc
dc
dc
dc
dc