16-1-L-S1

Manufacturer Part Number
16-1-L-S1
Description
VOLTAGE MONITOR, 12-30V, 5 SPADE CONNECTORS
Manufacturer
Time Mark Corporation
Datasheet
1.787
DIMENSIONS - Surface Mount Case
INSTALLATION AND ADJUSTMENT
Begin with NO POWER APPLIED to the unit, making
adjustments with a non-conductive tool being careful not
to apply to much torque to the controls.
Adjust the HIGH SETPOINT control fully clockwise (right
toward +), adjust the LOW SETPOINT control fully
counter-clockwise (left toward -).
Adjust the TRIP DELAY fully clockwise (right toward +
for max) and RESTART DELAY fully counter-clockwise
(left toward - for disabled).
8-Pin Case: Connect the voltage to be monitored to the
socket using the pin diagram on the unit OR
Surface Mount Case: Attach 1/4” terminal lugs to the
input voltage wires, and connect to the terminals
marked INPUT (refer to diagram on unit).
Apply power to the unit. The LED lights will sequence on
during self test. Complete the setup procedure in the
following box for either an Over Voltage, Under
Voltage or Over/Under Voltage monitor depending on
how you wish to configure your Model 16-1.
Telephone: Main (918) 438-1220
E-mail:
Internet:
MODEL 16-1-X-X
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 16.
Sales (800) 862-2875
Fax:
sales@time-mark.com
http://www.time-mark.com
3.712
2.711
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
3.201
(918) 437-7584
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
2.062
2.187
1.312
1.012
GENERAL SAFETY
WARRANTY
The Model 16-1 Over/Under Voltage Monitor is
warranted to be free from defects in materials or
workmanship for a period of 5 years from the date of
manufacture. See Time Mark’s Terms and Conditions of
Sale or contact Time Mark’s Sales department at 1-800-
862-2875 or 1-918-438-1220 Monday through Friday; 8
a.m. to 5 p.m., CST, for further details.
Over/Under Voltage Monitor
(cont.)
Adjust the TRIP DELAY and RESTART DELAY time to
the desired setting. A TRIP DELAY or RESTART
DELAY is optional, and can be disabled by turning the
control fully counter-clockwise (left toward -) if desired.
Specific setpoints will require the use of an adjustable
voltage source such as a VARIAC and a voltmeter.
Note: TRIAC type light dimmers do not provide a full
sine wave and will not provide a reliable calibration
voltage.
with Trip and Restart Delay
Over voltage with trip and restart delay
Slowly rotate the HIGH SETPOINT control counter-
clockwise (left toward -), until the UPPER TRIP LED
illuminates, and the TRIP DELAY LED blinks. Adjust
HIGH SETPOINT control clockwise (right toward +)
until the DEVICE NORMAL LED illuminates and the
TRIP DELAY LED stops blinking.
Under voltage with trip and restart delay
Slowly rotate the LOW SETPOINT control clockwise
(right toward +), until the LOWER TRIP LED
illuminates, and the TRIP DELAY LED blinks. Adjust
LOW SETPOINT counter-clockwise (left toward -)
until the DEVICE NORMAL LED illuminates and the
TRIP DELAY LED stops blinking.
Over/Under voltage with trip and restart delay
Follow the instructions above for Over voltage with
trip and restart delay and Under voltage with trip
and restart delay to enable both ranges.