UPA-WP100 ATC Diversified Electronics, UPA-WP100 Datasheet

no-image

UPA-WP100

Manufacturer Part Number
UPA-WP100
Description
POWER ALERT, ANSI WARNING PLATE FOR UPA-100
Manufacturer
ATC Diversified Electronics
Datasheet

Specifications of UPA-WP100

Termination
6’ (4) 18 AWG
Lead Free Status / Rohs Status
RoHS Compliant part
The UPA-100 Power Alert reduces the risk of electrical arc flash by
pre-verifying the electrical isolation from outside of a control panel.
Hardwired to the circuit breaker or main disconnect, the UPA flashes
whenever voltage is present. Engineered with redundant circuitry, the
Power Alert is powered by the same voltage that it indicates.
The eight detector UPA-100 visually alerts to the presence of dangerous
AC or DC (Stored Energy) potentials occurring between any combination
of the four monitored input lines (L1, L2, L3, GND). Two LED indicators
are assigned to each input line and are designated “+” and “-”. For each
input line carrying an AC potential (bi-polar), both the “+” and “-” LEDs
will be active. A DC or Stored Energy potential will illuminate the “+” LED
for the positive line and the “-” LED for the negative line.
OSHA 1910.147 THE CONTROL OF HAZARDOUS ENERGY (LOCKOUT/TAGOUT)
Following the application of lockout or tagout devices to energy isolating devices, all potentially hazardous
stored or residual energy shall be relieved, disconnected, restrained, and otherwise rendered safe. (d)(5)(ii)
If there is a possibility of reaccumulation of stored energy to a hazardous level, verification of isolation shall be con-
tinued until the servicing or maintenance is completed, or until the possibility of such accumulation no longer exists.
(d)(6)
“Verification of Isolation.” Prior to starting work on machines or equipment that have been locked out or tagged out, the
authorized employee shall verify that isolation and de-energization of the machine or equipment have been accomplished.
\\\
OPERATIONAL
RANGE
MAXIMUM RATED
VOLTAGE
DETECTION
THRESHOLDS
POWER
CONSUMPTION
TEMPERATURE
RATING
ENCLOSURE
TERMINATIONS
WEIGHT
INDICATOR FLASH RATES (L1, L2, L3, GND)
3- Phase Line-To-Line (VAC)
Flashes/Sec (Typical)
DC or Stored Energy (VDC)
Flashes/Sec (Typical)
GND DETECTOR THRESHOLDS (LEAKAGE ANY PHASE-TO-GROUND)
3- Phase Line-To-Line (VAC)
L1, L2, or L3 To Ground Continuity (OHMS)
Detector Included Fault Current ( A)
DETECTOR INCLUDED FAULT CURRENT (PHASE-TO-GROUND SHORT)
3- Phase Line-To-Line (VAC)
0 OHM Phase-To-Ground Current ( A)
\\\
800.727.5646
SPECIFICATIONS
OPERATION
750 VAC/1000 VDC (LINE-TO-LINE
or LINE-TO-GND)
29 VAC 3-Phase, 40 VAC SINGLE-Phase,
27 VDC (TYP Cutoff)
1.2 Watts @ 750 VAC (Approximately)
NEMA 4X 105°C PVC, Totally Encapsulated
for Environment Protection
(4) 8ft, 18 AWG 1000V, UL-1452
9 oz.
or 3-Phase
AC Single
Operate
Storage
Energy
Stored
DC or
atcdiversified.com
40 to 750 VAC, 50/60/400 Hz,
(LINE-TO-LINE or LINE-TO-GND)
30 to 1000 VDC,
(LINE-TO-LINE or LINE-TO-GND)
-4° to 131°F (-20° to +55°C)
-40° to 185°F (-40° to +85°C)
<29
<27
0
0
1.3
1.6
30
30
120 240 480 600 750
4.2
2.5
2M
48
30
30
28
7
110 300 600 1000
120 240 480 750
120 240 480 750
108 219 455 730
5.8
4.5
2M
26
Diversified Electronics
7.3
6.9
3M
38
8.0
8.8
5M
60
\\\
8.8
9.1
7M
• Detects Single or 3-Phase
• Redundant Circuitry
67
\\\
AC & DC Voltage or
Stored Energy
ORDERING INFORMATION
DIMENSIONS
MODEL NUMBER
UPA-100
P
_
_
+
2.00
+
(INCHES)
_
_
• Verification of Zero Energy
• Fits 1-1/4" Conduit
UPA-100 Series
in a Panel
Knock-Out
Universal Power Alert
PANEL MOUNT
1 1/4 CONDUIT
KNOCKOUT
DESCRIPTION