G3TCIDC24DC/AC24 Omron Automation, G3TCIDC24DC/AC24 Datasheet - Page 10

no-image

G3TCIDC24DC/AC24

Manufacturer Part Number
G3TCIDC24DC/AC24
Description
RELAY, SOLID STATE; INPUT; WHITE; 10-32 VDC/15-32VAC; 25 MA (MAX.); 100 UA (MAX.)
Manufacturer
Omron Automation
Type
Inputr
Datasheet

Specifications of G3TCIDC24DC/AC24

Brand/series
G3TC Series
Color
White
Connection To Host
Board Mount
Current, Input
25 mA
Current, Leakage
100 uA (Max.)
Dielectric Strength
4000 VAC @ 50⁄60 Hz
Dimensions
43.2mmL×15.2mmW×31.8mmH
Humidity
45 to 85%
Input
10 to 32 VAC/VDC
Input Type
Digital
Input, Range
10 to 32 VAC/VDC
Module Type
Input
Mounting Type
PCB
Number Of Channels
1
Primary Type
Control
Resistance, Input
1.5 Kiloohms
Resistance, Insulation
100 Megohms (Min.) @ 500 VDC
Special Features
Photo-Coupler Isolation
Standards
UL Listed, CSA Certified, TUV Approved, CE Marked
Temperature, Operating
-30 to +80 °C
Time, Turn-off
5 ms (Max.)
Time, Turn-on
5 ms (Max.)
Voltage, Isolation
4000 VAC
Voltage, Operating
10 to 32 VDC⁄VAC
Voltage, Supply
24 VDC
Lead Free Status / Rohs Status
RoHS Compliant part
Precautions
■ General Precautions
At OMRON, we are constantly working to improve the quality and
reliability of our products. SSRs, however, use semiconductors,
which are prone to malfunction. Be sure to use SSRs within their
rated value. Use the SSR only in systems that are designed with
redundancies, flame protection, counter measures to prevent opera-
tion errors, and other countermeasures to prevent accidents involv-
ing human life or fires.
1. Do not apply excessive voltage or current to the input or output
2. Do not connect the input and output circuits incorrectly. Doing so
3. Do not obstruct the flow of air around the G3TC. Abnormal heat-
■ Correct Use
Before Actual Operation
1. In actual operation, the G3TC may cause accidents that were
2. The ratings in this datasheet are for testing in a temperature
3. The input circuitry does not incorporate a circuit protecting the
4. Only use the G3TC with loads that are within the rated values.
5. Use a power supply within the rated frequency range. Using a
6. No over-voltage absorption element is built in. Therefore, if the
7. As protection against accidents due to short-circuiting, be sure to
8. Keep wiring separate from high-voltage power lines and use wires
404
Do not touch the relay while power is supplied or immediately after
G3TC is turned OFF. Doing so may result in burns.
Do not touch the load terminal of the G3TC immediately after the
power is turned OFF, otherwise an electric shock may be received
due to the residual charge of the built-in C/R circuit.
Be sure to turn OFF the power supply to the G3TC before wiring,
otherwise an electric shock may result.
Ensure that a short-circuit current does not flow on the load side of
the SSR, otherwise the G3TC may be damaged.
circuit of the G3TC. Doing so may result in malfunction or burning.
may result in malfunction or burning.
ing of the G3TC may result in short-circuiting of output elements
and burning.
unforeseeable at the theoretical stage. Therefore, it is necessary
to test the G3TC under a variety of conditions that are possible.
As for the characteristics of the G3TC, it is necessary to consider
the differences between G3TC models.
range of 15 to 30°C, a relative humidity range of 25% to 85%, and
an atmospheric pressure range of 88 to 106kPa. When testing
operation, it is necessary to confirm correct operation not only
with the actual load that will be used, but also at the same ambi-
ent conditions as for actual operation.
SSR from being damaged due to a reversed connection. Make
sure that the polarity is correct when connecting the input lines.
Using the G3TC with loads outside the rated values may result in
malfunction, damage, or burning.
power supply outside the rated frequency range may result in
malfunction, damage, or burning.
G3TC is connected to an inductive load, be sure to connect an
over-voltage absorption element.
install protective devices, such as fuses on the power supply side.
of an appropriate length, otherwise malfunction and damage may
result due to induction.
!WARNING
!WARNING
!WARNING
!WARNING
Solid State Relays for Industrial I/O
G3TC
9. For a DC inductive load, a diode should be connected in parallel
10.For an I/O mounting rack that is installed horizontally, use the
with the load to absorb the counter electromotive force of the
load.
G3TC with loads that are within the following conditions.
G3TC-ODC5, -ODC15, -ODC24
G3TC-OAC5, -OAC5A, -OAC15, -OAC15A, -OAC24, -OAC24A
0.64
2.7
0.64
2.1
4
3
2
1
0
−30
4
3
2
1
0
−30
−20
−20
Ambient temperature (°C)
Ambient temperature (°C)
0
Horizontal Mounting
Horizontal Mounting
0
20
20
40
40
45
45
60 70 80
60 70 80
100
100