FP0-C16T-A Panasonic Electric Works, FP0-C16T-A Datasheet

no-image

FP0-C16T-A

Manufacturer Part Number
FP0-C16T-A
Description
Automation Control; Tr. Sink 0.1 A/pt, 1.6 A (Max.)/Common; 19.6 to 26.4 VDC; 8
Manufacturer
Panasonic Electric Works
Type
PLCr
Datasheet

Specifications of FP0-C16T-A

Brand/series
FP0 Series
Current, Input
4.3 mA
Dimensions
25mmW×90mmH×60mmD
Input Type
Voltage
Memory
EEPROM
Memory Type
EEPROM
Number Of Inputs
8
Number Of Outputs
8
Output Type
Digital
Primary Type
Controller
Programmable With
CPU (Computer)
Standards
UL Listed, cUL Listed, CE Certified
Voltage, Supply
24 VDC
High-speed Operation
Scanning Speed Is Approx. 0.9 ms
Lead Free Status / Rohs Status
RoHS Compliant part
FP0 Series
Programmable Controller
Panasonic ... the new name for
10/2004

Related parts for FP0-C16T-A

FP0-C16T-A Summary of contents

Page 1

... FP0 Series Programmable Controller Panasonic ... the new name for 10/2004 ...

Page 2

... Even so, the size is still only W105 x H90 x D60mm, a super compact design that breaks all previous common sense rules on small-scale PLCs. With the smallest-ever attachment area, the FP0 is perfect for installation in machines, facilities, and control boards where miniaturization is progressing even further. ...

Page 3

Either 10 Points or the Maximum of 128 Points You save this much space! …up to 128 I/Os 105mm Control unit Expansion unit Easy Expansion The expansion unit can be attached easily without any cables. The expansion unit can easily ...

Page 4

... Input Output Input 6 points 4 points 6 points 4 points 8 points FP0-C10RSA FP0-C10CRSA FP0-C14RSA with 2nd RS232C This advanced FP0 CPU Control Unit 10k offers additional features: 10,000 steps FP0-T32C program memory Battery backed RAM Real-time clock 16383 words data register 32 points Input Output ...

Page 5

... FP0 Expansion Units Choose the number of I/O points to suit the application Digital I/O Units Relay output type Input only type 8 points 16 points 8 points Input Output Input Output 4 points 4 points 8 points 8 points 8 points FP0-E8RSA FP0-E16RSA FP0-E8XA Option: Output 8 points FP0-E8YRSA Analogue I/O Units ...

Page 6

... Pulse catch and interrupt input functions meet the need for high-speed response. High-speed execution Execution speed of 0.9µs per basic instruction. 500 steps program yields a scanning time of 1ms, which means the FP0 boosts the fastest processing time among the products of this class. ...

Page 7

... FP0 unit. (For transistor output type only) Serial communication function • The FP0’s second RS232C port (types C10CRS, C14CRS, C16C, C32C, and T32C) allows direct connection to computers and operation display panels. Also, bi-directional data communication with barcode readers and other RS232C devices is made easy. • ...

Page 8

... Communication – Simple and efficient via two serial interfaces: TOOL-Port and COM-Port (RS232C interface). Programming interface TOOL-Port (also for communication) In Computer Link mode, this port offers access to the entire FP0 memory area. For example during data exchange between a host PC running SCADA software and an FP0 PLC, the Windows the communications protocol (MEWTOCOL ...

Page 9

... Maintenance saving Program memory uses EEPROM. In addition, programs can be changed even in RUN mode! Overwrite function in RUN mode It is possible to overwrite a program while the FP0 is running, such as during program debugging and startup adjustments. Backup battery unnecessary The program memory uses EEPROM. The program and device contents can be stored without a backup battery, and even programming for a machine builder is safe ...

Page 10

... FP0 PROFIBUS DP Slave or Remote I/O Unit For cost effective control of distributed field device The FP0 DPS2 can operate either slave module remote I/O system to which different decentralised inputs and outputs can be connected. A DIP switch can be used to switch between the two modes: Mode 1: DP-Slave module ...

Page 11

... Controls 64 input points and 64 output points. Able to control up to 128 points for S-LINK-related devices. 3. Allows simultaneous use of expansion units. Similar to other FP0 units three expansion units can be used for efficient I/O wiring. FP0-SL1 4. A wide range of I/O modules allow manifold customer-oriented network layouts. ...

Page 12

... FP0 MEWNET-F Unit Networking units MEWNET-F The FP0 can be used as a slave station for MEWNET-F (remote I/O system) by adding I/O link unit. MEWNET reduced-wiring remote I/O system that connects PLCs located separately and I/O slave stations with 2-core cabling. By adding an I/O link unit to the FP0, you can link master station PLC and FP0 inputs and outputs via the network ...

Page 13

... Up to three units can be added to each control unit, enabling temperature control channels. The temperature data obtained using the thermocouple is converted to the digital value to be read into the FP0 control unit. Standard types of thermocouples can be used and R 3 temperature measurement ranges are available: -100° ...

Page 14

... The multimode FP0 analogue unit can be configured via the DIP switches on the front side into the required analogue ranges. Communication with the FP0 CPU unit is achieved via the expansion bus. The expansion bus is automatically connected after the FP0 analogue unit is connected to the FP0 CPU unit ...

Page 15

... Analogue Signal Processing FP0 Analogue Units General specifications Item Rated operating voltage 24VDC Operating voltage range 21.6 to 26.4VDC Rated current consumption FP0-A80: 60mA or less, FP0-A21/A04V: 100mA or less, FP0-A04I: 130mA or less Ambient temperature 0° 55°C Storage temperature -20° 70°C Size 60mm Weight appoximately 100g ...

Page 16

... FP0 RTD Input Expansion Unit User friendly acquisition of temperatures with high precision Features The module can be easily installed in an existing system: Special connection cables, backplanes, and so forth are unnecessary as the expansion unit employs a stacking system that uses expansion connectors and lock levers on the surface of the unit itself. ...

Page 17

... Interrupt program functions Periodical interrupt Constant scan One RS232C port is mounted on each of the models FP0- C10CR, C14CR,C16CT, C16CP, C32CT, C32CP, T32CT, T32CP and SL1 type (3P terminal block) RS232C port Transmission speed (Baud rate): 300 to 19200bits Communication method: half duplex Transmission distance: 3m ...

Page 18

... Operating indicator LED display Note: (*): Since the response time very fast (for high-speed counter input), the FP0 happens to catch chattering noise as an input signal. To prevent this recommended that timer instruction should be included in the program. Output specifications 1) Relay output type ...

Page 19

... Control FPWIN Pro is the Matsushita programming software according to the international standard IEC 61131-3. Control FPWIN Pro works with the FP0 as well as any FP series programmable controller. Also, since the tool port is an RS232C, connection easy – it only requires a single cable. No converter or adapter is required. ...

Page 20

... Applicable PLC types *All products on the market are supported. All FP series types are supported: FP Sigma, FP0, FP-e, FP1, FP2, FP2SH, FP3, FP10SH, FP-M Note: FPWIN GR Vers. 2.2 or later is needed to program the FP-e I/O comment edit function Successive I/O comments can be input for each device type. ...

Page 21

Control CommX, PCWAY, OPC Server Visualisation software for ready made or customised solutions Control CommX The connection in ActiveX technology. Connects your Visual Basic application to Matsushita PLCs. Gives you the possibility to easily develop highly customised control solutions. Create ...

Page 22

... FP0-E8YTA (NPN) Notes: A power cable (order number AFP0581) is enclosed with the control unit and the relay output type upgrade units (Transistor output type upgrade units do not require a power cable). Two Phoenix terminals (9-pin) are needed with the relay output type terminal type. A 2.5mm width screwdriver is needed for the wiring. ...

Page 23

... FP0 Analogue and Networking Units Products and order numbers Analogue units 3 points Input 2 points Output 1 points Terminal type FP0-A21A Order number: Order number: Temperature control units 4 points Input 4 points Terminal type FP0-TC4 Order number: Order number: Networking units PROFIBUS PROFIBUS DP-Slave or Remote I/O ...

Page 24

... Order number: Notes: (1) One I/O cable set (2 cables) is necessary with the following models: FP0-C10RS, C14RS, E8RS, E16RS. (2) One I/O cable set (2 cables) is necessary with the following models: FP0-C16T/C16P, E16T/E16P. (3) Two I/O cable sets (total 4 cables) are necessary with the following models: FP0-C32T/C32P, E32T/E32P. ...

Page 25

... Spanish, Japanese menu selectable. FPWIN Pro FPWIN Pro According to IEC 61131-3 Standard Ver.5 Ver.5 Order number: small version for MINI-PLC only (FP0, FP-e, FPM, FP1, FP (Sigma) 1995-2000 1995-2000 Matsushita Electric Works(Europe)AG Matsushita Electric Works(Europe)AG • FPWINPROSEN (English manual) Made in Germany Made in Germany • ...

Page 26

... FP Power supply Status display FP-PS24-050 E Standards NOTE: 1) Mounting distance between the FP0 pow- er supply and the FP0 CPU is needed to EMC permit heat radiation for the FP0-CPU 2) For side mounting, 2 additional LVD blue clips are needed: order part-no. 677-021-17101 (1pce.) for FP0-PSA2 ...

Page 27

... NAiS Control FPWIN Pro Programming software for all FP-series PLC (FP0, FP1, FP-M, FP2/2SH, FP3, FP10SH) including English manual NAiS Control FPWIN GR Programming software for all FP-series PLC (FP0, FP1, FP-M, FP2/2SH, FP3, FP10SH) including English manual Handheld programmer for FP 0 and all other FP programmable controllers FP0-Programming cable PC < ...

Page 28

Global Network North America Europe Aromat Matsushita Corporation Electric Works (Europe) AG Matsushita Electric Works Global Network Services Global Network Services Global Network Services Asia Pacific China Matsushita Matsushita Electric Works Electric Works (Asia Pacific) Pte. Ltd. (China) Co., Ltd. ...