■ Operation and Setting Methods
Connections
1. Input
2. Outputs
DIP Switch Settings
The Startup lock time, number of wires, and rated voltage are set using the DIP switch located on the bottom of the Unit.
Connect to L1, L2, and L3 (for three-phase three-wire mode) or L1, L2, L3, and N (for three-phase four-
wire mode), depending on the mode selected using pin 2 on the DIP switch.
The Unit will not operate correctly if the DIP switch setting and the wiring do not agree.
Make sure the phase sequence is wired correctly. The Unit will not operate normally if the phase
sequence is incorrect.
Terminals 11, 12, and 14 are the output terminals for overvoltage (SPDT).
Terminals 21, 22, and 24 are the output terminals for undervoltage (SPDT).
ON
OFF
SW1
SW2
SW3
SW4
DIP switch
DIP Switch Functions
K8AB-PW1
Note: All pins are set to OFF at the factory.
K8AB-PW2
Note: All pins are set to OFF at the factory.
Power ON lock time 5 s
Number of wires
Rated voltage
Power ON lock time 5 s
Number of wires
Rated voltage
SWITCH
SWITCH
1 s
Three-phase, four-wire
Three-phase, three-wire
Three-phase,
three-wire
240 V
230 V
220 V
200 V
1 s
Three-phase, four-wire
Three-phase, three-wire
Three-phase,
three-wire
480 V
415 V
400 V
380 V
Three-phase,
four-wire
138 V
133 V
127 V
115 V
Three-phase,
four-wire
277 V
240 V
230 V
220 V
OFF ❍ ↓
OFF ❍ ↓
ON ● ↑
ON ● ↑
OFF
OFF
OFF
OFF
ON
ON
ON
ON
---
---
---
---
---
---
---
---
4
4
4
4
N
L1
Load
L2 L3
---
---
---
---
---
---
---
---
3 3
3 3
Voltage input
Signal output
Signal output
K8AB-PW
---
---
---
---
---
---
---
---
---
---
---
---
2
2
14
12
24
22
L1
L2
L3
Undervoltage
alarm
Overvoltage
alarm
---
---
---
---
---
---
1
---
---
---
---
---
---
1
N
11
21
7