E2K-X15MY1 Omron Automation, E2K-X15MY1 Datasheet - Page 2

no-image

E2K-X15MY1

Manufacturer Part Number
E2K-X15MY1
Description
Sensor, Cylindrical; M30; 90 to 250 VAC @ 50/60 Hz; 2.2 mA @ 200 VAC; 10 Hz
Manufacturer
Omron Automation
Type
Capacitiver
Datasheet

Specifications of E2K-X15MY1

Body Style
Cylindrical
Current, Rating
2.2 mA @ 200 VAC
Current, Switching
200 mA
Frequency, Switching
10 Hz
Function
Proximity
Ip Rating
IP66
Material, Housing
ABS
Mounting Style
Two metal lock washers and M30 nuts included
Mounting Type
M30 Threaded
Output
NO
Primary Type
Proximity
Range, Measurement
15 mm
Standards
UL Recognized, File Number E76675, CSA Certified, File Number LR45951
Technology
Capacitive
Temperature, Ambient, Maximum
+70 °C
Temperature, Ambient, Minimum
-25 °C
Termination
2-Wire Cable
Voltage, Supply
220 VAC
Supply Voltage Range
10-30 VDC or 90-250 VAC, 50/60 Hz
Load Rating
200 mA (DC) or 10-200 mA (AC)
Approvals
CE, UL, CSA (Model Dependant)
Lead Free Status / Rohs Status
RoHS Compliant part

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
E2K-X15MY1
Manufacturer:
OMRON
Quantity:
1 000
Ratings and Specifications
*1. The above values are sensing distances for the standard sensing object. Refer to Engineering Data on page 3 for other materials.
*2. E Models (DC switching models): A full-wave rectification power supply of 24 VDC 20% (average value) can be used.
Item
Sensing distance
Set distance *1
Differential travel
Detectable object
Standard sensing object
Response frequency
Power supply voltage*2
(operating voltage range)
Current consumption
Leakage current
Control
output
Indicators
Operation mode
(with sensing object
approaching)
Protection circuits
Ambient temperature
range
Ambient humidity range
Temperature influence
Voltage influence
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Degree of protection
Connection method
Weight (packed state)
Materi-
als
Accessories
Load current
Residual voltage E Models: 1 V max. (Load current: 200 mA, Cable length: 2 m), Y Models: Refer to Engineering Data on page 4.
Case
Sensing surface
Clamping nuts
Model
4mm 10%
0 to 2.8 mm
4% to 20% of sensing distance
Conductors and dielectrics
Grounded metal plate: 50
E Models: 100 Hz, Y Models: 10 Hz
E Models: 12 to 24 VDC (10 to 30 VDC)
Y Models: 100 to 220 VAC (90 to 250 VAC)
E Models: 15 mA max.
Y Models: 2.2 mA max. (Refer to page 4.)
E Models: 200 mA max.*2, Y Models: 10 to 200 mA
E Models: Detection indicator (red), Y Models: Operation indicator (red)
E1/Y1 Models: NO
E2/Y2 Models: NC
E Models: Reverse polarity protection, Surge suppressor, Y Models: Surge suppressor
Operating/Storage: 25 to 70 C (with no icing or condensation)
Operating/Storage: 35% to 95% (with no condensation)
E Models: 2% max. of sensing distance at rated voltage at rated voltage 20%
Y Models: 2% max. of sensing distance at rated voltage at rated voltage 10%
50 M min. (at 500 VDC) between current-carrying parts and case
E Models: 1,000 VAC, 50/60 Hz for 1 min between current-carrying parts and case
Y Models: 2,000 VAC, 50/60 Hz for 1 min between current-carrying parts and case
Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions
Destruction: 500 m/s
IP66 (IEC), in-house standards: oil-resistant
Pre-wired Models (Standard cable length: 2 m)
Approx. 65 g
Heat-resistant ABS
Polyacetal
Tightening tool, Instruction Manual
20% max. of sensing distance at 23 C in the operating temperature range
E2K-X4ME@,
E2K-X4MY@
2
Refer to the timing charts under I/O Circuit Diagrams on page 4 for details.
3 times each in X, Y, and Z directions
50
1 mm
8 mm 10%
0 to 5.6 mm
Approx. 145 g
Instruction manual
E2K-X8ME@,
E2K-X8MY@
15 mm 10%
0 to 10 mm
Operating/Storage: 10 to 55 C
(with no icing or condensation)
Approx. 205 g
E2K-X15ME@,
E2K-X15MY@
E2K-X
2