PMD600 Macromatic, PMD600 Datasheet - Page 2

no-image

PMD600

Manufacturer Part Number
PMD600
Description
Relay; E-Mech; Phase Monitor; SPDT, SP-NC; Cur-Rtg 10A; Ctrl-V 575V; PCB Mnt; SMT
Manufacturer
Macromatic
Datasheet

Specifications of PMD600

Brand/series
PMD Series
Contact Form
SPDT, SP-NC
Current, Rating
10 A
Function
Phase Monitor
Mounting Type
SMD
Relay Type
Electro Mechanical
Standards
cULus, CE
Termination
SMT
Voltage, Control
575 V
Voltage, Rating
240⁄30 VAC⁄VDC
Lead Free Status / Rohs Status
RoHS Compliant part
Application Data
Phase Loss:
Unit trips on loss of any Phase A, B or C.
Phase Reversal:
Unit trips if rotation (sequence) of the three phases is anything
other than A-B-C.
Undervoltage:
Adjustable from 80-95% of nominal voltage. Unit trips when the
average of all three lines is less than the adjusted set point for
a period longer than the adjustable time delay drop-out.
Overvoltage:
Fixed at 110% of nominal voltage. Unit trips when the average
of all three lines is greater than the fixed set point for a period
longer than the time delay drop-out.
Phase Unbalance:
Adjustable from 2 - 10% unbalance. Unit trips when any one of
the three lines deviates from the average of all three lines by
more than the adjusted set point . There is also a “Disable”
setting adjustment that will turn off the Phase Unbalance
Protection if nuisance tripping is a problem.
Output Contacts:
10A SPDT & SPNC @ 240V AC/30VDC,
1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.)
Life:
Mechanical: 10,000,000 operations
Full Load: 100,000 operations
Response Times:
Power Up & Restart After Fault:
Drop-out Due to Fault:
Dimensions
Revised: 11/07
Phase Loss & Reversal 100ms fixed
Phase Unbalance
Undervoltage
Overvoltage
(70)
2.7
(60)
2.4
1 - 300 seconds adjustable
2 seconds fixed
0.1 - 20 seconds adjustable
Fixed Time Based on Inverse
Time Curve
1.8 (45)
1.4 (35)
TWO 0.2 (5) MOUNTING HOLES
PHASE MONITOR RELAYS
Unbalance, and Under/Over Voltage
Phase Loss, Phase Reversal, Phase
Hysteresis: 2 - 3%
Load (burden): Less than 3VA
Temperature: -28
Mounting:
Does not require a socket. Can either be mounted directly on
35mm DIN track with no additional parts or to a back-panel
with two screws.
Indicator LED:
Reset:
As standard, reset is automatic upon correction of fault. When
a momentary-contact N.C. switch is wired across the Manual
Reset terminals (5 & 6), the unit switches to manual reset
mode and remote manual reset is available.
Approvals:
4.3 (110)
4.4 (112)
* Applies to 208-480V units only.
Green Steady
Green Flashing
Red Steady
Red Flashing
Amber Steady
Amber Flashing
Green / Red Alternating
Red / Amber Alternating
PMD Series Surface-Mount
LED Status
File #E109466
Application Data & Dimensions
o
to 65
o
C (-20
*
Normal / Relay ON
Power Up / Restart Delay
Unbalance
Undervoltage / Overvoltage
Reversal
Loss
Undervoltage / Overvoltage
Nominal Voltage Set Error
Trip Pending
o
to 150
Low Voltage & EMC Directives
EN60947-1, EN60947-5-1
o
Indicator
F)
Inches (Millimeters)
All Dimensions in
15