E5AK-AA2-500 Omron Automation, E5AK-AA2-500 Datasheet - Page 2

no-image

E5AK-AA2-500

Manufacturer Part Number
E5AK-AA2-500
Description
Controller; 100 to 240 VAC; 4 to 20, 0 to 20 mA mA; 16 VA; Analog; SPST
Manufacturer
Omron Automation
Type
Processr
Datasheet

Specifications of E5AK-AA2-500

Brand/series
E5AK Series
Contact Form
SPST-NO
Current, Input
4 to 20, 0 to 20 mA mA
Dimensions
96mmW×96mmH×100mmD
Enclosure Rating
IP00, IP20, IP66
Height
4.41 in.
Input Type
Analog
Ip Rating
IP00, IP20, IP66
Length
3.78 x 3.78 in.
Mounting Type
Panel
Number Of Outputs
2
Output Type
Relay
Power Consumption
16 VA
Primary Type
Controller
Standards
UL, CSA, CE
Time, Response
200 ms (Typ.)
Voltage, Input
1 to 5, 0 to 5, 1 to 10
Voltage, Supply
100 to 240 VAC
Width
4.47 in.
Auxiliary Output
Relay — SPST-NO 3 A @ 250 VAC (Standard)
Supply Voltage
100-240 VAC/24 VAC/VDC
Thermocouple Inputs
K, J, T, E, L, U, N, R, S, B, W
Platinum Rtd Input
Pt100 and JPt100
Current Input
4 to 20 mA DC, 0 to 20 mA DC
Voltage Input
1 to 5 VDC, 0 to 5 VDC, 0 to 10 VDC
Control Output
SPST-NO 3 A @ 250 VAC/SSR 1 A @ 75 to 250 VAC
Lead Free Status / Rohs Status
RoHS Compliant part
Specifications
J Ratings
Note: 1. All control outputs are insulated from the input circuit.
Model
Supply voltage
Operating voltage range
Power consumption
Input
Mean Time Between Failure
Control output
(See Note 1)
Auxiliary output
Control method (See Note 2)
Setting method
Indication method - - 7-seg. digital display and LEDs E5AK: PV = 15 mm, SP = 10.5 mm
Potentiometer for valve positioning
(for E5AK-PRR and E5EK-PRR only)
Event input
Transmission output
Remote SP input
(for E5AK and E5EK only)
Current Transformer input (for E5AK and E5EK
only)
Other functions
Standards
4
p
2. Fuzzy self-tuning is available only when using the Digital Controller in standard control operation with temperature input.
y
p
p
Digital Process Controller
p
Thermocouple
Platinum resistance
thermometer (RTD)
Current input
Voltage input
Relay
Voltage
(
(pulse)
Linear
voltage
Linear
current
SPST-NO
Contact
i
input
No-contact
i
input
Standard
Option
l
t
t
g
)
E5AK
E5EK
E5CK
NPN
PNP
0 to 10 VDC
4 to 20 mA
0 to 20 mA
E5AK
E5EK
E5CK
ON
OFF
ON
OFF
Current
input
UL
CSA
CE
E5 K
E5jK Standard
100--240 VAC, 50/60 Hz
85% to 110% of rated supply voltage
16 VA
15 VA
10 VA (at 100 VAC)
14 VA (at 240 VAC)
K, J, T, E, L, U, N, R, S, B, W, PLII
JPt100, Pt100
4 to 20 mA, 0 to 20 mA
1 to 5 V, 0 to 5 V, 0 to 10 V
15.4 years (135,000 hours)
SPST, 3 A at 250 VAC (resistive load)
Mechanical life expectancy:
Electrical life expectancy:
20 mA at 12/24 VDC (with short-circuit protection)
20 mA at 24 VDC (with short-circuit protection)
Permissible load impedance: 1 kΩ min.
Resolution: Approximately 2600 steps
Permissible load impedance: 500 Ω max.
Resolution: Approximately 2600 steps
Permissible load impedance: 500 Ω max.
Resolution: Approximately 2600 steps
3 A at 250 VAC (resistive load)
3 A at 250 VAC (resistive load)
1A at 250 VAC (resistive load)
ON/OFF, Advanced PID Control (with auto-tuning) or Self-tuning
Digital setting using front panel keys or communications features
E5EK: PV = 14 mm, SP = 9.5 mm
E5CK: PV = 12 mm, SP = 8 mm
100 Ω to 2.5 kΩ
1 kΩ max.
100 kΩ min.
residual voltage: 1.5 V max.
leakage current: 0.1 mA max.
4 to 20 mA, permissible load impedance: 600 Ω max.,
resolution: Approximately 2600 steps
4 to 20 mA (Input impedance: 150 Ω)
Connect only an Omron Current Transformer (E54-CT1 or E54-CT3)
Manual output, heating/cooling control, SP limiter, loop burnout alarm, SP
ramp, MV limiter, MV change rate limiter, input digital filter, input shift,
run/stop, protect functions
Multiple SP, run/stop selection, transfer output functions, auto/manual
Communications (RS-232C, RS-422, or RS-485), Loop Break Alarm, and
Transfer Output.
File No.: E68481
File No.: LR59623
File No.: EN50081-2; EN50082-2; IEC 1010-1
10,000,000 operations min.
100,000 operations min.

Related parts for E5AK-AA2-500