E5CSV-Q1TFAC100240 Omron Automation, E5CSV-Q1TFAC100240 Datasheet - Page 3

no-image

E5CSV-Q1TFAC100240

Manufacturer Part Number
E5CSV-Q1TFAC100240
Description
Controller, Temperature, Digital
Manufacturer
Omron Automation
Type
Temperaturer
Datasheet

Specifications of E5CSV-Q1TFAC100240

Brand/series
E5CSV Series
Dimensions
48mmW×48mmH×78mmD
Enclosure Rating
IP00, IP20, IP66
Input Type
RTD/Thermocouple
Ip Rating
IP00, IP20, IP66
Mounting Type
DIN Rail
Output Type
Voltage
Primary Type
Controller
Standards
UL, cULus, CSA, CE
Voltage, Supply
100 to 240 VAC
Accuracy
0.1% FS
Supply Voltage
100-240 VAC
Control Output
RELAY
Voltage
12 VDC — 21 mA Max. (For Driving SSR) with Short-Circuit Protection
Alarm Output
SPST-NO 1 A @ 250 VAC
Lead Free Status / Rohs Status
RoHS Compliant part
■ Characteristics
Note: 1. The following exceptions apply to thermocouples.
■ Electrical Life Expectancy Curve for Relays (Reference Values)
Setting accuracy
Indication accuracy
(ambient temperature of 23° C)
Influence of temperature
Influence of voltage
Hysteresis (for ON/OFF control)
Proportional band (P)
Integral time (I)
Derivative time (D)
Alarm output range
Control period
Sampling period
Insulation resistance
Dielectric strength
Vibration
resistance
Shock resistance
Life expectancy
Weight
Degree of protection
Memory protection
EMC
Approved standards
Conformed standards
2. The following exceptions apply to platinum resistance ther-
500
300
100
50
30
10
5
3
1
0
• U, L: ±2° C ±1 digit max.
• R:
mometers.
Input set values 0, 1, 2, 3 for E5CSV: 0.5% FS ±1 digit max.
Input set value 1 for E5CSV: 0.5% FS ±1 digit max.
E5CSV
250 VAC, 30 VDC
(resistive load)
cosφ = 1
1
±3° C ±1 digit max. at 200° C or less
Malfunction 10 to 55 Hz, 20 m/s
Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hr each in X, Y, and Z directions
Malfunction 100 m/s
Destruction 300 m/s
Electrical
2
3
Thermocouple (See note 1.):
Platinum resistance thermometer (See note 2.):
R thermocouple inputs:
Other thermocouple inputs:
Platinum resistance thermometer inputs:
0.2% FS (0.1% FS for multi-input (thermocouple/platinum resistance thermometer) models)
1 to 999° C (automatic adjustment using auto-tuning/self-tuning)
1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning
1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning)
Absolute-value alarm:
Other:
Alarm hysteresis:
2/20 s
500 ms
20 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min between current-carrying terminals of different polarity
100,000 operations min. (relay output models)
Approx. 120 g (Controller only)
Front panel: Equivalent to IP66; Rear case: IP20; Terminals: IP00
EEPROM (non-volatile memory) (number of writes: 1,000,000)
EMI Radiated:
EMI Conducted:
ESD Immunity:
Radiated Electromagnetic Field Immunity:
Conducted Disturbance Immunity:
Noise Immunity (First Transient Burst Noise): EN 61000-4-4
Burst Immunity:
Surge Immunity:
Voltage Dip/Interrupting Immunity:
UL 61010C-1 (listing)
CSA C22.2 No.1010-1
EN 61326, EN 61010-1, IEC 61010-1
VDE 0106 Part 100 (finger protection), when the terminal cover is mounted.
Switching current (A)
4
2
2
5
min., 3 times each in 6 directions
min., 3 times each in 6 directions
6
2
for 10 min each in X, Y, and Z directions
Same as the control range
0% to 100% FS
0.2° C or ° F (fixed)
EN 55011 Group 1 Class A
EN 55011 Group 1 Class A
EN 61000-4-2: 4 kV contact discharge (level 2)
EN 61000-4-3: 10 V/m (80-1000 MHz, 1.4-2.0 GHz amplitude modulated) (level 3)
EN 61000-4-6: 3 V (0.15 to 80 MHz) (level 2)
2 kV power-line (level 3), 1 kV I/O signal-line (level 3)
EN 61000-4-5: Power line:
EN 61000-4-11 0.5 cycle, 100% (rated voltage)
(±0.5% of indication value or ±1° C, whichever is greater) ±1 digit max.
(±0.5% of indication value or ±1° C, whichever is greater) ±1 digit max.
(±1% of PV or ±10° C, whichever is greater) ±1 digit max.
(±1% of PV or ±4° C, whichever is greater) ±1 digit max.
(±1% of PV or ±2° C, whichever is greater) ±1 digit max.
Temperature Controllers
8 kV air discharge (level 3)
10 V/m (900 MHz pulse modulated)
Output line (relay output): Normal mode 1 kV; Common mode 2 kV
Normal mode 1 kV; Common mode 2 kV
E5CSV
3

Related parts for E5CSV-Q1TFAC100240