WM60AAA-120A STRUTHERS-DUNN, WM60AAA-120A Datasheet

no-image

WM60AAA-120A

Manufacturer Part Number
WM60AAA-120A
Description
Relay; Mercury Displacement, Up to 3PST, 60 Amp, AC and DC, 7 to 28VA 3 to 9W
Manufacturer
STRUTHERS-DUNN
Datasheet

Specifications of WM60AAA-120A

Application
Both series are same except for the types of gases used in the contactor tubes, the “ML” series was developed for use with resistive and tungsten loads on AC power only, the “M” series, which is our universal series is rated to be used on all types of loa
Brand/series
M60 Series
Contact Form
3PST-NO
Current, Rating
60 A
Dielectric Strength
2650 V (RMS) (Coil to Contacts, Across Open Contacts, Pole to Pole, Contacts to Frame), 1000 Megohms (Min.) @ 500 VDC (Insulation Resistance)
Dimensions
3.30 in. W x 5.062 in. H x 3.75 in. D
Function
Power
Material, Contact
Mercury
Relay Type
Electro Mechanical
Resistance, Coil
111 Ohms
Standards
UL, CSA
Temperature, Operating
-40 °C
Tolerance
± 10% (Resistance)
Voltage, Control
120 VAC
Voltage, Rating
240 VAC
GENERAL SPECIFICATIONS (@ 25° C)
Contacts:
Contact Configuration
Contact Material
Contact Rating
Contact Resistance, Initial
Coil:
Coils Available
Nominal Coil Power
Input Voltage Tolerance - AC
Input Voltage Tolerance - DC
Drop-out voltge
Duty
Timing:
Operate Time (max)
Release Time (max)
Dielectric Strength:
Across Open Contacts
Between Mutally Insulated Points
Insulation Resistance
Temperature:
Operating
Storage
Life Expectancy:
Electrical (full load operations)
Mechanical (no load operations)
Miscellaneous:
Mounting Position
Enclosure
Weight
Motor 120VAC 1 Phase
Motor 240VAC 1 Phase
120 / 240VAC Resistive
28VDC Resistive
E52197
*Material safety data sheet available on request
*Dispose of properly
The 35 & 60 series products are mercury displacement relays. Sealed tubes containing liquid
mercury assure contact surfaces are freshly replenished with every contact movement. Contact
resistance is among the lowest available for any electromechanical relay. The M35 series offers
superior long life performance. Products are available with 1, 2, or 3 poles rated 35 amps. Contacts
can be normally open or normally closed.
Optional DIN rail adaptors – 1 pole = 16-MDRDIN-1, 2 or 3 pole = 16-MDRDIN-2/3
1000 megohms @ 500VAC
50 milliohms max @ 6VDC
-40 to 105°C (-40 to 221°F)
-34 to 74°C (-30 to 165°F)
Vertical within 10 degrees
85% to 110% of nominal
80% to 110% of nominal
35 & 60 Series - Mercury Displacement Relay
7 to 28VA
Hermetically Sealed
Up to 3PST, 35 or 60 Amp
10% of nominal
Liquid Mercury
2650 VRMS
2650 VRMS
Up to 3PST
AC and DC
Continuous
5,000,000
250,000
35 Amp
35 Amp
Varies
50ms
80ms
5Hp
5Hp
35
3 to 9W
1000 megohms @ 500VAC
-40 to 105°C (-40 to 221°F)
50 milliohms max @ 6VDC
-34 to 74°C (-30 to 165°F)
Vertical within 10 degrees
85% to 110% of nominal
80% to 110% of nominal
Hermetically Sealed
7 to 28VA
10% of nominal
Liquid Mercury
2650 VRMS
2650 VRMS
Up to 3PST
AC and DC
Continuous
5,000,000
250,000
60 Amp
60 Amp
Varies
50ms
80ms
10Hp
5Hp
60
3 to 9W

Related parts for WM60AAA-120A

WM60AAA-120A Summary of contents

Page 1

Series - Mercury Displacement Relay Up to 3PST Amp The 35 & 60 series products are mercury displacement relays. Sealed tubes containing liquid mercury assure contact surfaces are freshly replenished with every contact movement. ...

Page 2

Series - Mercury Displacement Relay Up to 3PST Amp Ordering Code M35 A 120VAC Series M35 Series = 35 Amp M60 Series = 60 Amp Contact Arrangement A (1 N.O. tube N.O. ...

Page 3

Power Relays 30 - 300 Amp 1 Pole 1.94 (49.3) 2.38 (60.5) 2.05 (128.3) 1.18 (30.1) 2.30 (58.4) 1.94 (49.3) 3 Pole 3.75 (95.3) 3.13 (79.6) 4.98 (126.4) Ø .20 1.93 (5.2) 6 holes (49.1) *Normally closed tubes (B style) ...