HRP-600-15 Mean Well, HRP-600-15 Datasheet

Linear & Switching Power Supplies 645W 15V 43A ACTIVE PFC FUNCTION

HRP-600-15

Manufacturer Part Number
HRP-600-15
Description
Linear & Switching Power Supplies 645W 15V 43A ACTIVE PFC FUNCTION
Manufacturer
Mean Well
Datasheet

Specifications of HRP-600-15

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
SPECIFICATION
MODEL
OUTPUT
INPUT
PROTECTION
FUNCTION
ENVIRONMENT
SAFETY &
EMC
(Note 4)
OTHERS
NOTE
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
OVER VOLTAGE
OVER TEMPERATURE
DC OK SIGNAL
FAN CONTROL (Typ.)
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
MTBF
DIMENSION
PACKING
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max.)
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
600W Single Output with PFC Function
Note.5
Note.3
Note.2
80
90
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
3.3V
120A
0 ~ 120A
396W
100mVp-p
2.8 ~ 3.8V
1000ms, 50ms/230VAC
16ms/230VAC
85 ~ 264VAC
47 ~ 63Hz
PF>0.94/230VAC
8.5A/115VAC
35A/115VAC
<1.2mA / 240VAC
105 ~ 135% rated output power
Protection type :
3.96 ~ 4.62V
Protection type : Shut down o/p voltage, re-power on to recover
PSU turn on : 3.3 ~ 5.6V ; PSU turn off : 0 ~ 1V
Load 35 15% or RTH2 50
-40 ~ +70
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2, heavy industry level, criteria A
140.6K hrs min.
218*105*63.5mm (L*W*H)
1.5Kg;8pcs/13Kg/1.34CUFT
HRP-600-3.3
78.5%
2.0%
0.5%
1.0%
0.03%/
5
5
(TSW2)
(TSW1)detect on heatsink of power transistor
(0 ~ 50 )
(Refer to output load derating curve)
5V
120A
0 ~ 120A
600W
100mVp-p
4.3 ~ 5.8V
HRP-600-5
82%
6 ~ 7V
Constant current limiting, recovers automatically after fault condition is removed
2.0%
0.5%
1.0%
detect on heatsink of power doide
5A/230VAC
I/P-FG:1.5KVAC
70A/230VAC
120 ~ 370VDC
MIL-HDBK-217F (25 )
16ms/115VAC at full load
PF>0.99/115VAC at full load
2500ms, 50ms/115VAC at full load
Fan on
HRP-600-7.5
7.5V
80A
0 ~ 80A
600W
100mVp-p
6.8 ~ 9V
87%
9.4 ~ 10.9V
2.0%
0.5%
1.0%
O/P-FG:0.5KVAC
12V
53A
0 ~ 53A
636W
120mVp-p
10.2 ~ 13.8V
HRP-600-12
88%
14.4 ~ 16.8V
for 3.3V,5V,7.5V ; 100
1.0%
0.3%
0.5%
15V
43A
0 ~ 43A
645W
150mVp-p
13.5 ~ 18V
HRP-600-15
88%
18.8 ~ 21.8V
1.0%
0.3%
0.5%
5
H R P - 6 0 0
(TSW2)
HRP-600-24
24V
27A
0 ~ 27A
648W
150mVp-p
21.6 ~ 28.8V
88%
30 ~ 34.8V
1.0%
0.2%
0.5%
detect on main
File Name:HRP-600-SPEC 2010-11-29
HRP-600-36
36V
17.5A
0 ~ 17.5A
630W
200mVp-p
28.8 ~ 39.6V
89%
41.4 ~ 48.6V
1.0%
0.2%
0.5%
power
output choke
HRP-600-48
48V
13A
0 ~ 13A
624W
240mVp-p
40.8 ~ 55.2V
89%
57.6 ~ 67.2V
s e r i e s
1.0%
0.2%
0.5%
for others

Related parts for HRP-600-15

HRP-600-15 Summary of contents

Page 1

... Fan on (Refer to output load derating curve I/P-FG:1.5KVAC O/P-FG:0.5KVAC MIL-HDBK-217F ( HRP-600-15 HRP-600-24 HRP-600-36 15V 24V 36V 43A 27A 17. 43A 0 ~ 27A 0 ~ 17.5A 645W 648W 630W 150mVp-p 150mVp-p 200mVp-p 13 ...

Page 2

... Output Derating VS Input Voltage 100 (HORIZONTAL Case No. 977A 32.8 O 32.8 18max. Mating Housing Terminal DC-OK GND HRS DF11-4DS HRS DF11-**SC or equivalent or equivalent + fosc : 70KHz RECTIFIERS & FILTER DETECTION CIRCUIT O.T.P. O.V.P. 90 100 125 135 155 INPUT VOLTAGE (V) 60Hz File Name:HRP-600-SPEC 2010-11- Unit: 264 ...

Related keywords