HRP-450-15 Mean Well, HRP-450-15 Datasheet

Linear & Switching Power Supplies 450W 15V 30A W/PFC

HRP-450-15

Manufacturer Part Number
HRP-450-15
Description
Linear & Switching Power Supplies 450W 15V 30A W/PFC
Manufacturer
Mean Well
Datasheet

Specifications of HRP-450-15

Product
Switching
Commercial/medical
Commercial
Output Power Rating
450 W
Input Voltage
85 VAC to 264 VAC, 120 VDC to 370 VDC
Number Of Outputs
1
Output Voltage (channel 1)
15 V
Output Current (channel 1)
30 A
Mounting Style
Chassis
Dimensions
218 mm L x 105 mm W x 41 mm H
Open Frame/enclosed
Enclosed
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
SPECIFICATION
MODEL
OUTPUT
INPUT
PROTECTION
FUNCTION
ENVIRONMENT
SAFETY &
EMC
(Note 4)
OTHERS
NOTE
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max.)
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
OVER VOLTAGE
OVER TEMPERATURE
DC OK SIGNAL
FAN CONTROL (Typ.)
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
MTBF
DIMENSION
PACKING
450W Single Output with PFC Function
Note.5
Note.3
Note.2
90
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
3.3V
90A
0 ~ 90A
297W
80mVp-p
2.8 ~ 3.8V
1000ms, 100ms/230VAC
16ms/230VAC
85 ~ 264VAC
47 ~ 63Hz
PF>0.95/230VAC
5A/115VAC
HRP-450-3.3
80%
35A/115VAC
<1.5mA / 240VAC
105 ~ 135% rated output power
Protection type :
3.96 ~ 4.62V
Protection type : Shut down o/p voltage, re-power on to recover
PSU turn on : 3.3 ~ 5.6V ; PSU turn off : 0 ~ 1V
Load 20 10% or RTH2 50
-40 ~ +70
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2, heavy industry level, criteria A
139.9K hrs min.
218*105*41mm (L*W*H)
1.19Kg; 12pcs/15.3Kg/0.82CUFT
2.0%
0.5%
1.0%
0.03%/
5
(70
(0 ~ 50 )
(Refer to output load derating curve)
5V
90A
0 ~ 90A
450W
80mVp-p
4.3 ~ 5.8V
HRP-450-5
2.4A/230VAC
83%
6 ~ 7V
5
2.0%
0.5%
1.0%
Constant current limiting, recovers automatically after fault condition is removed
I/P-FG:1.5KVAC
120 ~ 370VDC
70A/230VAC
MIL-HDBK-217F (25 )
16ms/115VAC at full load
5V only) (TSW1 : detect on heatsink of power transistor) ; 90
PF>0.99/115VAC at full load
2500ms, 100ms/115VAC at full load
Fan on
HRP-450-7.5
7.5V
60A
0 ~ 60A
450W
100mVp-p
6.8 ~ 9V
86.5%
9.4 ~ 10.9V
2.0%
0.5%
1.0%
O/P-FG:0.5KVAC
12V
37.5A
0 ~ 37.5A
450W
120mVp-p
10.2 ~ 13.8V
HRP-450-12
88%
14.4 ~ 16.8V
1.0%
0.3%
0.5%
HRP-450-15
15V
30A
0 ~ 30A
450W
150mVp-p
13.5 ~ 18V
89%
18.8 ~ 21.8V
1.0%
0.3%
0.5%
H R P - 4 5 0
HRP-450-24
24V
18.8A
0 ~ 18.8A
451.2W
150mVp-p
21.6 ~ 28.8V
88%
30 ~ 34.8V
1.0%
0.2%
0.5%
5
(TSW2 :
detect on heatsink of power doide
File Name:HRP-450-SPEC 2010-11-29
HRP-450-36
36V
12.5A
0 ~ 12.5A
450W
240mVp-p
28.8 ~ 39.6V
89%
41.4 ~ 48.6V
1.0%
0.2%
0.5%
HRP-450-48
40.8 ~ 55.2V
48V
9.5A
0 ~ 9.5A
456W
240mVp-p
89.5%
57.6 ~ 67.2V
s e r i e s
1.0%
0.2%
0.5%
)

Related parts for HRP-450-15

HRP-450-15 Summary of contents

Page 1

... Constant current limiting, recovers automatically after fault condition is removed 9.4 ~ 10.9V 14.4 ~ 16. only) (TSW1 : detect on heatsink of power transistor Fan on (Refer to output load derating curve I/P-FG:1.5KVAC O/P-FG:0.5KVAC MIL-HDBK-217F ( HRP-450-15 HRP-450-24 HRP-450-36 15V 24V 36V 30A 18.8A 12. 30A 0 ~ 18. 12.5A 450W 451.2W 450W ...

Page 2

... Output Derating VS Input Voltage 100 (HORIZONTAL Case No. 995A 32.8 O 32.8 18max. Mating Housing Terminal HRS DF11-4DS HRS DF11-**SC or equivalent or equivalent PMW fosc : 70KHz RECTIFIERS & FILTER DETECTION CIRCUIT O.T.P. O.V. 100 125 135 155 INPUT VOLTAGE (V) 60Hz File Name:HRP-450-SPEC 2010-11- Unit: 264 ...

Page 3

... Signal DC-OK signal is a TTL level signal. High when PSU turns on. Between DC-OK(pin5) and GND(pin6) Output Status 3 OFF CN100 (Pin3) (Pin4) LOAD Fig 1.1 CN100 Fig 2 CN100 2 GND DC- Sense lines should be twisted in pairs CN100 1 2 GND DC- File Name:HRP-450-SPEC 2010-11-29 ...

Related keywords