CP2000DC54-PE Lineage Power, CP2000DC54-PE Datasheet - Page 4

no-image

CP2000DC54-PE

Manufacturer Part Number
CP2000DC54-PE
Description
Linear & Switching Power Supplies -40 to -72Vdc +/-54Vdc 2000W
Manufacturer
Lineage Power
Datasheet

Specifications of CP2000DC54-PE

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Data Sheet
Lineage Power
Specifications (continued)
Physical
Length (in./mm)
Width (in./mm)
Height (in./mm)
Weight (lb/kg)
Environmental
Parameter
Ambient Temperature
Storage Temperature
Humidity
Shock and Vibration
Earthquake Rating
Acoustic Noise
Radiated Emissions
Conducted Emissions - dc
ESD
Radiated Immunity
Differential mode surge
Differential mode surge
transient
Common mode surge
(1.2/50s pulse)
Conducted Immunity
Reliability (calculated)
Isolation
Service Life
2. Designed to start at an ambient as low as -40°C, but may not meet operational limits until above -5°C.
3. Radiated emissions compliance was met using a Lineage Power shelf. This shelf includes output common and differential
mode capacitors that assist in meeting compliance.
Output-Chassis/Signals
Input-Chassis/Signals
Input-Output/Signals
Drop and Tip Over
Main-Aux Outputs
Ambient Derating
Operational Test
Power Derating
Test Levels
3
Operating
2
FCC and CISPR22 (EN55022) - Class A
Telcordia GR-1089-CORE and CISPR22 (EN55022) - Class A
Error free per EN/IEC 61000-4-2 Level 4 (8 kV contact discharge, 15 kV air discharge).
Error free per EN/IEC 61000-4-3 Level 3 (10 V/m).
Error free per EN/IEC 61000-4-6 Level 3 (10Vrms).
1700
2250
2250
2250
Min
-40
-5
5
4
2
13.85 / 351.8
4.00 / 101.6
1.66 / 42.2
4.6 / 2.1
400,000
Typ
55
10
1
100
1000
1000
Max
45
85
95
1
Vdc
Vdc
Vdc
Hours
Years
Units
%/°C
Zone
dBA
Vdc
°C
°C
°C
%
3
Notes
Air inlet from sea level to 5,000 feet.
Per 1,000 feet above 5,000 feet.
Up to 55°C
Relative humidity, non-condensing
IEC 68-2
IEC 721-3-2
IEC 68-2-31
Per Telcordia GR-63-CORE, all floors, when
installed in CP Shelf.
Noise is proportional to fan speed, load and
ambient temperature.
At ambient of 25°C at full load per Telcordia SR-
332, Reliability Prediction for Electronic
Equipment, Method I Case III.
Per EN60950.
Per IEEE802.3af.
25°C ambient, full load excluding fans.
ANSI T1.315, No errors
No errors. IEEE C62.41 defined pulse transient
CP2000DC54-PE DC/DC Converter
Compact Power Line
4

Related parts for CP2000DC54-PE