E2EY-X8C1 Omron, E2EY-X8C1 Datasheet - Page 2

Proximity Sensors M30 NPN-NO out 8mm Non-ferrous inductiv

E2EY-X8C1

Manufacturer Part Number
E2EY-X8C1
Description
Proximity Sensors M30 NPN-NO out 8mm Non-ferrous inductiv
Manufacturer
Omron
Series
E2EYr
Type
Non-Ferrous Metal Detecting Cylindricalr
Datasheet

Specifications of E2EY-X8C1

Maximum Operating Temperature
+ 55 C
Supply Voltage
30 V
Operating Supply Voltage
10 V to 30 V
Sensing Distance
8 mm
Minimum Operating Temperature
- 10 C
Features
High visibility indicator
Sensor Type
Inductive
Sensing Object
Metallic
Response Frequency
70Hz
Material - Body
Nickel-Plated Brass
Shielding
Shielded
Voltage - Supply
10 V ~ 30 V
Output Type
NPN-NO
Terminal Type
3-Wire
Package / Case
Cylinder, Threaded - M30
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Ratings and Specifications
* The response frequency is an average value. Measurement conditions are as follows: standard sensing object, a distance of twice the standard sensing object, and
Item
Sensing distance
Set distance
Differential travel
Detectable object
Standard sensing object
Response frequency
Power supply voltage
(operating voltage range)
Current consumption
Control
output
Indicators
Operation mode (with sensing
object approaching)
Protection circuits
Ambient temperature range
Ambient humidity range
Temperature influence
Voltage influence
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Degree of protection
Connection method
Weight (packed state)
Materials
Accessories
a set distance of half the sensing distance.
Load current
Residual
voltage
Case
Sensing surface
Clamping nuts
Toothed washer
*
Model
4 mm ±10%
0 to 2.8 mm
20% max. of sensing distance
Non-ferrous metal (Does not detect ferrous metal.)
Aluminum: 18 × 18 × 1 mm
70 Hz
12 to 24 VDC (10 to 30 VDC), ripple (p-p): 10% max.
20 mA max.
NPN open-collector output, 100 mA max. (at 30 VDC)
2 V max. (Load current: 100 mA, Cable length: 2 m)
Detection indicator (red)
Load ON: NO (Refer to the timing charts under I/O Circuit Diagrams on page 3 for details.)
Reverse polarity protection, Load short-circuit protection, Surge suppressor
Operating/Storage: −10 to 55°C (with no icing or condensation)
Operating/Storage: 35% to 95% (with no condensation)
±20% max. of sensing distance at 23°C in the temperature range of −10 to 55°C
±2.5% max. of sensing distance at rated voltage in rated voltage ±15% range
50 MΩ min. (at 500 VDC) between current-carrying parts and case
1,000 VAC, 50/60 Hz for 1 minute between current-carrying parts and case
Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions
Destruction: 1,000 m/s
IEC 60529 IP67, in-house standards: oil-resistant
Pre-wired Models (Standard cable length: 2 m)
Approx. 140 g
Nickel-plated brass
Heat-resistant ABS
Nickel-plated brass
Zinc-plated iron
E2EY-X4C1
2
10 times each in X, Y, and Z directions
---
8 mm ±10%
0 to 5.6 mm
Aluminum: 30 × 30 × 1 mm
Approx. 190 g
E2EY-X8C1
E2EY
2