2734507 Phoenix Contact, 2734507 Datasheet - Page 2

I/O Modules IBS RL 24 DO 16/ 8-R-LK-2MBD

2734507

Manufacturer Part Number
2734507
Description
I/O Modules IBS RL 24 DO 16/ 8-R-LK-2MBD
Manufacturer
Phoenix Contact
Datasheet

Specifications of 2734507

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
IBS RL 24 DO 16/8-R-LK-2MBD
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2734507
I/O errors can be clearly localized by means of extended diagnostics. Short-circuits of the power supply of the sensors,
for example, are reported in groups of 4 inputs. And, in the case of a short-circuit at an output, the respective output is
even reported directly. This information will be made available to the controller and displayed at the module.
In the case of modules with fiber optic connection, the diagnostics capability even goes one step further. By using the
latest fiber optic technology, the quality of the transmission path is permanently ascertained and optimally adjusted. This
information is available to the controller and at the module. Due to these additional features, slow deterioration of the
transmission path can be detected before errors occur during transmission or transmission is interrupted.
In the case of Ruggedline modules, the bus medium can be selected. Apart from versions with fiber optic connection
(polymer fiber), there are modules which are used with twisted pair cables. The bus medium can be changed from FO
installation to a copper medium at any time using the corresponding plug-in adapters.
The bus is connected by means of IP67 plug connectors, which transport both the bus signal and the power supply to
the modules. For easy preparation, the power supply cable is connected to the plug using the QUICKON fast connection
method, and connection of the fiber optic cable is made using a simple cutting and assembly tool; additional polishing is
not necessary.
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Technical data
General data
Width
Height
Depth
Note on dimensions
Weight
Note on weight specifications
Mounting type
Ambient temperature (operation)
Ambient temperature (storage/transport)
Permissible humidity (operation)
Permissible humidity (storage/transport)
Air pressure (operation)
Air pressure (storage/transport)
Degree of protection
Note
Test section
Interface
Fieldbus system
Name
Connection method
Transmission speed
Transmission physics
Order No.: 2734507
179 mm
67 mm
71 mm
With bus connectors and mounting plate
810 g
Without connector or mounting plate
Wall mounting
-20 °C ... 55 °C
-25 °C ... 70 °C
100 %
95 % (no condensation)
800 hPa ... 1060 hPa (up to 2000 m above sea level)
700 hPa ... 1060 hPa (up to 3000 m above sea level)
IP67, when screwed together
Seal unused slots/connections to ensure the degree of protection.
Between bus logic and outputs 500 V AC 50 Hz 1 min
INTERBUS
Remote bus
Optic fiber (polymer fiber 980/1000 µm)
2 MBaud
FO
Jun 3, 2011
Page 2 / 6