E5EZ-PRR
Descriptions of Each Level
Protect Level
Operation Level
Adjustment Level
Manual Control Level
Initial Setting Level
Advanced Function Setting Level
Communications Setting Level
• To select this level, simultaneously press the
• This level is displayed when you turn the power ON. You can
• Normally, select this level during operation. During operation, the
• To select this level, press the
• This level is for entering set values and offset values for control.
• Pressing the A key under the operation/adjustment level for 1
• To access this level, press the
• To activate this level, set the parameters in the “initial setting/
• The initial setting level can be accessed from this level.
• This level is for setting the automatic display return time, MV lim-
• To select this level, press the
at least 3 seconds. This level is to prevent unwanted or acciden-
tal modification of parameters. Protected levels will not be dis-
played, and so the parameters in that level cannot be modified.
move to the protect level, initial setting level, manual control level
and adjustment level from this level.
process value and manipulated variable can be monitored, and
the set points, alarm values, and upper- and lower-limit alarms
can be monitored and modified.
This level contains parameters for setting the AT (auto-tuning),
communications writing enable/disable, hysteresis, multi-SP, in-
put shift values, heater burnout alarm (HBA) and PID constants.
You can move to the top parameter of the operation level, initial
setting level and protect level from here.
second or more will activate manual mode, and switch to the
manual control level.
Under manual control, only “process value/set value/valve open
percentage (manual MV)” can be displayed. Under the “process
value/set value/valve open percentage (manual MV)” manual
control level, pressing the A key for 1 second or more will switch
to automatic mode, switch to the operation level, display the de-
fault in the level, and allow manual operation of MV in this mode.
the operation level or adjustment level. 1 second later, the PV dis-
play will blink. This level is used to indicate input type and select
control method, control period, direct/reverse operation, and
alarm type. You can move to the advanced function setting level
or communications setting level from this level. Press the
for at least 1 second to switch to the operation level. Press the
key less than 1 second to switch to the communications level.
communications protect” under the “protect level” to “0” and then
enter the password (“-169”) in the initial setting level.
iter, event input assignment, standby sequence, alarm hystere-
sis, and ST (self-tuning).
initial setting level. When the communications function is used,
set the communications conditions in this level. Communicating
with a personal computer (host computer) allows set points to be
read and written, and manipulated variables to be monitored.