AFF1 Hammond Manufacturing, AFF1 Datasheet

Accessories for Racks & Cabinets FILTER FOR DTD5201

AFF1

Manufacturer Part Number
AFF1
Description
Accessories for Racks & Cabinets FILTER FOR DTD5201
Manufacturer
Hammond Manufacturing
Datasheet

Specifications of AFF1

Product
Rack Accessories
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
388
Cooling Products
Sizing an Air Conditioner
Sizing an Air Conditioner
The proper selection of an air conditioner is determined by the following steps:
Step 1) Internal heat load quoted as Watts that must be dissipated.
Step 2) The exposed surface area of the enclosure.
Step 3) Temperature differential required between maximum inside temperature and maximum outside ambient.
Step 4) Final calculation of the above.
The DTS/DTT offering is available in the most popular selection of cooling capacities, sizes, voltages and mounting configurations. Available
capacities range from 1,200 to 16,000 BTU/H in both side mounting and top mounting models. All models use powerful radial fans for maximum
air circulation inside the enclosure in ambient temperatures of 125°F (+52°C). Models from 2,000 BTU/H capacity are equipped with thermal
expansion valves for optimal use of the evaporator heat exchange surface under all operating conditions. For additional protection of the
compressor motor, these valves are supplied as standard with Maximum Operating Pressure control devices (MOP). For energy conservation,
the use of hot gas bypass valves is limited to the unloaded starting and control of large compressors from 8,000 BTU/H upwards. All air
conditioners were developed, designed and subject to final inspections in accordance with international standards.
Technical references and DXF downloads available at www.hammfg.com
© Hammond Manufacturing
Step Four
(in Watts) that must be dissipated.
Determine the internal heat load
1 Watt = 3.413 BTU/H
(Watts x 3.413)
Canada: 519.822.2960 or 905.456.3770
+
Quality Enclosures. Service Excellence.
2(h" x w") + 2(h" x d") + (w" x d")
(Example for freestanding enclosure)
Calculate the exposed surface
area of the enclosure:
1 m
144
[1.25 x Area ft
2
= 10.76 ft
2
USA: 716.630.7030
=Area (ft
2
All dimensions in inches unless specified otherwise
2
)
x
Determine the temperature differential
by subtracting the maximum allowable
temperature inside the enclosure (T
from the maximum ambient temperature
outside the enclosure (T
1°C or 1°K T=1.8°F T
Data Subject to change without notice
DT (°F)] = BTU/H
BTU/H. Capacity Rating.
T
o
Capacity Required
-T
i
= DT
o
).
i
)

AFF1 Summary of contents

Page 1

... BTU/H upwards. All air conditioners were developed, designed and subject to final inspections in accordance with international standards. Technical references and DXF downloads available at www.hammfg.com 388 © Hammond Manufacturing 10. ...

Page 2

... Protection DTT4500A115LG 12 DTT4500A230LG 12 A115 units can be operated 110 V and A460 units can be operated at 50Hz at 380V. Technical references and DXF downloads available at www.hammfg.com © Hammond Manufacturing Canada: 519.822.2960 or 905.456.3770 General Specifications for All Air Conditioners Rating BTU/H Rated Voltage Hz 1,200 115 ...

Page 3

... Running Amps 2.2 A Starting Current 15.7 A Line Cord With plug Technical references and DXF downloads available at www.hammfg.com 390 © Hammond Manufacturing Description • Designed for side mounting where hot spot cooling or low capacity cooling is required. • Compact design uses minimal surface area. ...

Page 4

... Starting Current 13.8 A 7.4 A Line Cord With plug Without plug Technical references and DXF downloads available at www.hammfg.com © Hammond Manufacturing Canada: 519.822.2960 or 905.456.3770 Side Mounting DTS Series Description • Compact design for side mounting on any enclosure surface where hot spot cooling or low capacity cooling is required. • ...

Page 5

... Power Consumption 690 W Running Amps Starting Current Line Cord With Plug Technical references and DXF downloads available at www.hammfg.com 392 © Hammond Manufacturing Description • Compact design for side mounting on any enclosure surface where hot spot or low capacity cooling is required. • Closed loop cooling ensures clean ...

Page 6

... Running Amps 6.7 A Starting Current 17.5 A Line Cord With plug Technical references and DXF downloads available at www.hammfg.com © Hammond Manufacturing Canada: 519.822.2960 or 905.456.3770 Side Mounting DTS Series Description • Compact design for side mounting on any enclosure surface where hot spot or low capacity cooling is required. • ...

Page 7

... DTS3141A115LG DTS3141A230LG 99 DTS3241A115LG 127 127 DTS3241A230LG Technical references and DXF downloads available at www.hammfg.com 394 © Hammond Manufacturing Features • R134a refrigerant. • Thermostat control accessible from inside enclosure. • Hot gas bypass valve prevents evaporator freeze up while minimizing heavy inrush currents on large BTU/H units. • ...

Page 8

... Exterior Case Galvanized sheet steel Finish RAL7035 Light Grey powder finish NEMA Rating Enclosures IP 54/NEMA 12 Technical references and DXF downloads available at www.hammfg.com © Hammond Manufacturing Canada: 519.822.2960 or 905.456.3770 Side Mounting DTS Series DTS3241A115/ A230LG 7,500 BTU/H (2,197 Watts) R134a 500 g Factory setting +95°F (+35°C) +125° ...

Page 9

... DTS8000A115LG 189 189 DTS8000A230LG DTS12000A115LG 189 DTS12000A230LG 189 Technical references and DXF downloads available at www.hammfg.com 396 © Hammond Manufacturing Features • R134a refrigerant. • Thermostat control. • Hot gas bypass valve prevents evaporator freeze up while minimiz- ing heavy inrush currents on large BTU/H units. • ...

Page 10

... Exterior Case Galvanized sheet steel Finish RAL7035 Light Grey powder finish NEMA Rating Enclosures IP 54/NEMA 12 Technical references and DXF downloads available at www.hammfg.com © Hammond Manufacturing Canada: 519.822.2960 or 905.456.3770 Side Mounting DTS Series DTS12000A115LG DTS12000A230LG 12,000 BTU/H (3,500 Watts) R134a 850 g Factory setting +95° ...

Page 11

... Galvanized sheet steel Finish RAL7035 light grey finish NEMA Rating Enclosures IP 54/NEMA 12 Technical references and DXF downloads available at www.hammfg.com 398 © Hammond Manufacturing Quality Enclosures. Service Excellence. Canada: 519.822.2960 or 905.456.3770 USA: 716.630.7030 Description • Designed for side mounting on any enclosure surface where high capacity system cooling is required. • ...

Page 12

... Running Amps 7.7 A 5.2 A Starting Current 24.9 A 18.5 A Line Cord With plug Without plug Technical references and DXF downloads available at www.hammfg.com © Hammond Manufacturing Canada: 519.822.2960 or 905.456.3770 Top Mounting DTT Series Features • R134a refrigerant. • Thermostat control. • Expansion valve increases effi ...

Page 13

... Weight Quality Enclosures. Service Excellence. Canada: 519.822.2960 or 905.456.3770 USA: 716.630.7030 RAL 7032 Beige Use with Part No. Air Conditioner PG3RAL DTS1200 - DTS3500 DTS8000 - DTS12000 PG5RAL AFF1 DTT4500 Use With Filter Density A B Air Conditioner (g/m 8.30 8.30 DTS1200 - DTS6000 150 210 210 ...

Page 14

... Running Amps 6.0 A Starting Current 28 A Line Cord With plug Technical references and DXF downloads available at www.hammfg.com © Hammond Manufacturing Canada: 519.822.2960 or 905.456.3770 Side Mounting DTS Series - NEMA 3R Description • Compact design for side mounting on any enclosure surface where spot cooling or low capacity cooling is required. • ...

Page 15

... Running Amps 7.2 A Starting Current 17.1 A Terminal Block Line Cord Technical references and DXF downloads available at www.hammfg.com 402 © Hammond Manufacturing Description • Designed for side mounting on any enclosure surface where high capacity system cooling is required. • Closed loop cooling ensures clean ...

Page 16

... Galvanized Steel Powdercoat Finish Finish RAL7035 Light Grey powder finish (LG) NEMA Rating Enclosures IP56 /NEMA 3R/4 Technical references and DXF downloads available at www.hammfg.com © Hammond Manufacturing Canada: 519.822.2960 or 905.456.3770 Side Mounting DTS Series - NEMA 3R, 4 DTS3261A115/230N3LG 7,500 BTU/H (2,197 Watts) R134a 500 g Factory setting +95° ...

Page 17

... Running Amps 7.2 A Starting Current 17.1 A Line Cord Terminal Block Technical references and DXF downloads available at www.hammfg.com 404 © Hammond Manufacturing Description • Designed for side mounting on any enclosure surface where high capacity system cooling is required. • Closed loop cooling ensures clean ...

Page 18

... Stainles Steel Finish Polish #3 NEMA Rating Enclosures IP56 /NEMA 3R/4x Technical references and DXF downloads available at www.hammfg.com © Hammond Manufacturing Canada: 519.822.2960 or 905.456.3770 Side Mounting DTS Series - NEMA 3R 4000 & 7500 BTU/H - Stainless Steel DTS3281A115/230N4SS 7,500 BTU/H (2,197 Watts) R134a 500 g Factory setting +95° ...