NIC1001-C01-10VV Eltek Valere, NIC1001-C01-10VV Datasheet - Page 12

no-image

NIC1001-C01-10VV

Manufacturer Part Number
NIC1001-C01-10VV
Description
Manufacturer
Eltek Valere
Datasheet

Specifications of NIC1001-C01-10VV

Lead Free Status / Rohs Status
Supplier Unconfirmed
System Parameters
Load 3 Reconnect
Delay Time**
BDT Status
BD Time (Duration)
BDT Alarm
(Alarm V)
BDT Abort* (Abort V)
T Comp BDT
BDT State
Temp Alarm Thresh.
(Int Max)
Temp Alarm Thresh.
(Int Min)
Temp Alarm Thresh.
(Ext Max)
Temp Alarm Thresh.
(Ext Min)
HV Restart Enabled
The amount of time delayed after
reaching the load 3 reconnect voltage
set point, before closing the load 3
disconnect contactor
Enables or Disables the battery
discharge test feature
Sets the length of time that the battery
discharge test will run.
Sets the voltage at which an alarm will
be generated if the battery voltage falls
below it during the Battery Discharge
Test. This is a user adjustable value
The voltage at which the battery
discharge test will abort at when the
system voltage drop below this point.
This is a user settable value that should
be at least 2V below BDT Alarm (Alarm
V).
Enabling T Comp BDT will take thermal
compensation effects into account
during Battery Discharge Test. Disabling
T Comp BDT will disable Thermal
Compensation effects during BDT.
Both Thermal Compensation, and T
Comp BDT have to be Enabled for
thermal comp. effects to take place
during BDT.
Starts or stops the battery discharge test
when BDT Status is enabled.
When internal temperature exceeds this
set point, Temp Alarm
( Minor) is issued
When internal temperature falls below
this set point, Temp Alarm ( Minor) is
removed
When external temperature exceeds this
set point, Temp Alarm ( Minor) is issued
When external temperature falls below
this set point, Temp Alarm ( Minor) is
removed
When enabled, all the rectifiers in the
plant will make up to 3 restart attempts
before shutting down permanently
Description
Page - 12 - of 19
Nominal
Disabled
Disabled
Enabled
11.25 V
12 Volt
10.75V
60 min
5 Sec
90°C
85°C
90°C
85°C
Stop
Nominal
Disabled
Disabled
Enabled
24 Volt
60 min
22.5 V
21.5V
5 Sec
90°C
85°C
90°C
85°C
Stop
Nominal
Disabled
Disabled
Enabled
48 Volt
60 min
5 Sec
90°C
85°C
90°C
85°C
45 V
43 V
Stop