793-5607 WAGO, 793-5607 Datasheet - Page 30

WMB MKR 5-5.2MM 51-100 (2X)

793-5607

Manufacturer Part Number
793-5607
Description
WMB MKR 5-5.2MM 51-100 (2X)
Manufacturer
WAGO
Series
WMBr
Datasheet

Specifications of 793-5607

Rohs Compliant
YES
Accessory Type
Terminal Block Marker
Legend
51 To 100
Legend Color
Black
Marker Color
White
Background Color
White
For Use With
Terminal Blocks And Connectors
TOPJOB
N-Disconnect Terminal Blocks and Power Distribution Disconnect Terminal Blocks
Series 2002, 2006 and 2016
0.25
250 V/4 kV/3
32 A
Terminal block width 5.2 mm / 0.205 in
L 10 – 12 mm / 0.43 in
1-conductor N-disconnect terminal block
blue
1-conductor power distribution disconnect terminal
block
grey
End and intermediate plate, 0.8 mm /0.031 in thick
orange
For appropriate through and earth conductor
terminal blocks see page 17
Testing with test plug Ø 2 mm
Removing the separator plate from the busbar
carrier.
– 2.5 (4) mm
< 35.5 mm /1.4 in >
<______ 56 mm /2.2 in _______>
®
S
Item
No.
2002-7114
2002-7111
2002-7192
2
AWG 22 – 12
Pack.-unit
pcs
100 (4 x 25)
50
50
0.5
250 V/4 kV/3
51 A
Terminal block width 7,5 mm / 0.295 in
L 13 – 15 mm / 0.55 in
1-conductor N-disconnect terminal block
blue
1-conductor power distribution disconnect terminal
block
grey
End and intermediate plate, 1 mm /0.039 in thick
orange
For appropriate through and earth conductor
terminal blocks see page 17
Operation of the slide link using a simple
screwdriver
Insertion of the separator plate.
To protect the N-busbar against accidental contact
– 6 (10) mm
< 35.5 mm /1.4 in >
<_______ 60 mm /2.36 in ________>
Item
No.
2006-7114
2006-7111
2006-7192
2
30
AWG 20 – 8
Pack.-unit
pcs
100 (4 x 25)
50
50
0.5
250 V/4 kV/3
76 A
Terminal block width 12 mm / 0.472 in
L 18 – 20 mm / 0.75 in
1-conductor N-disconnect terminal block
blue
1-conductor power distribution disconnect terminal
block
grey
End and intermediate plate, 1 mm /0.039 in thick
orange
For appropriate through and earth conductor
terminal blocks see page 17
WAGO N-disconnect terminal blocks meet this
requirement.
The WAGO power distribution disconnect terminal
blocks meet these requirements.
see also appropriate through terminal blocks
For the construction and operation of power
installations in fire hazardous locations or public
buildings, such as meeting places, stores, hospitals,
schools, theaters, hotels etc., the VDE 0100 or VDE
0108-1 standards must be observed. VDE 0100-482
must be observed for fire hazardous locations. Both
VDE regulations determine that insulation testing must
be possible for every circuit without disconnecting the
N-conductor.
According to VDE 0107 “Installing and testing
electrical installations in medical locations“, the
equipotential bonding conductors must be connected
to a potential equalization busbar. The potential
equalization busbar and the protective earth
conductor busbar must be accommodated in a
common housing and be connected by means of a
disconnectable connection using a copper conductor
with a minimum cross section of 16 mm2.
Furthermore, all equipotential bonding conductors
must be connected to the potential equalization
busbar in such a way that they are clearly arranged,
that they can be disconnected individually and
accessed at any time and, depending on their
function, they must be provided with captive marking.
– 16 (25
< 37 mm /1.46 in >
<____________ 69 mm /2.72 in __________>
“f“
) mm
Item
No.
2016-7114
2016-7111
2016-7192
2
AWG 20 – 4
Pack.-unit
pcs
100 (4 x 25)
25
25