CUB4TC00 Red Lion Controls, CUB4TC00 Datasheet

METER PANEL LCD THERMOCOUPLE

CUB4TC00

Manufacturer Part Number
CUB4TC00
Description
METER PANEL LCD THERMOCOUPLE
Manufacturer
Red Lion Controls
Series
CUB4r
Type
Thermocoupler
Datasheet

Specifications of CUB4TC00

Display Type
LCD Non-Backlit
Display Face Size
2.95" L x 1.54" W (74.9 x 39.1mm)
Display Digits
5
Display Digits - Height
0.480" (12.19mm)
Backlight
Without
Mounting Type
Panel Mount
Termination
Screw Terminals
Voltage - Supply
9 V ~ 26 V
Applications
Thermocouple Input - Type T, E, J, K, R, S, B, N, or mV
Number Of Digits/alpha
5
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
Q1421239
Q763911
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
ORDERING INFORMATION
MODEL CUB4RT/TC - INTELLIGENT TEMPERATURE INDICATORS
DESCRIPTION
based indicators, with a selectable decimal point. Models are available for use
with RTD or Thermocouple sensors. The CUB4TC offers cold junction
compensation and a mVDC display mode with a range of -10.00 to 60.00 mV.
Programmable features include temperature type, Fahrenheit or Celsius display,
input filtering range, and user offset.
SAFETY SUMMARY
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
MODEL NO.
CUB4RT
CUB4TC
DIMENSIONS In inches (mm)
These CUB4 temperature meters are 9 to 26 VDC powered, microprocessor
All safety related regulations, local codes, and instructions that appear in the
MLPS
CAUTION: Read complete instructions prior to installation and
RTD Indicator, Reflective LCD
RTD Indicator, Red Backlit Transmissive LCD
Thermocouple Indicator, Reflective LCD
Thermocouple Indicator, Red Backlit Transmissive LCD
Micro Line/Sensor Power Supply
UL Recognized Component,
File # E179259
operation of the unit.
DESCRIPTION
Note: Recommended minimum clearance (behind the panel) for
PART NUMBER
CUB4RT00
CUB4RT20
CUB4TC00
CUB4TC20
MLPS1000
mounting clip installation is 2.1" (53.3) H x 3.0" (76.2) W.
1
SPECIFICATIONS
1. DISPLAY: Reflective LCD or Transmissive LCD with red backlight, 5 digit
2. POWER: 9 to 26 VDC @ 65 mA with backlight, 25 mA without backlight.
3. TEMPERATURE EFFECTS:
4. ENVIRONMENTAL CONDITIONS:
5. MAIN SENSOR INPUT RANGES AND ACCURACIES
!
!
!
!
!
!
!
!
!
display 0.48"(12.2 mm) height, F or C annunciator.
Reverse polarity protected.
Must use the MLPS or a Class 2 or SELV rated power supply.
CUB4TC Backlight version: 0.15
CUB4RT Span Drift: 100 ppm/°C Max
CUB4TC Span Drift: 150 ppm/°C Max.
Zero Drift: < 1 V/°C Max.
Operating Temperature Range: 0 to 50 °C
Storage Temperature Range: -30 to 85 °C
Operating and Storage Humidity: 85% max. relative humidity
Altitude: Up to 2000 meters (6561 feet)
Isolation: The sensor input and excitation, if applicable are not isolated from
Response Time: 500 msec
Failed Sensor Display: OPEN
Overrange/Underrange Input: OLOL/ULUL
Overrange/Underrange Display: “…..”/”-…..”
Normal Mode Rejection: 40 dB @ 50/60 Hz
Common Mode Rejection: 100 dB @ DC to 60 Hz
CUB4TC - Thermocouple types T, E, J, K, R, S, B, N, or mV
CUB4RT - RTD types Pt385, Pt392, Ni672, Cu427
TRANSMISSIVE WITH RED BACKLIGHT
PROGRAMMABLE INPUTS
PROGRAMMABLE TEMPERATURE OFFSET
SELECTABLE F or C WITH 1 or 0.1 RESOLUTION
F OR C DISPLAY ANNUNCIATORS
CONFORMS TO ITS-90 TEMPERATURE SCALE
COLD JUNCTION COMPENSATION (Enable/Disable) CUB4TC
0.48 INCH (12.2 mm) HIGH DIGITS
5 DIGIT LCD, POSITIVE REFLECTIVE OR NEGATIVE
NEMA 4X/IP65 SEALED FRONT BEZEL
than 12 VDC. May be compensated with offset.
Example: 24 VDC supply, (24V-12V)*0.15 °C/V = 1.8 °C,
(non-condensing) from 0 to 50 °C.
the power supply.
Accuracies reflect ALL errors @ 12 VDC supply and 15 minute warm-up,
except probe errors and lead resistance effects.
Enter -1.8 °C user offset.
PANEL CUT-OUT
°
C/Volt CJC error if powered from other
Bulletin No. CUB4RT/TC-X
Drawing No. LP0583
Effective 10/04

CUB4TC00 Summary of contents

Page 1

... CUB4RT00 Overrange/Underrange Display: “…..”/”-…..” Normal Mode Rejection 50/60 Hz CUB4RT20 Common Mode Rejection: 100 CUB4TC00 Accuracies reflect ALL errors @ 12 VDC supply and 15 minute warm-up, except probe errors and lead resistance effects. CUB4TC20 MLPS1000 Note: Recommended minimum clearance (behind the panel) for mounting clip installation is 2.1" ...

Page 2

SPECIFICATIONS (Cont’d) CUB4TC Thermocouple Inputs: ACCURACY* ACCURACY* TC DISPLAY RANGE @ 23° 50°C TYPE ±°C -200 to 400° 2.3 -328 to 752°F -200 to 1372° 2.3 -328 to 2502°F -200 to 760°C J ...

Page 3

WIRING CONNECTIONS All conductors should meet voltage and current ratings of the unit. Also, cabling should conform to appropriate standards of good installation, local codes and regulations recommended that power supplied to the unit be protected by a ...

Page 4

This program item sets the display for Fahrenheit or Celsius and whole number or tenths. Tenths is not available for thermocouple types R, S, and B. To ...

Page 5

Voltage Calibration Diagram 1. Connect a precision Voltage Source with an output range of 0.000 to 105.000 mV and an accuracy of 0.03% or better to the SIG+ (#3) and SIG- (#5) terminals. Placement of jumper does not affect voltage ...

Page 6

VOLTAGE CALIBRATION Voltage Calibration Wiring 1. Connect a precision Voltage Source with an output range of -10.000 to 60.000 mV and an accuracy of 0.03% or better to the TC- (#5) and TC+ (#3) terminals. Cold junction calibration must be ...

Page 7

INSTALLATION The meter meets NEMA 4X/IP65 requirements for indoor use, when properly installed. The units are intended to be mounted on an enclosed panel. The viewing window and buttons are factory sealed for a wash down environment. A sponge rubber ...

Page 8

... The Company disclaims all liability for any affirmation, promise or representation with respect to the products. The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries, deaths, property ...