K3HB-RNB 24VAC/VDC Omron, K3HB-RNB 24VAC/VDC Datasheet

no-image

K3HB-RNB 24VAC/VDC

Manufacturer Part Number
K3HB-RNB 24VAC/VDC
Description
ROTARY PULSE INDICATR NPN/V INPT
Manufacturer
Omron
Series
K3HBr
Type
Pulse Meterr
Datasheet

Specifications of K3HB-RNB 24VAC/VDC

Measuring Range
0 ~ 50kHz
Display Style
Green, Red Characters, Black Background
Display Type
LCD
Display Face Size
3.78" L x 1.89" W (96.0 x 48.0mm)
Display Digits
5
Display Digits - Height
0.193" (4.90mm), 0.559" (14.20mm)
Backlight
Green, Red
Mounting Type
Panel Mount
Termination
Screw Terminals
Voltage - Supply
24VAC/DC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
K3HB-RNB24VAC/VDC
K3HBRNB24VACVDC
• Easy recognition of judgment results using two-color
• Equipped with a position meter for monitoring
• External event inputs allows using various
• Series expanded to include DeviceNet models.
• Short body with depth of only 95 mm (see note)
• UL certification (Certification Mark License).
• CE Marking conformance by third party assessment
• Water-resistant enclosure conforms to NEMA 4X
Note: Depth of 97 mm for DeviceNet models.
The K3HB Series has been made complete with
the addition of Digital Signal Input Models.
Features
Red-Green Display Allows Easy
Recognition of Judgment Results
The measurement value display can be set to switch between red
and green in accordance with the status of comparative outputs. This
means that the status can be easily seen at a distance.
Position Meter Enables Easy Monitoring of
Operating Status Trends
The present value with respect to the measurement or display range
(full scale) can be viewed on a bar display. The operating status can
be grasped intuitively, allowing easy judgment of levels and threshold
values.
Note: This function is different from the single-LED display of the K3HB-C.
Short Body with Depth of Only 95 mm
(from Behind the Front Panel)
A short body of only 95 mm (see note) contributes to the
development of slimmer and smaller control panels and installations.
Note: Depth of DeviceNet models is 97 mm.
display that can be switched between red and green.
operating status trends.
measurement and discrimination applications.
(from behind the front panel).
body.
(equivalent to IP66).
Digital Indicators
K3HB Series (Pulse Input Series)
(The depth is 100 mm when mounted to the terminal cover.)
Refer to Common Precautions on page 30.
MAX/MIN
HH
LL
Depth:
H
P
L
Max
B
Min
L
95 mm
CMW
Hold
LEVEL
T
(See note.)
MODE
HH
LL
H
L
SHIFT
UP
Digital Indicators
than earlier
shorter
models
27%
Position meter
K3HB Series (Pulse Input Series)
50 kHz High-speed Pulse Measurement
(K3HB-R)
Supports high-speed pulse measurement (up to 50 kHz) of rotary
encoders or any ON/OFF pulse signal, which enables rotational
measurement of objects rotating at high speeds.
Note: No-voltage contacts of up to 30 Hz are supported.
Measurement of Wide Range of Pulse
Interval Times (K3HB-P)
Measures and displays the results of the pulse interval between two
points. The pulse interval measurement range is broad, from 10 ms
to 3,200 s.
High-speed Up/Down Counting Pulse
Measurement (K3HB-C)
Perfect for high-speed measurement of rotary encoders or any
ON/OFF pulse signals. Cumulative pulse input is 50 kHz, quadrature
pulse inputs are 25 kHz, and up/down pulse inputs are 30 kHz.
Note: No-voltage contacts of up to 30 Hz are supported.
10 ms to 3200 s
50 kHz
50 kHz
1

K3HB-RNB 24VAC/VDC Summary of contents

Page 1

... MAX/MIN LEVEL MODE SHIFT Note: This function is different from the single-LED display of the K3HB-C. Short Body with Depth of Only 95 mm (from Behind the Front Panel) A short body of only 95 mm (see note) contributes to the development of slimmer and smaller control panels and installations. ...

Page 2

... K3HB Series (Pulse Input Series) 2 Digital Indicators PASS: SPDT C1 ...

Page 3

... Inputs: Passing speed, cycle, time difference, time band, measuring length, interval • Measurement ranges: Functions F1, F3, and F4 3200 s Function F2: Functions F5 and F6: ■ K3HB-C Up/Down Counting Pulse Indicator (Page 15) Measuring and Monitoring High-speed Up/Down Pulses Up/down Counting Pulse Input Model: K3HB-C K3HB-CNB: NPN input/voltage pulse input • ...

Page 4

... Refer to Common Precautions on page 30. Model Number Structure ■ Model Number Legend Base Units and Optional Boards can be ordered individually or as sets. Base Units K3HB Input Sensor Codes NB: NPN input/voltage pulse input PB: PNP input 5. Supply Voltage ...

Page 5

... DC power supply models. The OMRON S8VS-series DC Power Supply Unit is recommended. 2. PNP input types are also available. 3. For K3HB-series DeviceNet models, use only the DeviceNet Connector included with the product. The crimp terminals provided are for Thin Cables max. ...

Page 6

... Voltage Dips and Interruptions Immunity EN61000-4-11: 0.5 cycle, 0 /180 100% (rated voltage) 6 Rotary Pulse Indicator Must have a switching capacity higher. Must be able to properly switch load currents less sweeps of 5 min each and Z directions 2 2 (100 m/s for relay outputs) 3 times each in 3 axes, 6 directions K3HB-R ...

Page 7

... These calculations are automatically made internally and displayed whenever any input pulse is received. Measuring roller winding speed Prescale value ( ) 1/N 1/60 N 1/60 1/60000 1000 d/60 N 100 d/60 N d/60 N d/N 0.06 d/N 60 Frequency ( Rotation speed (rpm) Operation image (application) Measuring motor speed (for product testing) K3HB-R Rotary Pulse Indicator PASS L OK/NG judgment 7 ...

Page 8

... Measuring the line speed error ratio between two conveyors Measuring the rotation (rpm)/circumferential speed error (absolute error) between two conveyors Monitoring liquid mixture flow rate ratio Displaying the passing time for a conveyor line L/( d/N) K3HB-R Operation image (application PASS L LL ...

Page 9

... Contact 10 11 Note: Set to or The largest measurement range is 30 Hz. Rotary Pulse Indicator is set, the frequency can be force-set to zero if Meaning Prescale value menu setting Minute display h.mm.ss display mm.ss.d display (d = tenths of a second when there is a large variation in the display. K3HB-R 9 ...

Page 10

... Refer to Common Precautions on page 30. Model Number Structure ■ Model Number Legend Base Units and Optional Boards can be ordered individually or as sets. Base Units K3HB Input Sensor Codes NB: NPN input/voltage pulse input PB: PNP input 5. Supply Voltage ...

Page 11

... DC power supply models. The OMRON S8VS-series DC Power Supply Unit is recommended. 2. PNP input types are also available. 3. For K3HB-series DeviceNet models, use only the DeviceNet Connector included with the product. The crimp terminals provided are for Thin Cables max. ...

Page 12

... Must have a switching capacity higher. Must be able to properly switch load currents less sweeps of 5 min each and Z directions 2 2 (100 m/s for relay outputs) 3 times each in 3 axes, 6 directions K3HB-P •Voltage pulse OFF voltage Input impedance •Open collector will malfunction if a pulse greater than the input frequency range is input ...

Page 13

... T, then system clock count (0.5 s) 100,000 (the passing speed) is calculated internally 1 using the formula 60 (m/min), and the T 1 display, in this example, would be 0.05 s 1200 (m/min). Operation image (application) Measuring the length of a workpiece step by changing prescale values. K3HB-P 60= 13 ...

Page 14

... Measuring slit intervals Input Type Setting No-contact or voltage pulse input Contact Note: Set when there is a large variation in the display. The largest measurement range is 30 Hz. K3HB-P Operation image (application) Managing the valve release time Communications output BCD To Programmable Controller H PASS L OK judgment ...

Page 15

... This is effective for feed amount and position monitor displays. Refer to Common Precautions on page 30. Model Number Structure ■ Model Number Legend Base Units and Optional Boards can be ordered individually or as sets. Base Units K3HB Input Sensor Codes NB: NPN input/voltage pulse input PB: PNP input 5 ...

Page 16

... Note power supply models require a control power supply capacity of approximately 1 A per Unit when power is turned ON. Particular attention is required when using two or more DC power supply models. The OMRON S8VS-series DC Power Supply Unit is recommended. 2. For K3HB-series DeviceNet models, use only the DeviceNet Connector included with the product. The crimp terminals provided are for Thin Cables. 16 Up/Down Counting Pulse Indicator : 4 mA max ...

Page 17

... Up/Down Counting Pulse Indicator ON voltage OFF voltage Input impedance 4 Note: The Up/Down Counting Pulse Meter will malfunction if a pulse greater than the input frequency range is input. SYSERR may appear on the display. K3HB-C 17 ...

Page 18

... Counting the number of people entering an area Increment Detecting position and speed on a semiconductor wafer conveyor line Counting the number of workpieces Short-circuit Open NC: Voltage pulse low 01 11 K3HB-C Operation image (application) Photoelectric sensor To BCD output Programmable Controller Decrement Wafer E6L BCD output To Programmable Controller ...

Page 19

... Prescaling converts the count value to any numeric value. To display @@@@.@ system that outputs 250 pulses for a 0.5-m feed, the length per pulse = 500 mm (0 The prescale value for the K3HB-C is set using the mantissa X so the prescale value = 2.0000 × 10° 2.000, and Y = 00. ...

Page 20

... MIN RESET Outputs DATA POLARITY OVER DATA VALID RUN K3HB-R PASS L LL Refer to the K3HB Communications User's Manual (Cat. No. N129) for details on serial and DeviceNet communications. 100 A max Item K3HB-C Input signal No-voltage contact input REQUEST COMPEN- Input current for 10 mA ...

Page 21

... DeviceNet power supply 50 mA max. (24 VDC) 64 (DeviceNet Configurator is counted as one node when connected.) 63 CRC errors Supplied from DeviceNet communications connector Digital Indicators Drop line length Total drop line length (max.) (max max max max max max. 156 m max. K3HB-R/-P/-C 21 ...

Page 22

... Only one of the following can be used for each Digital Indicator: communications, BCD, or DeviceNet Sensor 12 VDC power 80 mA supply B6 <A> Sensor power supply + communications N Sensor 12 VDC 12 VDC power supply B6 RS-485 RS-232C <FLK3A> <FLK1A> K3HB-R/-P/-C 22 Digital Indicators Relay Outputs Transistor Outputs <C1> <C2> <T1> <T2> COM C3 PASS ...

Page 23

... Applicable Connector (Sold separately) XG4M-1030 (OMRON) Special Cable (Sold separately) K32-DICN (OMRON) (XG4M-1030 with 3-m cable) The following signals depend on the model: S-TMR: Used by the K3HB-R only. COMPENSATION: Used by the K3HB-C only. Shape Connected device end (PLC, display device, etc.) 300 mm 46 ...

Page 24

... Waveform Event input circuit shaping circuit Linear output Drive Linear output circuit circuit Sensor power Filter supply V O Power supply circuit (isolated) Power supply K3HB-R/-P/-C 24 Digital Indicators 60 Keys Indications Transistor Drive circuit output Micro- computer Drive X Relay output circuit Drive ...

Page 25

... DATA VALID signal turns ON. The DATA VALID signal will turn OFF 40 ms later, and the data will turn OFF 16 ms after that. • The K3HB BCD output model has an open collector output, so wired OR connection is possible K3HB (1) ...

Page 26

... HH, H, comparative set value HH displayed. K3HB-P Indicator Function H In RUN level, turn ON when the HH comparative set value HH displayed. K3HB-C Indicator Function Turns ON when parameters for which T teaching can be performed are 3 displayed RUN level, turn ON when the comparative set value displayed. UP Key ...

Page 27

... Insert the adapter into the grooves on the left and right sides of the rear case and push until it reaches the panel and is fixed in place. LCD Field of Vision The K3HB is designed to have the best visibility at the angles shown in the following diagram Waterproof Packing The waterproof packing ensures a level of waterproofing that conforms to NEMA 4X ...

Page 28

... The K3HB-P has the following six functions for receiving and displaying input pulses. F1: Passing speed F2: Cycle F3: Time difference F4: Time band F5: Measuring length F6: Interval The K3HB-C has the following three functions for receiving and displaying input pulses. F1: Individual inputs F2: Phase differential inputs F3: Pulse counting input Filters avg-t, avg-n Average Processing Average processing of input signals with extreme changes or noise smooths out the display and makes control stable ...

Page 29

... A set of set comparative values can be selected as a group. copy Bank Copy Any bank settings can be copied to all banks. memo C Interruption Memory The measured value can be recorded when the power supply is interrupted User Calibration The K3HB can be calibrated by the user. K3HB-R/-P/-C Digital Indicators 29 ...

Page 30

... I/O memory of other nodes, check the nodes to confirm safety. Changing the program or I/O memory of other nodes may occasionally cause unexpected operation, resulting in minor or moderate injury, or damage to the equipment. K3HB-R/-P/-C 30 Digital Indicators Precautions for Safe Use 1. Do not use the product in the following locations. ...

Page 31

... If a noise filter is used for the power supply, check the voltage and current, and install the noise filter as close to the product as possible. 5. Reception interference may occur if the product is used close to a radio, television, or wireless. Digital Indicator Surge absorber Digital Indicator Digital Indicators K3HB-R/-P/-C 31 ...

Page 32

... Warranty and Limitations of Liability ■ WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE ...

Page 33

... Cancellation; Etc. Orders are not subject to rescheduling or cancellation unless Buyer indemnifies Omron against all related costs or expenses. 10. Force Majeure. Omron shall not be liable for any delay or failure in delivery resulting from causes beyond its control, including earthquakes, fires, floods, strikes or other labor disputes, shortage of labor or materials, accidents to machinery, acts of sabotage, riots, delay in or lack of transportation or the requirements of any government authority ...

Page 34

Cat. No. N135-E1-02 1/06 Specifications subject to change without notice Printed in USA ...