K3HB-XVD 100-240VAC Omron, K3HB-XVD 100-240VAC Datasheet - Page 24

PROCESS INDICATR DC VOLTAG INPUT

K3HB-XVD 100-240VAC

Manufacturer Part Number
K3HB-XVD 100-240VAC
Description
PROCESS INDICATR DC VOLTAG INPUT
Manufacturer
Omron
Series
K3HBr
Type
Process Meterr
Datasheet

Specifications of K3HB-XVD 100-240VAC

Measuring Range
0 ~ 199.99V
Display Style
Green, Red Characters, Black Background
Display Type
LCD
Display Face Size
3.78" L x 1.89" W (96.0 x 48.0mm)
Display Digits
5
Display Digits - Height
0.193" (4.90mm), 0.559" (14.20mm)
Backlight
Green, Red
Mounting Type
Panel Mount
Termination
Screw Terminals
Voltage - Supply
100 ~ 240VAC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
K3HB-XVD100-240VAC
K3HBXVD100240VAC
Common Specifications
■ Event Input Ratings
■ Output Ratings
Contact Output
Linear Output
Serial Communications Output
Note: For details on serial and DeviceNet communications, refer to
Contact
No-contact
Rated load
Rated through
current
Mechanical life
expectancy
Electrical life
expectancy
Allowable load impedance
Resolution
Output error
Communications method Half duplex
Synchronization method Start-stop synchronization
Baud rate
Transmission code
Data length
Stop bit length
Error detection
Parity check
the Digital Indicator K3HB Communications User's Manual
(Cat.No. N129).
Item
Input type
Item
Item
5 A at 250 VAC
5 A at 30 VDC
5A
5,000,000 operations
100,000 operations
30 VDC, L/R=0 ms)
(250 VAC, cosφ=1;
Resistive loads
9,600, 19,200, or 38,400 bps
ASCII
7 bits or 8 bits
2 bits or 1 bit
Vertical parity and FCS
Odd, even
ON: 1 kΩ max., OFF: 100 kΩ min.
ON residual voltage: 2 V max.
OFF leakage current: 0.1 mA max.
Load current: 4 mA max.
Maximum applied voltage: 30 VDC max.
500 Ω max.
Approx. 10,000
±0.5%FS
S-TMR, HOLD, RESET, ZERO, BANK1, BANK2,
RS-232C, RS-485
0 to 20 mA
30 VDC, L/R=7 ms)
(250 VAC, closed
circuit, cosφ=0.4;
Inductive loads
1 A at 250 VAC
1 A at 30 VDC
BANK4
4 to 20 mA
Transistor Output
Maximum load voltage
Maximum load current
Leakage current
5 kΩ min.
---
ON residual voltage: 3 V max.
OFF leakage current: 1.5 mA max.
Load current: 17 mA max.
Maximum applied voltage: 30 VDC max.
0 to 5 V
Panel Meter Series
24 VDC
50 mA
100 µA max.
1 to 5 V
Timing
K3HB
0 to 10 V
B-31