CUB50000 Red Lion Controls, CUB50000 Datasheet

COUNTER/RATE INDICATOR RELFECT

CUB50000

Manufacturer Part Number
CUB50000
Description
COUNTER/RATE INDICATOR RELFECT
Manufacturer
Red Lion Controls
Series
CUB5r
Datasheet

Specifications of CUB50000

Count Rate
20kHz
Number Of Digits/alpha
8
Input Type
Voltage
Voltage - Supply
9 V ~ 28 V
Display Type
LCD Non-Backlit
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Output Type
-
Other names
Q517088
RLC500
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion-controls.com
MODEL CUB5 -
!
!
!
DESCRIPTION
indicator and two counters). The display can be toggled either manually or
automatically between the rate and counter(s) display.
available in Positive Image Reflective (CUB50000), Negative Image-
Transmissive with yellow/green backlighting (CUB50010), or Negative Image-
Transmissive with red backlighting (CUB50020).
The counters and rate indicator have separate scaling and decimal point
placement for read-outs in different engineering units.
signal for the Count display or direction control. In the anti-coincidence mode,
both inputs are monitored simultaneously so that no counts are lost. The final
count can be chosen as the sum or difference of the two inputs. The Rate
Indicator has programmable low (minimum) and high (maximum) update times
to provide optimal display response at any input frequency. There is a
programmable user input that can be set for one of a variety of functions.
viewing window. The sealed front panel meets NEMA 4X/IP65 specifications
for wash-down and/or dusty environments, when properly installed.
Supply (MLPS0000) attached directly to the rear of a CUB5. The MLPS0000
is powered from either a 115 or 230 VAC source.
LCD, POSITIVE REFLECTIVE OR NEGATIVE TRANSMISSIVE
0.46 INCH (11.7 mm) HIGH DIGITS
PROGRAMMABLE DECIMAL POINT
DIMENSIONS In inches (mm)
WITH YELLOW/GREEN OR RED LED BACKLIGHTING
The CUB5 provides up to three functions in a single display package (rate
The CUB5 display has 0.46" (11.7 mm) high digits. The LCD display is
The counters may be programmed for one of eight different count modes.
Input A accepts a signal for the Count and Rate displays. Input B accepts a
The unit is housed in a lightweight, high-impact plastic case with a clear
The CUB5 can be powered from an optional RLC Micro Line/Sensor Power
instructions prior to installation
and operation of the unit.
CAUTION: Read complete
MINIATURE ELECTRONIC 8-DIGIT DUAL COUNTER & RATE INDICATOR
CAUTION: Risk of electric shock.
Note: Recommended minimum clearance (behind the panel) for mounting clip installation is 2.15" (54.6) H x 3.00" (76.2) W.
1
!
!
!
!
!
!
!
!
!
!
!
!
SAFETY SUMMARY
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
SPECIFICATIONS
1. DISPLAY: 8 digit LCD 0.46" (11.7 mm) high digits
2. POWER REQUIREMENTS:
3. MEMORY: Nonvolatile E
4. USER INPUT: Programmable, connect to common to activate function.
5. INPUTS A and B:
QUADRATURE SENSING (Up to 4 Times Resolution)
FRONT PANEL AND REMOTE RESET
COUNT SPEEDS UP TO 20 KHz (High Speed Input)
OPERATES FROM 9 to 28 VDC POWER SOURCE
PROGRAMMABLE PRESCALER FOR TOTALING
BI-DIRECTIONAL COUNTING, UP/DOWN CONTROL
ANTI-COINCIDENCE COUNTING (ADD/ADD & ADD/SUB)
SEPARATE COUNT AND RATE INPUT MODE
WIRE CONNECTIONS MADE VIA SCREW CLAMP TYPE
DUAL COUNTER MODE
COUNT INPUT VOLTAGE UP TO +28 VDC
NEMA 4X/IP65 SEALED FRONT BEZEL
TERMINALS
All safety related regulations, local codes and instructions that appear in the
Transmissive red or yellow/green backlight, or Reflective. The viewing
angle of a transmissive display is designed for viewing at eye level or above
the display. Reflective display units have a full viewing angle.
Reflective Versions: 9 to 28 VDC @ 15 mA max.
Backlight Versions: 9 to 28 VDC @ 60 mA max.
Must use an RLC model MLPS or a Class 2 or SELV rated power supply.
parameters and the count value when power is removed.
Threshold Levels: V
Response Time: 50 msec for Inhibit function, 100 msec for all others.
Current Sinking: Internal 40 KΩ typical. Pull-up to +5 V.
Current Sourcing: External pull-down resistor required, 2KΩ max.
Trigger Levels: V
Max Input Frequency: 20 KHz, 50% duty cycle.
Current Sinking: Internal 40 KΩ typical. Pulled-up to +5 V.
Current Sourcing: External pull-down resistor required, 2 KΩ max.
Filter A and B: Limits Input signal to a max. frequency of 100 Hz. Connect
Above 24 VDC, derate operating temperature to 50°C.
to common to activate.
IH
= 4.2 V min, V
IH
= 4.2 V min, V
2
PROM memory retains all programming
IL
= 0.5 V max, V
IL
= 0.5 V max, V
Bulletin No. CUB5-H
Drawing No. LP0268
Released 6/02
MAX
MAX
= 28 VDC.
= 28 VDC.

CUB50000 Summary of contents

Page 1

... The display can be toggled either manually or automatically between the rate and counter(s) display. The CUB5 display has 0.46" (11.7 mm) high digits. The LCD display is available in Positive Image Reflective (CUB50000), Negative Image- Transmissive with yellow/green backlighting (CUB50010), or Negative Image- Transmissive with red backlighting (CUB50020). ...

Page 2

... If all P’s appear in the display, press the select (SEL) button and check all of the data setups. The CUB5 can be programmed to function as a single counter, dual counters, single counter with rate indication or dual counters with rate indication. ...

Page 3

... When the count mode INP A-b is programmed for “dUAL cnt” the front panel reset button can be enabled to reset: - (total) Counter total) Counter B - (both) Counters A and B - (diSPLy) Displayed count - (NONE) None. If “NONE” is selected, neither counter can be reset from the front panel. ...

Page 4

... Counter - (b totAL) “B” Counter - (both) “A” and “B” Counters 17. FACTORY SETTINGS (FACt SEt) All of the parameters are restored to the factory default settings when YES is selected and the front panel select button is pressed. The CUB5 displays “ ...

Page 5

SCALING FOR RATE INDICATION Scaling the Rate channel involves programming the CUB5 so that input pulses to the unit are scaled to the desired display units. Note not necessary to increase the pulse information to obtain higher resolution. ...

Page 6

INSTALLATION ENVIRONMENT The unit should be installed in a location that does not exceed the maximum operating temperature and provides good air circulation. Placing the unit near devices that generate excessive heat should be avoided. The bezel should be cleaned ...

Page 7

... Dual Counter & Rate Indicator w/Red Backlighting Micro Line/Sensor Power Supply 7 0.0 Desired Display Units x Decimal Point Position Number of Pulses 1 0.3125 YES 0.0 15.0 GPM pulses per unit rAtE dSP x desired time format 15 8.0 Hz 1.0 sec. 5.0 sec. PART NUMBERS CUB50000 CUB50010 CUB50020 MLPS0000 ...

Page 8

... The Company disclaims all liability for any affirmation, promise or representation with respect to the products. The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries, deaths, property ...