Y92S-33 Omron, Y92S-33 Datasheet
Y92S-33
Specifications of Y92S-33
Y92S-33 Summary of contents
Page 1
Total Counter/Time Counter (DIN 72 x 36) H7HP DIN 72 x 36-mm Total Counter/Time Counter with Easy-to-read Displays and Water and Oil Resistance Equivalent to IP66 • Large, easy-to-read displays: 15-mm-high characters for 6-digit models; 12-mm-high characters for 8-digit models. ...
Page 2
Specifications ■ Ratings Item 6-digit total counter/time counter H7HP-A Rated supply voltage 100 to 240 VAC (50/60 Hz VDC (see note 1) 100 to 240 VAC (50/60 Hz VDC (see note 1) External power ...
Page 3
Characteristics Insulation resistance 100 MΩ min. (at 500 VDC) Dielectric strength 2,000 VAC, 50/60 Hz for 1 min between current-carrying terminal and exposed non-current-carrying metal parts (AC model) 1,000 VAC, 50/60 Hz for 1 min between current-carrying terminal and ...
Page 4
Connections ■ Terminal Arrangement Note: 1. Incremented for count 1 (CP1) inputs; decremented for count 2 (CP2) inputs. 2. Non-contact input is also available. AC Models H7HP-A External power supply 100 to 240 VAC 12 VDC 50 mA max. Power ...
Page 5
Operating Modes Total Counters Reset input CP1 CP2 999999 (see note) Display 0 −99999 (see note) Note: Display values are shown for a 6-digit model. The count value will return to "0" when "999999" is exceeded. Time Counters Reset ...
Page 6
... Panel cutouts are as shown below (according to DIN43700). With Flush Mounting Bracket M3.5 terminal screw Terminal cover (provided) Note: 1. The mounting panel thickness should mm. 2. Water resistance will be lost if Counters are mounted side-by-side. Y92F-33 flush mounting Y92S-33 rubber Panel adaptor (provided) packing (provided) H7HP 6 ...
Page 7
Connections (Common) ■ Input Connections Note: The following is common for all H7GP/H7HP models. No-voltage Input (NPN Input Mode) Reset, Count 1, Count 2, Start, and Gate Inputs Open Collector Output Voltage Output H7GP/H7HP 12 VDC ( VDC) ...
Page 8
Safety Precautions (Common) Refer to Safety Precautions for All Counters. Note: The following is common for all H7GP/H7HP models. !CAUTION This may occasionally cause electric shock, fire, or malfunction. Never disassemble, repair, or modify the H7GP/H7HP. This may occasionally cause ...
Page 9
Precaution for Correct Use Power Supplies When turning the power ON and OFF, input signal reception is possible, unstable, or impossible as shown in the diagram below. Apply the power supply voltage through a relay or switch in such ...
Page 10
... Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS ...