B84299D1151E3 EPCOS Inc, B84299D1151E3 Datasheet - Page 2

FILTER POWER LINE 150A 250/440V

B84299D1151E3

Manufacturer Part Number
B84299D1151E3
Description
FILTER POWER LINE 150A 250/440V
Manufacturer
EPCOS Inc
Datasheets

Specifications of B84299D1151E3

Filter Type
Power Line
Voltage - Rated
250V, 440V
Current
150A
Mounting Type
Chassis Mount
Termination Style
Stud Lug
Operating Frequency
50 to 60Hz
Current Rating (max)
150A
Voltage Rating Max
250VAC/250VDC
Termination
Screw
Mounting Style
Flange
Voltage Rating
440 VAC / 250 VAC
Current Rating
150 A
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Inductance
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
2- and 4-line-filters
16 to 150 A
Multi-stage
Stopband attenuation 14 kHz to 40 GHz
Features
Design
The electrical components are incorporated in an RF-tight case of stainless steel. The cables
enter through glands. The RF-tight termination of the openings is produced by specially shaped
lids.
The conductors and equipment grounding conductor are connected by threaded bolts. The sur-
face around the fixing holes is left as bare metal (unpainted) to ensure good RF contact with met-
al surfaces (chassis, ground).
Protective measures (grounding)
The high capacitances between the lines and ground require special protective measures. If there
are no product-specific requirements, protection with a secondary ground wire (cross section min.
10 mm
necting bolts at each end.
Resistors are incorporated in the filter to discharge capacitors after turn-off.
Scope of supply
Filters are supplied complete with all parts required for RF-tight installation (fixing screws,
flanges, RF gaskets, cable glands) and installation instructions.
Installation
No welding is needed on the shielding wall, so any subsequent installation is quite simple.
Accessories and special versions
RF-tight flexible connector fittings are available for installation spaced away from the shielding
wall. Filters with an EMP protection add-on for surge currents up to 100 kA per line are available
on request. To match requirements, filters can be supplied with different kinds of EMC or shield-
ing cable glands.
Tests
All filters are 100% tested and the results are archived under a filter's serial number. If required, a
test report can be generated for the serial number.
Filters for power lines
16 to 150 A, 100 dB from 14 kHz
General-purpose use through design with separate lines without intercoupling
Use of single chokes. Thus the insertion loss values are not reduced under all operating cur-
rent conditions and not when operated with artificial mains networks (AMN) or other equipment
with high leakage currents.
Insertion loss to CISPR 17
2
) in accordance with EN 50178 is necessary. For this purpose the filter case have con-
2
B84299*B003
B84299*E003