Specifications of B84263C23B13

Filter Type
Power Line
Voltage - Rated
250V
Current
40A
Mounting Type
Chassis Mount
Termination Style
Stud Lug
Voltage Rating
250 VAC
Current Rating
40 A
Mounting Style
Screw
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Inductance
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Filters for Power Lines
(Low leakage current)
16 to 100 A,
100 dB from 14 kHz
Series/Type:
B84263
Date: January 2004
EPCOS AG 2004. Reproduction, publication and dissemination of this data sheet, enclosures hereto and the
information contained therein without EPCOS' prior express consent is prohibited.
Purchase orders are subject to the General Conditions for the Supply of Products and Services of the Electrical
and Electronics Industry recommended by the ZVEI (German Electrical and Electronic Manufacturers' Associ-
ation), unless otherwise agreed.

Related parts for B84263C23B13

B84263C23B13 Summary of contents

Page 1

... Filters for Power Lines (Low leakage current 100 A, 100 dB from 14 kHz Series/Type: B84263 Date: January 2004 EPCOS AG 2004. Reproduction, publication and dissemination of this data sheet, enclosures hereto and the information contained therein without EPCOS' prior express consent is prohibited. Purchase orders are subject to the General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry recommended by the ZVEI (German Electrical and Electronic Manufacturers' Associ- ation), unless otherwise agreed ...

Page 2

... RF gaskets, cable glands) and installation instructions. Installation No welding is needed on the shielding wall, so any subsequent installation is quite simple. And the uniform template of the attachment points allows straightforward replacement of 2-line filters by 4-line filters for example. Accessories and special versions RF-tight flexible connector fittings are available for installation spaced away from the shielding wall ...

Page 3

... Filters for power lines (low leakage current 100 A, 100 dB from 14 kHz Circuit diagrams 2-line filters 4-line filters 3 B84263 ...

Page 4

... Filters for power lines (low leakage current 100 A, 100 dB from 14 kHz Insertion loss (typical values Asymmetrical measurement circuit to MIL-STD-220A General technical data Rated voltage 2-line filters Rated voltage 4-line filters Rated frequency Rated current Maximum admissible overcurrent Test voltage Voltage drop/phase Maximum DC resistance ) V 250 ...

Page 5

... Characteristics and ordering codes I Mechanical max D version 2-line filters 16 C < 40 < < 40 < < 20 < < 20 < 60 4-line filters 16 C < 80 < < 80 < < 30 < 140 < 2 < 30 < 140 < 2.5 100 C < 6 < 70 100 D < 6 < 180 < 2 See characteristics D I See characteristics ...

Page 6

... Filters for power lines (low leakage current 100 A, 100 dB from 14 kHz Dimensional drawings Dimensional drawing 1 (cable glands at both ends) B84263C0022B013 Input end: Cable gland PG 21 (mounted) Shielded end: Cable gland PG 29/21 (cable gland PG 29 and reducer ring in accessory bag) Paint color: RAL 7035 (light gray, semigloss) ...

Page 7

... Filters for power lines (low leakage current 100 A, 100 dB from 14 kHz Dimensional drawing 2 (direct connection to shielding wall) B84263D0022B013 Input end: Cable gland PG 21 (mounted) Shielded end: Cable gland PG 29/21 (cable gland PG 29 and reducer ring in accessory bag) Paint color: RAL 7035 (light gray, semigloss) ...

Page 8

... Filters for power lines (low leakage current 100 A, 100 dB from 14 kHz Dimensional drawing 3 (cable glands at both ends) B84263C0023B013 Input end: Cable gland PG 21 (mounted) Shielded end: Cable gland PG 29/21 (cable gland PG 29 and reducer ring in accessory bag) Paint color: RAL 7035 (light gray, semigloss) ...

Page 9

... Filters for power lines (low leakage current 100 A, 100 dB from 14 kHz Dimensional drawing 4 (direct connection to shielding wall) B84263D0023B013 Input end: Cable gland PG 21 (mounted) Shielded end: Cable gland PG 29/21 (cable gland PG 29 and reducer ring in accessory bag) Paint color: RAL 7035 (light gray, semigloss) ...

Page 10

... Filters for power lines (low leakage current 100 A, 100 dB from 14 kHz Dimensional drawing 5 (cable glands at both ends) B84263C1160E003 Input end: Cable gland PG 29/21 (PG 29 mounted and reducer ring in accessory bag) Shielded end: Cable gland PG 29/21 (cable gland PG 29 and reducer ring in accessory bag) ...

Page 11

... Filters for power lines (low leakage current 100 A, 100 dB from 14 kHz Dimensional drawing 6 (direct connection to shielding wall) B84263D1160E003 Input end: Cable gland PG 29/21 (PG 29 mounted and reducer ring in accessory bag) Shielded end: Cable gland PG 29/21 (cable gland PG 29 and reducer ring in accessory bag) ...

Page 12

... Filters for power lines (low leakage current 100 A, 100 dB from 14 kHz Dimensional drawing 7 (cable glands at both ends) B84263C1400E003 Input end: Cable gland PG 29/21 (PG 29 mounted and reducer ring in accessory bag) Shielded end: Cable gland PG 29/21 (cable gland PG 29 and reducer ring in accessory bag) ...

Page 13

... Filters for power lines (low leakage current 100 A, 100 dB from 14 kHz Dimensional drawing 8 (direct connection to shielding wall) B84263D1400E003 Input end: Cable gland PG 29/21 (PG 29 mounted and reducer ring in accessory bag) Shielded end: Cable gland PG 29/21 (cable gland PG 29 and reducer ring in accessory bag) ...

Page 14

... Filters for power lines (low leakage current 100 A, 100 dB from 14 kHz Dimensional drawing 9 (cable glands at both ends) B84263C1101E003 Input end: Cable gland PG 42/29 (PG 42 mounted and reducer ring in accessory bag) Shielded end: Cable gland PG 42/29 (cable gland PG 42 and reducer ring in accessory bag) ...

Page 15

... Filters for power lines (low leakage current 100 A, 100 dB from 14 kHz Dimensional drawing 10 (direct connection to shielding wall) B84263D1101E003 Input end: Cable gland PG 42/29 (PG 42 mounted and reducer ring in accessory bag) Shielded end: Cable gland PG 42/29 (cable gland PG 42 and reducer ring in accessory bag) ...

Page 16

... Filters for power lines (low leakage current 100 A, 100 dB from 14 kHz RF-tight connection to shielding wall with connector fitting (mechanical version C) Cable Connector fitting (must gland be ordered separately Nominal width Nominal width 40 mm (***: add required length in cm (see also chapter "Installation accessories"). ...