FN2412-25-33 Schaffner EMC Inc, FN2412-25-33 Datasheet - Page 2

FILTER EMC/RFI DIN RAIL MNT 25A

FN2412-25-33

Manufacturer Part Number
FN2412-25-33
Description
FILTER EMC/RFI DIN RAIL MNT 25A
Manufacturer
Schaffner EMC Inc
Series
FN 2412r
Type
Filterr
Datasheet

Specifications of FN2412-25-33

Termination Style
Terminal Block
Filter Type
Power Line
Voltage - Rated
250V
Current
25A
Mounting Type
DIN Rail
Voltage Rating
300 VAC
Current Rating
25 A
Mounting Style
DIN Rail
Filtered
Yes
Frequency
400 Hz
Leakage Current
3.4 mA
Product
Power Line Filters
Type Of Inlet
Power Line
Brand/series
FN 2412 Series
Current, Rating
25 A
Dimensions
87 H × 93 W × 110 L mm
Hipot Rating, Line To Ground
2000
Hipot Rating, Line To Line
1100
Ip Rating
IP20
Phase
1
Primary Type
AC, Industrial
Schaffner Part Number
801-530
Voltage, Operating
250 VAC
Voltage, Rating
250 VAC
Wire Size
6 AWG
Design Corresponding To
UL1283, CSA22.2 No. 8 1986, EN 133'200
High Potential Test Voltage
P → E 2000VAC for 2 Seconds
Svhc
No SVHC (18-Jun-2010)
External Depth
87mm
External Length / Height
110mm
External Width
93mm
No. Of Phases
2
Voltage Rating Vac
250V
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Inductance
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
801-530
817-1359
FN2412 - 25-33
Filter selection table
Filter
FN 2410-8-44
FN 2410-16-44
FN 2410-25-33
FN 2410-32-33
FN 2410-45-33
FN 2410-60-34
FN 2410-80-34
FN 2410-100-34
FN 2410H-8-44
FN 2410H-16-44
FN 2410H-25-33
FN 2410H-32-33
FN 2410H-45-33
FN 2410H-60-34
FN 2410H-80-34
FN 2410H-100-34
FN 2412-8-44
FN 2412-16-44
FN 2412-25-33
FN 2412-32-33
FN 2412-45-33
FN 2412H-8-44
FN 2412H-16-44
FN 2412H-25-33
FN 2412H-32-33
FN 2412H-45-33
*
Typical filter attenuation
Per CISPR 17; A = 50Ω/50Ω sym; B = 50Ω/50Ω asym; C = 0.1Ω/100Ω sym; D = 100Ω/0.1Ω sym
8 to 45A types
> Components
Maximum leakage under normal operating conditions. Note: if the neutral line is interrupted, worst case leakage could reach twice this level.
> FN 2410 / FN 2412
Rated current
@ 50°C (40°C)
100 (109.5)
100 (109.5)
60 to 100A types
16 (17.5)
25 (27.4)
32 (35.0)
45 (49.3)
60 (65.7)
80 (87.6)
16 (17.5)
25 (27.4)
32 (35.0)
45 (49.3)
60 (65.7)
80 (87.6)
16 (17.5)
25 (27.4)
32 (35.0)
45 (49.3)
16 (17.5)
25 (27.4)
32 (35.0)
45 (49.3)
8 (8.8)
8 (8.8)
8 (8.8)
8 (8.8)
[A]
Leakage current*
@ 230VAC/50Hz
[mA]
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
@ 25°C/50Hz
Power loss
15.4
15.4
[W]
2.6
3.5
5.5
5.6
7.4
5.5
9.9
2.6
3.5
5.5
5.6
7.4
5.5
9.9
2.6
3.5
5.5
5.6
7.4
2.6
3.5
5.5
5.6
7.4
Input/Output
connections
-44
-44
-33
-33
-33
-34
-34
-34
-44
-44
-33
-33
-33
-34
-34
-34
-44
-44
-33
-33
-33
-44
-44
-33
-33
-33
Weight
[kg]
0.4
0.5
0.6
0.7
0.7
1.8
1.8
1.8
0.5
0.6
0.7
0.8
0.8
1.9
1.9
1.9
0.4
0.6
0.7
0.8
0.8
0.5
0.7
0.8
0.9
0.9

Related parts for FN2412-25-33