W2G115-AG71-12 EBM-Papst Industries Inc, W2G115-AG71-12 Datasheet - Page 7

FAN 127 X 38MM 24VDC

W2G115-AG71-12

Manufacturer Part Number
W2G115-AG71-12
Description
FAN 127 X 38MM 24VDC
Manufacturer
EBM-Papst Industries Inc
Series
W2G115r
Type
Tubeaxialr

Specifications of W2G115-AG71-12

Bearing Type
Ball
Fan Type
Tubeaxial
Size / Dimension
Square - 127mm L x 127mm H x 38mm W
Voltage - Rated
24VDC
Power (watts)
12.0W
Features
Locked Rotor Sensor
Rpm
4050 RPM
Noise
52 dB(A)
Air Flow
160.0 CFM (4.53m³/min)
Termination
2 Terminals
Weight
1.2 lbs (544.3g)
Voltage Range
16 ~ 28VDC
Termination Style
52 dB(A)
External Height
127mm
External Width
127mm
External Depth
38mm
Current Type
DC
Supply Voltage
24VDC
Flow Rate
160CFM
Noise Rating
52dBA
Power Connection Type
Terminal
Brand/series
W2G117
Dimensions
127 x 127 x 38 mm
Noise Level
52 dBA
Power Rating
12 W
Size
5 x 1.5 (127 x 38) In. (mm)
Voltage, Rating
24 V
Flow Rate - Imperial
160CFM
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Static Pressure
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
381-1068
W2G115-AG71-13
W2G115AG7112
W2G115AG7113
4.5 Checking the connections
4.6 Switch on device
4.7 Switching off the device
Item no.: 50987-5-9970 · Revision status: KM72138 · Print-out on 02/12/2010 · Created by A. Kehm (VM---) · Page 7 of 8
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone: +49(0)7938/81-0 · Fax: +49(0)7938/81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
W2G115-AG71-12
Make sure that the power is off (all phases).
Secure it from being switched on again.
Check that the mating connector is correctly locked into the panel
connector.
Check that the mating connector is correctly crimped to the
connection line.
Inspect the device for visible external damage and the proper function
of the protective features before switching it on.
Check the air flow paths of the fan for foreign objects and remove any
that are found.
Apply the nominal voltage to the voltage supply.
Start the device by changing the input signal.
Disconnect the device from the supply voltage.
WARNING
Hot motor housing
Fire hazard
Ensure that no combustible or flammable materials are
located close to the fan.
Operating instructions
5. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES
Motor and electronics enclosure are sealed by ebm-papst. Changes or
repairs may be carried out by ebm-papst only.
Do not perform any repairs on your device. Return the device to ebm-
papst for repair or replacement.
Malfunction/error
Motor does not turn
Impeller running
roughly
Overtemperature of
electronics/motor
WARNING
Terminals and connections have voltage even with a
unit that is shut off
Electric shock
CAUTION
If control voltage is applied or a speed setpoint is stored,
the motor automatically restarts, e.g. after a power failure.
Danger of injury
If the device remains out of use for some time, e.g. when in
storage, we recommend switching the device on for at least 2
hours to allow any condensate to evaporate and to move the
bearings.
Wait for five minutes after disconnecting the voltage at all
poles before touching the unit.
Keep out of the danger zone of the device.
When working on the device, switch off the mains
supply voltage and secure the latter from being switched on
again.
Wait until the device stops.
Possible cause
Mechanical blockage
Mains supply
voltage faulty
Faulty connection
Imbalance in rotating
parts
Insufficient cooling
Ambient temperature
too high
Possible remedy
Switch off, de-
energise, and
remove mechanical
blockage
Check mains supply
voltage, restore
power supply
apply control signal
Correct connection,
see connection diagram
Clean the device; if
imbalance is still
evident after
cleaning, replace
device.
If you have
attached any weight
clips during cleaning,
make sure to
remove them
afterwards.
Improve cooling if
possible.
Reset by switching
off the mains supply
voltage for at least
20 s after motor
standstill
Lower ambient
temperature if
possible.

Related parts for W2G115-AG71-12