LSA2B Honeywell, LSA2B Datasheet - Page 3

Basic / Snap Action / Limit Switches 0.75 -14NPT 2NC/2NO DPDT

LSA2B

Manufacturer Part Number
LSA2B
Description
Basic / Snap Action / Limit Switches 0.75 -14NPT 2NC/2NO DPDT
Manufacturer
Honeywell
Type
Limit Switchr
Series
HDLSr
Datasheets

Specifications of LSA2B

Pole Throw Configuration
DPDT
Switch Function Configuration
N.O./N.C.
Operating Temp Range
-12C to 121C
Contact Form
DPDT
Contact Rating
10 Amps
Operating Force
0.45 N
Termination Style
Screw
Current Rating (max)
10 Amps
Voltage Rating Ac
600 Volts
Voltage Rating Dc
250 Volts
Actuator Type
Side Rotary
Current, Rating
10 A
Ip Rating
NEMA 1, 3, 4, 4X, 6, 6P, 12, 13
Mounting Hole Size
0.203 In.
Mounting Type
Mount by either of two methods: (a) use two #10 screws from the front, or (b) use two #10-32 UNF screws from the back.
Standards
UL Listed, CSA Certified, CE Marked, EN Approved, NEMA Approved
Temperature, Operating
-20 to 121 °C
Termination
Screw
Voltage, Rating
600/250 VAC/VDC
Lead Free Status / RoHS Status
Compliant

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
LSA2B
Manufacturer:
honeywell
Quantity:
200
Part Number:
LSA2B
Manufacturer:
honeywell
Quantity:
200
Part Number:
LSA2B-1A
Manufacturer:
honeywell
Quantity:
200
Part Number:
LSA2B-1B
Manufacturer:
honeywell
Quantity:
200
Part Number:
LSA2B-1D
Manufacturer:
honeywell
Quantity:
200
Rotary Actuated Switches
ACTUATION DIRECTION
(Drawings apply to listings on facing page only).
HEAD ORIENTATION
ASSEMBLY MODIFICATIONS
How to order
Momentary action rotary switches can be
furnished in other than the normal assem-
bled conditions described on the facing
page. To specify modifications, add the
number(s) shown below to the catalog list-
ings. Prices are the same as their counter-
parts shown in the order guide.
Modification number suffixes are:
Examples:
Catalog Listing LSA1A23 is an LSA1A switch
adjusted for counterclockwise operation
only. The operating shaft is to the right side
of the switch when viewing it from the front
(label side). No lever.
Catalog Listing LSA8A7 is an LSA8A switch
with the 240 volt indicator light wired to the
N.C. circuit. No lever.
Switches with assembly modifications are
not normally stocked and may extend deliv-
ery leadtimes.
A34
1 Clockwise operation only
2 Counterclockwise operation only
3 Shaft to right of switch front
4 Shaft to left of switch front
5 Shaft to back of switch
7 Indicator light wired to N.C. circuit
Mod. 5
Mod. 4
CW & CCW
(Normal)
Honeywell
Sensing and Control 1-800-537-6945 USA
(Normal)
Front
Mod. 3
Mod. 1
CW
10 amps continuous carry (except for elec-
ELECTRICAL RATINGS
trical rating ‘‘C’’). Circuits on any one pole
must be the same polarity.
AC Volts
Pilot duty: 600 VAC, 720VA
DC Volts
Pilot duty: 240 VDC, 30 watts
*For switches with indicator light, use only at voltage stated for indicator light.
**These switches have either gold plated or gold cross point contacts. Cross point contacts improve high
reliability of contact make when particle contamination is a problem or low energy loads must be carried.
Electrical
Electical
Rating
Rating
C**
C**
A*
A*
B
D
B
D
1-815-235-6847 International 1-800-737-3360 Canada
Single-Pole
Double-Throw
Double-Pole
Double-Throw
Single-Pole
Single-Throw
Normally Closed
Single-Pole
Double-Throw
Single-Pole
Double-Throw
Double-Pole
Double-Throw
Single-Pole
Single-Throw
Normally Closed
Single-Pole
Double-Throw
Mod. 2
CCW
Circuitry
Circuitry
LEVERS
Levers for rotary actuated switches are nor-
mally ordered as separate catalog listings.
They also may be ordered by including a
suffix to the switch catalog listing and add-
ing the lever price. See pages A34-A39.
SWITCHES FOR SPECIAL
APPLICATIONS
HDLS limit switches for special application
needs are described on pages A42 and A43.
They include: manifold mount, low temper-
ature, complete fluorocarbon-sealed, grav-
ity return, extra low torque and 20 Amp
switches.
Adapter plates for interchanging HDLS with
LS/200LS limit switches are described on
page A49.
VAC
VDC
120
240
480
600
120
240
480
600
120
240
480
600
120
240
120
240
120
250 VAC or 60 VDC, .050 amp max.
30
250 VAC or 60 VDC, .050 amp max.
Amps at 0.35 Power Factor
Inductive
Make
Make and Break Amps
60
30
15
12
30
15
7.5
6
60
30
15
12
0.25
0.15
0.25
0.15
4.3
1.1
Resistive
Break
6
3
1.5
1.2
3
1.5
0.75
0.60
6
3
1.5
1.2
0.8
0.4
0.8
0.4
4.3
1.1