15.904 Altech, 15.904 Datasheet - Page 2

no-image

15.904

Manufacturer Part Number
15.904
Description
Circuit Breakers MA0.6 0.40-0.63A Motor Protector
Manufacturer
Altech
Series
MAr
Datasheet

Specifications of 15.904

Product Type
Circuit Breakers
Current Rating
0.63 Amp
Voltage Rating
277 VoltsAC
Mounting Style
DIN Rail
Termination Style
Screw
Circuit Function
ON/OFF
Features
Adjustable Trip Miniature Circuit Breakers/ Manual Motor Controllers
Height
89.5 mm
Illuminated
No
Length
68 mm
Product
Thermal Magnetic Circuit Breakers
Width
44 mm
Number Of Poles
3 Poles
Actuator Type
Handle
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
MA/USA Manual Motor Con trol ler
DIMENSIONS
Altech Corp.
6mm (.24 in.)
17.5mm (0.69 in.)
25.5mm (1.0 in.)
7mm (.28 in.)
®
• 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
O OFF
(.28 in.)
37.5mm (1.48 in.)
7mm
52.5mm (2.07 in.)
(1.20 in.)
30.5mm
44mm (1.73 in.)
44mm (1.73 in.)
68mm (2.68 in.)
O OFF
O OFF
120
120
0.6
0.4
0.2
0.1
0.6
0.4
0.2
0.1
60
40
20
10
40
20
10
60
40
20
10
40
20
10
6
4
2
1
6
4
2
1
6
4
2
1
6
4
2
1
1 1.15 1.5
11.15 1.5
MA20UM-MA40UM
MA 3 Phase Controller
Thermal Overload (B, C, D)
“Must Trip” Current = 115% of Dial Setting
“Must Not Trip” > 1 hr = 105% of Dial Setting
Multiple of Dial Setting (Thermal)
Multiple of Rated Current (Magnetic Trip)
Rated Current = Max. Dial Setting
Multiple of Dial Setting (Thermal)
Multiple of Rated Current (Magnetic Trip)
Rated Current = Max. Dial Setting
MA016UM-MA16UM
MA 3 Phase Controller
Thermal Overload (B, C, D)
“Must Trip” Current = 115% of Dial Setting
“Must Not Trip” > 1 hr = 105% of Dial Setting
Magnetic Trip
Nominal 1100% of Rated Current
Magnetic Trip
Nominal 1100% of Rated Current
2 2.3
2 2.3 3
3
4 5 6 6.9 8 1012
4 5 6 6.9 8 10 12
12.5
15
16 19
45

Related parts for 15.904