LPS-RK-1-8/10SP Cooper/Bussmann, LPS-RK-1-8/10SP Datasheet

LPS-RK-1-8/10SP

Manufacturer Part Number
LPS-RK-1-8/10SP
Description
Manufacturer
Cooper/Bussmann
Type
Dual Elementr
Datasheet

Specifications of LPS-RK-1-8/10SP

Acting
Slow Blow
Voltage Rating (vac)
600V
Voltage Rating (vdc)
300V
Current Rating
1.8A
Mounting
Surface Mount
Product Depth (mm)
Not Requiredmm
Product Height (mm)
Not Requiredmm
Lead Free Status / RoHS Status
Compliant
LOW-PEAK
Dual-Element, Time-Delay Fuses
Class RK1 – 600 Volt
Catalog Symbol: LPS-RK_SP
Dual-Element, Time-Delay – 10 seconds (minimum) at 500%
Current-Limiting
Ampere Rating: ⁄Ω ¡ º to 60A
Voltage Rating: 600Vac (or less)
Interrupting Rating:
ac: 300,000A RMS Sym.
dc: 100,000A
Agency Information:
UL Listed, Special Purpose**, Guide JFHR, File E56412
CSA Certified, (200,000AIR), Class RK1 per CSA C22.2,
**Meets all performance requirements of UL Standard 248-12 for Class RK1 fuses.
Catalog Symbol and Amperes
LPS-RK-⁄Ω ¡ ºSP
LPS-RK-¤Ω ¡ ºSP
LPS-RK-‹Ω ¡ ºSP
LPS-RK-›Ω ¡ ºSP
LPS-RK-⁄Ω ™ SP
LPS-RK-flΩ ¡ ºSP
LPS-RK-°Ω ¡ ºSP
LPS-RK-1SP
LPS-RK-1⁄Ω • SP
LPS-RK-1⁄Ω ¢ SP
LPS-RK-1›Ω ¡ ºSP
Carton Quantity and Weight
Ampere
Ratings
0–30
35–60
*Weight per carton.
7-25-03
rated current
No. 248.12, Class 1422-02, File 53787
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
A03014
LPS-RK-1⁄Ω ™ SP
LPS-RK-1flΩ ¡ ºSP
LPS-RK-1°Ω ¡ ºSP
LPS-RK-2⁄Ω ¢ SP
LPS-RK-2⁄Ω ™ SP
LPS-RK-2°Ω ¡ ºSP
LPS-RK-3SP
LPS-RK-3¤Ω ¡ ºSP
LPS-RK-3⁄Ω ™ SP
LPS-RK-4SP
LPS-RK-4⁄Ω ™ SP
Carton
300Vdc (or less)
Qty.
10
10
®
LPS-RK-5SP
LPS-RK-5flΩ ¡ ºSP
LPS-RK-6SP
LPS-RK-6⁄Ω ¢ SP
LPS-RK-7SP
LPS-RK-8SP
LPS-RK-9SP
LPS-RK-10SP
LPS-RK-12SP
LPS-RK-15SP
LPS-RK-17⁄Ω ™ SP
Lbs.
1.6
2.6
Weight*
LPS-RK-20SP
LPS-RK-25SP
LPS-RK-30SP
LPS-RK-35SP
LPS-RK-40SP
LPS-RK-45SP
LPS-RK-50SP
LPS-RK-60SP
0.725
1.178
Kg.
Features:
• Current-limitation for maximum short-circuit protection.
• Type 2 protection for IEC and NEMA starters when
• High inrush current motor protection.
• Time-delay permits 130% FLA sizing for back-up motor
• Protection against single-phase motor damage.
• Low watt loss power consumption.
• Electrically isolated end caps.
• 300Vdc, UL Listed.
Applications:
• Branch distribution
• Motors
• Transformers
• Solenoids
• General purpose circuits
Current-Limitation Curve
Dimensional Data
⁄Ω¡ºA to 30A
properly sized.
protection.
( 0.31)
5"
.81" ( 0.008)
RMS SYMMETRICAL CURRENTS IN AM
AÐB=ASYMMETRICAL AVAILABLE P
35A to 60A
(2.3 x SYMM RMS AMPS)
( 0.31)
5.5"
Bussmann
0-60 Amps
LPS-RK
Form No. LPS-RK 0-60
1.06" ( 0.008)
Data Sheet: 1001
Page 1 of 2
®

Related parts for LPS-RK-1-8/10SP

LPS-RK-1-8/10SP Summary of contents

Page 1

... LPS-RK-35SP LPS-RK-40SP LPS-RK-45SP LPS-RK-50SP LPS-RK-60SP — — — Weight* Kg. 0.725 1.178 Bussmann LPS-RK 0-60 Amps 5.5" ( 0.31) .81" ( 0.008) 1.06" ( 0.008) 35A to 60A RMS SYMMETRICAL CURRENTS IN AM AÐB=ASYMMETRICAL AVAILABLE P (2.3 x SYMM RMS AMPS) Form No. LPS-RK 0-60 Page Data Sheet: 1001 ® ...

Page 2

... Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. 7-25-03 A03014 AMPERE RATING Bussmann ® LPS-RK 0-60 Amps CURRENT IN AMPERES Form No.LPS-RK 0-60 Page Data Sheet: 1001 ...

Related keywords