LRCD220 Megger, LRCD220 Datasheet - Page 2

TESTER, LOOP+RCD

LRCD220

Manufacturer Part Number
LRCD220
Description
TESTER, LOOP+RCD
Manufacturer
Megger
Datasheet

Specifications of LRCD220

Insulation Tester Type
RCD
Insulation Test Resistance
2kohm
Operating Temperature Range
-5°C To +40°C
External Height
203mm
External Width
148mm
External Depth
78mm
Weight
980g
Battery Size Code
AA
External
RoHS Compliant
Additionally for the LRCD220
RCD Testing
Testing the trip times of RCDs with all commonly found
RCD current ratings.
For most international applications and the UK, 5 tests
must be performed:
1) 1/2 x RCD current rating, to ensure the RCD does not
2) 1 x RCD current rating. This is a trip test to ensure the
3) 5 x RCD current rating. A Trip test to ensure the RCD
4 & 5) both the 1x and 5x tests must be performed at both
All LRCD testers offer:
Additionally the LRCD210 and LRCD220 offers:
plus the LRCD220 offers:
1/2 x I and 5 x I RCD testing
0 degrees and 180 degrees (positive and negative supply
half cycles) to ensure worst case time is recorded.
10 mA to 500 mA RCD testing
PFC calculation and display from the loop test
measurement
Supply voltage display on connection to circuit.
Supply frequency measurement
2-wire fast test is provided
415 V Phase to Phase loop measurement
110 V operation
Backlit LCD display
Phase rotation display
1 x I RCD Test
AC, AC selective, DC and DC selective RCD type
selection
0/180 degree selection
Ramp testing
25 V or 50 V Touch voltage selection
Optional Touch voltage display
1000 mA RCD testing
Display backlight
Test lock
trip when half the rated current is flowing in the RCD.
RCD trips with the specified trip time.
trips within the specified time.
Additionally, instruments for non-UK markets can operate
with the Live/Neutral supply reversed.
Selection Guide
Loop testing
Non tripping loop test
PFC
Single phase
Hi current loop test
Phase to phase
3 phase safe
Voltmeter
RCD test
1/2 x I test
1 x I test
5 x I Test
Touch/ Contact
voltage display
Selectable 25/50 V
touch voltage
10, 30,100, 300,
500 mA ranges
1000 mA
AC, AC Selective, DC &
DC Selective RCD tests
Selectable phase 0/180
Ramp test (20% to 110%)
General testing
Frequency
Phase rotation
Reverse polarity operation
(Continental instruments only)
Backlight
Mechanical
BS1363, CEE7/7, AS/
NZS 3112 plug variants
IP54
Working voltage 230 V
Working voltage 110
& 230 V
Phase rotation display
Combined Loop and RCD Testers
LRCD200 LRCD210 LRCD220
(not UK)
LRCD200 Series