T+PRO-1AC KIT Fluke, T+PRO-1AC KIT Datasheet - Page 2

ELECTRICAL TESTER 10.2 - 600V, LCD COLOR

T+PRO-1AC KIT

Manufacturer Part Number
T+PRO-1AC KIT
Description
ELECTRICAL TESTER 10.2 - 600V, LCD COLOR
Manufacturer
Fluke
Datasheets

Specifications of T+PRO-1AC KIT

Voltage Measuring Range Ac
10.2 - 600 V
Meter Display Type
LCD Color
Operating Temperature Range
-10°C To +55°C
Voltage Measuring Range Dc
10.2 - 600 V
No. Of Batteries
2
Lead Free Status / RoHS Status
na
Features and Benefits contd.
1
 Fluke Corporation
Specifications
When used properly per Article 110.9 Use of Equipment (A) Test Instruments and Equipment.
Temperature
Relative humidity
Altitude
Battery type/life
Shock, vibration
Safety
AC Bandwidth
Maximum working voltage
Maximum measurable voltage
Duty cycle
Replaceable test probes for added flexibility and
convenience
Convenient probe storage on the back
Probe holder for easier testing
Hazardous voltage warning light for added user
protection
Test lead strap included for better test lead
management
AC/DC Voltage: 1 V – 600 V on LED bar, 10. V
– 600 V on LCD (LCD on T+PRO only)
Auto-off saves battery power
-year warranty
Operating
Storage
Operating
Storage
Fluke T+ and T+PRO Electrical Testers
-10 °C to 55 °C (14 °F to 131 °F)
-30 °C to 60 °C (- °F to 140 °F)
0 °C to 30 °C (3 °F to 86 °F): 90 %
30 °C to 40 °C (86 °F to 104 °F): 75 %
40 °C to 50 °C (104 °F to 1 °F): 45 %
,000 m (approx. 6,561.6 ft)
10,000 m (approx. 3,808.4 ft)
AAA (); 40 hours
Sinusoidal vibration per MIL-PRF-8800F for a Class  instrument
ISA-8.0.01 (IEC 61010-1 Mod) Second Edition, CAN/CSA-C. No. 61010-1
Second Edition, IEC 61010 - 1 to 1000 V CAT III/600 V CAT IV
Compliance to NFPA 70E
45 Hz to 66 Hz
1000 V ac/dc
600 V ac/dc
Indefinitely for voltages up to 40 V.
For voltages between 40 V and 600 V the duty cycle is 30 s on / 300 s off.
For voltages above 40 V the tester must connect to a voltage source only for a
MAXIMUM of 30 s and then disconnect for a MINIMUM of 300 s.
Added functionality available only
on the T+PRO
Backlit LCD display for easier viewing
Display resolution of 0.1 V, ideal for
troubleshooting low-voltage lighting
Resistance (Ohms) to 9.99 kOhms
Rotary Field Indication
Display Hold for easier viewing in hard-to-test
areas
1