G32J-CA20 Omron, G32J-CA20 Datasheet
G32J-CA20
Specifications of G32J-CA20
Related parts for G32J-CA20
G32J-CA20 Summary of contents
Page 1
... B: Screw terminals (screw clamps) ❍ 5. Control Voltage ❍ AC100-240: 100 to 240 VAC 50/60 Hz AC/DC24: Accessories G32J-@@ 1. Option CA: Auxiliary Contact Block 2. Number of Contacts 10 20 G32J-@ 1. Option Motor CF64: Fan TA10: Round Terminal Block Adapter − ) wiring. CSM_G3JA-C_DS_E_5_1 VAC 50/60 Hz, 24 VDC ...
Page 2
... When replacing G3JA-C (version 2) with G3JA-D, refer to “Three-phase, 6-wire Motors (Star-delta Wiring)” list above. ■ Accessories (Order Separately) Product name Model Auxiliary Contact Blocks G32J-CA10 G32J-CA20 G32J-CA01 G32J-CA11 Fan G32J-CF64 Round Terminal Block Adapters G32J-TA10 Note: Refer to Safety Precautions on page 16. ...
Page 3
Specifications ■ Ratings and Characteristics Ratings Item Model G3JA-C403 Rated operating current 3 A Heat dissipation, continuous 11 W Rated operating voltage of main circuit 200 to 480 VAC (±10%), 50/60 Hz (±5%), 3-phase Main circuit power Wire gauge 2.5 ...
Page 4
... Voltage range Overvoltage category Input onstate voltage minimum during start (A1, A2) 90 VAC max. (100 to 240 VAC), 15.2 VAC/21.6 VDC max. (24 VAC/DC) Input onstate current, during start with the G32J- CF64 Fan (IN1, IN2) Input offstate voltage maximum (A1, A2) Offstate current consumption (IN1, IN2) ...
Page 5
Environmental Conditions Item Classification Ambient operating temperature 0 to 50°C −25 to 85°C Ambient storage temperature Elevation 2,000 m max. Ambient operating humidity 5% to 85% (with no condensation) Pollution degree 2 Degree of protection IP20 Other Specifications Item Classification ...
Page 6
Connections ■ Wiring Two-wire Connections Fuse, NF breaker, etc - GRD -E1 G3JA *2 Main circuit -SB terminals E-STOP Start/Stop Motor -M ...
Page 7
Examples: Main Circuit Fault Shutoff Fuse, NF breaker, etc - Transformer * - GRD -E1 *3 G3JA Main circuit ...
Page 8
Operation ■ Operating Modes Soft Start A soft start is used to reduce mechanical shock when starting the motor. The motor voltage is increased from the initial torque to full voltage. The initial torque can be set to 15%, 25%, ...
Page 9
Description of Functions Overload Protection The G3JA-C is equipped with overload protection. The overload class can be set to OFF, 10, 15, or 20. Either automatic or manual mode can be used to reset an overload (trip). Set the ...
Page 10
Nomenclature ■ Part Names and Functions Upgraded Models Production of a new version of the Soft Starter (version 2) with added functions was started in August 2008. The DIP switch settings of the new version are different from the previous ...
Page 11
DIP Switch Settings Start Time t1 DIP switch pins Time (seconds OFF OFF OFF 2 ON OFF OFF 5 OFF ON OFF OFF 15 OFF OFF OFF ON 25 OFF ...
Page 12
Engineering Data Trip Curves Trip Class 10 1,000 Cold trip 100 Hot trip 10 1 100 1,000 Current (%) ■ Dimensions Note: All models are the same size regardless of the capacity. Mounting Dimensions for the Auxiliary Contact Block ...
Page 13
Upgrades for Version 2 ■ Upgrades 1. Control of 3-phase, 6-wire motors (star-delta wiring) is supported. 2. The soft start time can be set ■ Previous Version The DIP switch settings are different for the ...
Page 14
Comparison of DIP Switch Setting Differences 1. Start Time Previous version DIP switch pins 1 2 OFF OFF Not used ON OFF OFF --- 2. Auxiliary Contact and Optional Auxiliary Contact Block (New Version) Auxiliary Contact (Previous ...
Page 15
... Terminals on the G3JA, tighten the screws again on the main G32J-CA10 terminals of the G3JA and the Terminal Block Adaptor to the specified tightening torque once wiring is completed. Note: 1. The Round Terminal Block G32J-CA20 Adaptor (G32J-TA10) is delivered with the cover removed. 2. The mounting strength of the ...
Page 16
... Altitude Derating The rated current of the G3JA must be decreased at altitudes above 2,000 m because of decreased efficiency of the heat sink and fan (G32J-CF64). Warning Labels Included with Product If voltage is applied to the main circuit power supply side of the G3JA, there will be voltage in the terminals on the main circuit load side even if the G3JA is OFF ...
Page 17
Connecting a Power Capacitor If you use a power capacitor, connect it to the primary side (i.e., power supply side) of the G3JA output terminals. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To ...
Page 18
... Cancellation; Etc. Orders are not subject to rescheduling or cancellation unless Buyer indemnifies Omron against all related costs or expenses. 10. Force Majeure. Omron shall not be liable for any delay or failure in delivery resulting from causes beyond its control, including earthquakes, fires, floods, strikes or other labor disputes, shortage of labor or materials, accidents to machinery, acts of sabotage, riots, delay in or lack of transportation or the requirements of any government authority ...
Page 19
... São Paulo, SP, Brasil • 55.11.2101.6300 • www.omron.com.br OMRON ELECTRONICS MEXICO • HEAD OFFICE Apodaca, N.L. • 52.811.156.99.10 • 001.800.556.6766 • mela@omron.com OMRON EUROpE B.V. Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands. Tel: +31 (0) 23 568 13 00 Fax: +31 (0) 23 568 13 88 www.industrial.omron.eu CSM_G3JA-C_DS_E_5_1 12/09 OMRON ARGENTINA • ...