E8CC-AN0C Omron, E8CC-AN0C Datasheet

PRESSURE SENSOR

E8CC-AN0C

Manufacturer Part Number
E8CC-AN0C
Description
PRESSURE SENSOR
Manufacturer
Omron
Series
E8CCr
Type
Gager
Datasheets

Specifications of E8CC-AN0C

Pressure Type
Gauge
Operating Pressure
-14.65 ~ +0 PSI, -101 ~ 0 kPa
Port Size
Male, 1/8" (3.175mm) 27 NPT
Output
Digital
Voltage - Supply
12 V ~ 24 V
Termination Style
Cable
Operating Temperature
-10°C ~ 55°C
Package / Case
Module
Output Voltage Range
1 to 5V
Pressure Range
-101 to 0KPa
Mounting
Din-Rail
Pin Count
4
Operating Temp Range
-10C to 55C
Operating Temperature Classification
Commercial
Operating Supply Voltage (typ)
15/18V
Operating Supply Voltage (min)
12V
Operating Supply Voltage (max)
24V
Mounting Style
DIN Rail
Maximum Operating Temperature
+ 55 C
Minimum Operating Temperature
- 10 C
Operating Supply Voltage
15 V, 18 V
Output Voltage
1 V to 5 V
Sensor Type
Sensors
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
E8CCAN0C
Ordering Information
J SENSOR
Digital display Pressure range
No
Yes
Pressure Sensor
Flat-pack, Slim, DIN-rail Mount
Pressure Sensor
H
H
H
H
Withstands a pressure of 490 kPa
(71 psi)
Easy pressure setting with a two-turn
pressure adjuster
Linear analog output
E8CC has digital display
Positive pressure
Negative pressure
Positive pressure
Negative pressure
Positive pressure
R
0 to 98 kPa
(0 to 14.2 psi)
0 to - - 101 kPa
(0 to - - 14.6 psi)
0 to 98 kPa
(0 to 14.2 psi)
0 to - - 101 kPa
(0 to - - 14.6 psi)
0 to 980 kPa
(0 to 142.1 psi)
ON/OFF output
NPN open collector
2
Linear
output
1 to 5 V
Part number
E8CB-01C
E8CB-CN0C2B
E8CC-A01C
E8CC-AN0C
E8CC-B10C
E8CB/E8CC

Related parts for E8CC-AN0C

E8CC-AN0C Summary of contents

Page 1

... Negative pressure 101 kPa ( 14.6 psi) Yes Positive pressure kPa (0 to 14.2 psi) Negative pressure 101 kPa ( 14.6 psi) Positive pressure 0 to 980 kPa (0 to 142.1 psi) ON/OFF output Linear Part number output NPN open collector E8CB-01C E8CB-CN0C2B E8CC-A01C E8CC-AN0C E8CC-B10C 2 E8CB/E8CC ...

Page 2

... FS ± 1 digit max. within a temperature range from 50°C to 55°C (122°F to 131°F) ±5% FS ± 1 digit max. within a temperature range from 0° 10°C (32°F to 14°F) 3 E8CC-AN0C E8CC-B10C (See Note 2 101 kPa 0 to 980 kPa --- --- ( ...

Page 3

... J TEMPERATURE VS LINEAR OUTPUT FLUCTUATION (TYPICAL) E8CB-01C Temperature (°C) E8CB- E8CC-A01C CN0C2B (See Note 2 (3280 ft times each and Z directions Approx (2.82 oz) J PRESSURE VS LINEAR OUTPUT VOLTAGE (TYPICAL) E8CB-01C 4 E8CB/E8CC E8CC-AN0C E8CC-B10C (See Note 2.) 2 (328 ft/s ) for 2 hours each and Z 2 Pressure (kgf/cm ) ...

Page 4

... J VOLTAGE VS. OPERATING PRESSURE FLUCTUATION (TYPICAL) E8CB-01C Voltage (V) J TEMPERATURE VS. LINEAR OUTPUT FLUCTUATION (TYPICAL) E8CC-A01C Temperature (°C) J LINEARITY (TYPICAL) E8CB-01C Pressure (kgf/cm J VOLTAGE VS. LINEAR OUTPUT FLUCTUATION (TYPICAL) E8CB-01C Voltage (V) J PRESSURE VS. LINEAR OUTPUT VOLTAGE (TYPICAL) E8CC-A01C Pressure (kgf/cm Pressure (cmHg) Pressure (kPa ...

Page 5

... E8CB/E8CC J TEMPERATURE VS. OPERATING PRESSURE (TYPICAL) E8CC-A01C Temperature (°C) J VOLTAGE VS. OPERATING PRESSURE FLUCTUATION (TYPICAL) E8CC-AN0C Voltage (V) J LINEARITY (TYPICAL) E8CC-A01C Pressure (kgf/cm Pressure (kPa) J VOLTAGE VS. LINEAR OUTPUT FLUCTUATION (TYPICAL) E8CC-AN0C Voltage (V) 6 E8CB/E8CC 2 ) ...

Page 6

... Operation J E8CB/E8CC PRESSURE SENSOR Output Model Timing Charts configu- ration NPN E8CB-01C, output E8CC-A01C, E8CC-B10C Pressure Setting 2 (kgf/cm ) Output Indicator E8CB-CN0C2B, E8CC-AN0C Pressure (cmHg) Output Indicator Output Circuits Operation OFF indicator ON OFF 0 Setting - - 76 ON OFF ON OFF 7 Brown Load White (ON/OFF) White (ON/OFF) ...

Page 7

... RUN mode by turning the pressure adjuster. Do not turn the pressure adjuster after it has been set to the desired pressure. Permissible range Positive pressure E8CC-A01C E8CC-B10C kPa 0 to 980 kPa (0 to 14.2 psi 142.1 psi) 8 E8CB/E8CC Negative pressure E8CC-AN0C 101 kPa ( 14.6 psi) --- 101 kPa ( 14.6 psi) ...

Page 8

... Dimensions Unit: mm (inch) J E8CB 26.8 (1.06) J E8CC 36.6 (1.44) 27.4 Operation indicator (1.08) Pressure adjuster 8.5 52.5 (0.34) (2.07) 40.5 (1.59) Two, M4 mounting 3.75 (0.15) holes 19 25 (0.75) (0.98) 4 (0.16) 4-dia. vinyl-insulated round cable (0.12) with 4 cores; standard length 51.2 (2.01) Operation indicator 2 ...

Page 9

... DIN-rail mounting 4-dia. vinyl-insulated round cable with 4 cores; standard length 2.6 (0.10) J DIN-RAIL MOUNTING BRACKET (E8CC) Mounting Fit the front part onto the bracket. • Press the rear part onto the bracket. • Removing Apply a flat-blade screwdriver to the rear hook. Then the • ...

Page 10

... OMRON ELECTRONICS LLC One East Commerce Drive Schaumburg, IL 60173 1-800-55-OMRON Cat. No. CEDSAX4 11/01 OMRON ON- - LINE Global - - http://www.omron.com USA - - http://www.omron.com/oei Canada - - http://www.omron.com/oci Specifications subject to change without notice. OMRON CANADA, INC. 885 Milner Avenue Scarborough, Ontario M1B 5V8 416-286-6465 Printed in U.S.A . ...